Exeltech Static Transfer Switch Operation and Installation Manual, p.24

Exeltech

Exeltech's MX series STS manual: an SCR-based static transfer switch in a 4RU cage, 1-3 phase, 85 or 170 A steps at 117 V, with failed-source transfer typically under 4 ms and 98.9% efficiency.

On this page

Overview

Exeltech's 2020 manual describes a static transfer switch (STS) system designed to give an Exeltech inverter system a second AC source. The system consists of a backplane and relay assembly, one or more power-switch modules and a controller module, all installed in a 19 or 23 inch 4RU cage. It can be configured for one, two or three phases, each 85 A (10 kW) or 170 A (20 kW), with a 117 V output.

The operating principle is SCR switching. Good-to-good transfers occur at the current zero cross and so are seamless; detect-and-transfer time for a failed source varies from zero to 4 ms depending on where in the waveform the failure occurs. The manual states most loads are not disturbed by a single-source failure. Three dry-contact alarms, maintenance bypass switch (MBS) lockout terminals and SNMP and Modbus TCP/IP monitoring are standard.

The installation sections cover location, AC wiring and grounding, and start-up: the cage must be where only non-conductive pollution can occur, power is derated by 20% per 10 C above 40 C, and 12 inches at the front, 18 inches at the rear and 1U above must be left clear. Conductor size follows NEC Table 310.16 for a 40 C ambient: 3 AWG for 85 A and 3/0 AWG for 170 A (1/0 AWG with 90 C conductors). The maintenance section lists common maintenance tasks.

The specification section gives electrical and mechanical data for the system, the power-switch module and the controller module: input 90-135 VAC at 58-61 Hz, SCR voltage drop of 1.3 V, and a heat table by load. The manual uses US units (inches, lb, AWG, BTU/hr). Page 24 only notes that a maintenance bypass switch is recommended; the model rows on the specification page are the two ratings, 10 kW and 20 kW.

Key points

  1. Two model rows: 10 kW (85 A) and 20 kW (170 A), 117 V output, 1, 2 or 3 phases.
  2. Failed-source detect-and-transfer is typically 4 ms; good-to-good transfers are timed to the current zero cross.
  3. Input is 90-135 VAC at 58-61 Hz; SCR voltage drop is 1.3 V; efficiency is 98.9%.
  4. Heat dissipation: 221 W (755 BTU/hr) at 170 A and 110.5 W (377 BTU/hr) at 85 A.
  5. Ambient is -25 to +40 C at full power; derate 20% per 10 C above 40 C; humidity 5-95%; altitude -60 to 1800 m.
  6. Cage is 7 x 17.2 x 15 in (19 in rack) or 7 x 21.2 x 15 in (23 in rack); clearance is 12 in front, 18 in rear, 1U above.
  7. Weight: for 85 A, 20.5 lb (1 phase) and 25.5 lb (3 phase); for 170 A, 22.5 lb (1 phase) and 31.5 lb (3 phase).
  8. Wiring: 3 AWG for 85 A and 3/0 AWG for 170 A (1/0 AWG with 90 C conductors); mechanical lugs 1/0-6 AWG, torque 45 in-lb.
  9. Three dry-contact alarms; Modbus and SNMP monitoring; a maintenance bypass switch is recommended.

Using it in design

  • Select the STS rating (85 or 170 A) from per-phase load current and confirm the 117 V output matches the load voltage; this series is not directly usable at 400 V class facilities.
  • Use it for loads that accept up to 4 ms of transfer time (most IT loads) and confirm with the manufacturer for tighter requirements.
  • Include the maintenance bypass switch (MBS) in the single-line diagram and wire the MBS lockout terminal to the STS controller.
  • Add the front and rear service clearances (12 and 18 inches) and the heat dissipation (for example 755 BTU/hr at 170 A) to the room layout.
  • Size the input cable from the NEC table and apply the 20% per 10 C derating above 40 C ambient.

Who should read it

Electrical engineers and system integrators designing inverter plus STS arrangements in telecom and DC-fed systems.

Document contents

  1. System overview
  2. Standard features and system configuration
  3. Installation (location, AC wiring, start-up)
  4. Operation (power-switch module, controller module, alarms, data logs, Modbus tables)
  5. Maintenance
  6. Specifications

Publication details

Authors
Exeltech
Publisher
Exeltech
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Exeltech Exeltech Static Transfer Switch Operation and Installation Manual, p.24. Exeltech. https://exeltech.com/Manuals/statictransferswitch.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.