Exeltech Static Transfer Switch Operation and Installation Manual, p.24
Exeltech
Exeltech's MX series STS manual: an SCR-based static transfer switch in a 4RU cage, 1-3 phase, 85 or 170 A steps at 117 V, with failed-source transfer typically under 4 ms and 98.9% efficiency.
On this page
Overview
Exeltech's 2020 manual describes a static transfer switch (STS) system designed to give an Exeltech inverter system a second AC source. The system consists of a backplane and relay assembly, one or more power-switch modules and a controller module, all installed in a 19 or 23 inch 4RU cage. It can be configured for one, two or three phases, each 85 A (10 kW) or 170 A (20 kW), with a 117 V output.
The operating principle is SCR switching. Good-to-good transfers occur at the current zero cross and so are seamless; detect-and-transfer time for a failed source varies from zero to 4 ms depending on where in the waveform the failure occurs. The manual states most loads are not disturbed by a single-source failure. Three dry-contact alarms, maintenance bypass switch (MBS) lockout terminals and SNMP and Modbus TCP/IP monitoring are standard.
The installation sections cover location, AC wiring and grounding, and start-up: the cage must be where only non-conductive pollution can occur, power is derated by 20% per 10 C above 40 C, and 12 inches at the front, 18 inches at the rear and 1U above must be left clear. Conductor size follows NEC Table 310.16 for a 40 C ambient: 3 AWG for 85 A and 3/0 AWG for 170 A (1/0 AWG with 90 C conductors). The maintenance section lists common maintenance tasks.
The specification section gives electrical and mechanical data for the system, the power-switch module and the controller module: input 90-135 VAC at 58-61 Hz, SCR voltage drop of 1.3 V, and a heat table by load. The manual uses US units (inches, lb, AWG, BTU/hr). Page 24 only notes that a maintenance bypass switch is recommended; the model rows on the specification page are the two ratings, 10 kW and 20 kW.
Key points
- Two model rows: 10 kW (85 A) and 20 kW (170 A), 117 V output, 1, 2 or 3 phases.
- Failed-source detect-and-transfer is typically 4 ms; good-to-good transfers are timed to the current zero cross.
- Input is 90-135 VAC at 58-61 Hz; SCR voltage drop is 1.3 V; efficiency is 98.9%.
- Heat dissipation: 221 W (755 BTU/hr) at 170 A and 110.5 W (377 BTU/hr) at 85 A.
- Ambient is -25 to +40 C at full power; derate 20% per 10 C above 40 C; humidity 5-95%; altitude -60 to 1800 m.
- Cage is 7 x 17.2 x 15 in (19 in rack) or 7 x 21.2 x 15 in (23 in rack); clearance is 12 in front, 18 in rear, 1U above.
- Weight: for 85 A, 20.5 lb (1 phase) and 25.5 lb (3 phase); for 170 A, 22.5 lb (1 phase) and 31.5 lb (3 phase).
- Wiring: 3 AWG for 85 A and 3/0 AWG for 170 A (1/0 AWG with 90 C conductors); mechanical lugs 1/0-6 AWG, torque 45 in-lb.
- Three dry-contact alarms; Modbus and SNMP monitoring; a maintenance bypass switch is recommended.
Using it in design
- Select the STS rating (85 or 170 A) from per-phase load current and confirm the 117 V output matches the load voltage; this series is not directly usable at 400 V class facilities.
- Use it for loads that accept up to 4 ms of transfer time (most IT loads) and confirm with the manufacturer for tighter requirements.
- Include the maintenance bypass switch (MBS) in the single-line diagram and wire the MBS lockout terminal to the STS controller.
- Add the front and rear service clearances (12 and 18 inches) and the heat dissipation (for example 755 BTU/hr at 170 A) to the room layout.
- Size the input cable from the NEC table and apply the 20% per 10 C derating above 40 C ambient.
Who should read it
Electrical engineers and system integrators designing inverter plus STS arrangements in telecom and DC-fed systems.
Document contents
- System overview
- Standard features and system configuration
- Installation (location, AC wiring, start-up)
- Operation (power-switch module, controller module, alarms, data logs, Modbus tables)
- Maintenance
- Specifications
Publication details
- Authors
- Exeltech
- Publisher
- Exeltech
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Exeltech Exeltech Static Transfer Switch Operation and Installation Manual, p.24. Exeltech. https://exeltech.com/Manuals/statictransferswitch.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.