Europa Automatic Transfer Switch data sheet EDS1331-002, pp.1-4

Europa

Europa's ATS-CON PME is a contactor-based automatic transfer switch to BS/EN/IEC 60947-6-1: five AC-1 current steps from 40 to 125 A, single phase 230 V or three phase 415 V.

On this page

Overview

Europa's EDS1331-002 data sheet presents the contactor-based ATS-CON family that changes over automatically between mains and generator. The order code takes the form ATS_CON_PME: current is selected as 40, 60, 80, 100 or 125 A and pole count as 2 (single phase 230 V) or 4 (three phase 415 V). The 5 currents and 2 configurations give 10 model rows. The standard is BS/EN/IEC 60947-6-1.

Ratings are stated as AC-1 operational current, each step with a maximum cable size: 10 mm2 for 40 A, 16 mm2 for 60 A, 25 mm2 for 80 A, 35 mm2 for 100 A and 50 mm2 for 125 A. Pages 1-4 also contain the single-phase and three-phase circuit diagrams (contactors KM1 and KM2, mains and generator supplies, load).

Parameter settings are grouped into five timers and relays: the mains failure relay (over- and under-voltage thresholds, hysteresis, delay), the delay-on-start timer (DOST) for the generator, the mains return timer (MRT), the cool-down timer (CDT, generator stop delay) and the changeover timer (DOCT). The changeover delay DOCT must include DOST plus the time the generator needs to reach full speed and correct voltage; in the example a 7 s changeover timer minus a 5 s start timer leaves 2 s for the generator.

The later pages are data sheets for auxiliary relays and timers (the ECPF02 single-phase failure relay, ECPF03/05/08 phase failure relays, ECTON/ECTDOFF timers and GRV8 voltage monitoring relays); these are accessory parts and not the full ATS dimensions or weight. The document opens with a UK installation notice: compliance with the IET wiring regulations, checking connection tightness and not using power tools.

Key points

  1. Order structure ATS_CON_PME: current 40, 60, 80, 100, 125 A; poles 2 (single phase 230 V) or 4 (three phase 415 V); 10 model rows in total.
  2. AC-1 operational current and maximum cable size: 40 A/10 mm2, 60 A/16 mm2, 80 A/25 mm2, 100 A/35 mm2, 125 A/50 mm2.
  3. Standard: BS/EN/IEC 60947-6-1 (low-voltage control gear and switchgear).
  4. Adjustable functions: mains failure relay, delay-on-start (DOST), mains return timer (MRT), cool-down timer (CDT) and changeover timer (DOCT).
  5. DOCT must include DOST plus the generator's speed and voltage build-up time; example 7 s minus 5 s = 2 s.
  6. ECPF02 voltage monitoring relay: 110-240 V AC/DC, 45-65 Hz, hysteresis 5-20%, delay 0.1-10 s, output 1 x SPDT 10 A AC-1.
  7. ECPF02 measures 90 x 18 x 64 mm and weighs 59 g; operating temperature is -20 to +55 C.
  8. Installation notice: IET wiring regulation compliance, connection tightness checks, no power tools.

Using it in design

  • Choose the load current against the AC-1 steps (40-125 A); for loads above 125 A move to another ATS family.
  • Limit cable size to the step's maximum (10-50 mm2); if a larger cable is needed choose the next step or a separate terminal arrangement.
  • Set generator start, changeover and cool-down times with DOST, DOCT and CDT against the generator maker's speed and voltage build-up time.
  • Match the single-phase 230 V or three-phase 415 V choice to the distribution scheme; a contactor-based ATS interrupts supply during transfer, so ride-through must come from the UPS.
  • Do not use the auxiliary relay dimensions as the ATS enclosure size; obtain a separate drawing for the enclosure.

Who should read it

Electrical engineers and installers designing small and medium mains-to-generator changeover.

Document contents

  1. ATS product code and ratings
  2. Wiring diagram and parameter settings
  3. Single-phase and three-phase circuit diagrams
  4. Auxiliary relay and timer data sheets

Publication details

Authors
Europa
Publisher
Europa
Year
Year not stated
Document number
EDS1331-002
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Europa Europa Automatic Transfer Switch data sheet EDS1331-002, pp.1-4. Europa. EDS1331-002. https://www.europa-plc.com/_uploads/www.europa-plc.com/EDS1331002.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.