Fuji Electric India Hornbill 1000S/2000S 16A-32A brochure FEI/HORNBILL1000/02/2022, p.2

Original title Fuji Electric India Hornbill1000S/2000S16A-32A brochure FEI/HORNBILL1000/02/2022, p.2 (visually checked)

Fuji Electric

A 2022 brochure from Fuji Electric India giving the features and technical table of the single-phase, 16 A and 32 A, 19-inch rack-mounted Hornbill 1000S and 2000S static transfer switches.

On this page

Overview

The brochure presents a single-phase static transfer switch with 32-bit DSP control that transfers and retransfers automatically and instantly between two sources without cross-connecting them. Listed features include enhanced monitoring and diagnostics, RS232 or RS485 interface with Modbus protocol, redundant power supply, natural air cooling and compliance with IEEE 446. The unit is 2U and rack-mounted in 19 inches.

The technical table covers both models: Hornbill 1000S has single-pole and Hornbill 2000S two-pole switching, and both are rated 16 A and 32 A. Nominal voltage is 110/115/230/240 V AC (1 phase + N), tolerance ±15 percent, and frequency 40-70 Hz auto-selectable. Source voltage distortion is below 10 percent THD, and load power factor ranges from 0.6 to unity, leading or lagging.

Overload capacity is 110 percent for 1 hour, 150 percent for 60 s, 200 percent for 10 s and 1000 percent for 100 ms. Transfer time is below 5 ms for synchronous sources and below 15 ms for non-synchronous; retransfer is below 5 ms when synchronous and not applicable otherwise. Efficiency at full load and nominal input voltage exceeds 99 percent for the 1000S and 98 percent for the 2000S. A manual bypass is provided.

Environmental conditions are 0-40 C operating, 0-70 C storage, humidity up to 95 percent non-condensing, noise below 45 dBA at 1 m and altitude up to 1000 m without derating. Protection is IP20, cable entry is at the back and size is 485 x 450 x 88.5 mm. Standards are IEC 62310-1 and IEEE 446. Four discrete model and current configurations (1000S/2000S x 16/32 A) make up the product rows.

Key points

  1. Models: Hornbill 1000S (single pole) and Hornbill 2000S (two pole), each at 16 A and 32 A.
  2. Nominal voltage 110/115/230/240 V AC (1 phase + N), tolerance ±15 percent, frequency 40-70 Hz auto.
  3. Overload: 110 percent for 1 h, 150 percent for 60 s, 200 percent for 10 s, 1000 percent for 100 ms.
  4. Transfer <5 ms (synchronous) and <15 ms (non-synchronous); retransfer <5 ms (synchronous), not applicable otherwise.
  5. Efficiency (full load, nominal input): >99 percent for 1000S, >98 percent for 2000S.
  6. Load power factor 0.6 to unity, leading or lagging; source THD <10 percent.
  7. Operation 0-40 C, storage 0-70 C, humidity up to 95 percent non-condensing, noise <45 dBA, altitude <1000 m.
  8. 2U 19-inch rack, 485 x 450 x 88.5 mm, IP20, natural cooling, rear cable entry.
  9. Standards IEC 62310-1 and IEEE 446; interface RS485 Modbus (RS232 also listed).

Using it in design

  • When choosing 16 A or 32 A for single-phase rack loads, decide between single-pole (1000S) and two-pole (2000S) switching to suit the earthing and neutral scheme.
  • Compare synchronous and non-synchronous transfer times (5 ms and 15 ms) with the load hold-up time.
  • Allow for derating above 1000 m altitude.
  • Check the overload curve against the load current profile and the trip curves of downstream protection.
  • Add the Modbus monitoring point to the BMS design.

Who should read it

Designers and integrators selecting STS equipment for single-phase dual-fed rack loads.

Document contents

  1. Special features
  2. Technical specification: input/output, switch, environmental, physical, user interface, standards

Publication details

Authors
Fuji Electric
Publisher
Fuji Electric
Year
2022
Document number
FEI/HORNBILL1000/02/2022
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Fuji Electric (2022). Fuji Electric India Hornbill1000S/2000S16A-32A brochure FEI/HORNBILL1000/02/2022, p.2 (visually checked). Fuji Electric. FEI/HORNBILL1000/02/2022. https://www.india.fujielectric.com/hubfs/Product-Energy/Hornbill%201000%20%26%202000.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.