People Electric RDQH5 Series Automatic Transfer Switch (ATS), 16-630 A

Original title People Electric RDQH5 series ATS, main technical parameter tables

People Electric

People Electric RDQH5 is a 400 V AC, 16-630 A, 3P/4P circuit-breaker type ATS: 125/250/400/630 frames, 35-100 kA breaking capacity, AC-33iB, and a controller with a 3 s default changeover delay.

On this page

Overview

The page presents the RDQH5 ATS series for 50/60 Hz, 400 V AC systems from 16 A to 630 A. The normal and backup sides can be wired to two grid circuits or to one grid and one generator. When one supply fails through phase loss, over-voltage or under-voltage, the product changes to the other supply. Short-circuit and overload protection are built in. Target places include high-rise buildings, hospitals, banks and airports that cannot accept a power cut.

The selection code sets the frame (125/250/400/630), breaker type (L, M, H), poles (3P/4P) and working mode. Mode R is automatic changeover and automatic return, S is changeover without return, T means both supplies are backup; grid-to-generator allows only R. Rated voltage Ue is AC 400 V, insulation voltage AC 800 V, impulse withstand 8 kV, utilization category AC-33iB. Rated currents are 16-125 A (frame 125), 100-250 A (250), 225-400 A (400) and 400-630 A (630).

The controller monitors over-voltage 230-280 V (default 270 V), under-voltage 140-220 V (default 170 V) and phase loss. Normal-to-backup and backup-to-normal delay is 1-255 s (default 3 s), double-break delay 0-10 s; fire-protection linkage uses a 12-36 V input. Breaking capacity Icn for L/M/H is 35/50/85 kA on frames 125 and 250 and 50/65/100 kA on frames 400 and 630. Electrical life is 1000 operations; mechanical life is 5000, 5000, 3000 and 2000. Ambient range is -35 to +70 °C with a 24 h mean not above 35 °C, altitude up to 5000 m, pollution degree 3.

Key points

  1. Rated voltage 400 V AC, 50 Hz; frames 125/250/400/630, current 16-630 A, 3P or 4P.
  2. Rated breaking capacity Icn: 35/50/85 kA on frames 125 and 250, 50/65/100 kA on frames 400 and 630 (L/M/H).
  3. Insulation voltage AC 800 V, impulse withstand 8 kV, utilization category AC-33iB, CB class ATSE.
  4. Working modes: R automatic changeover and return, S no return, T both supplies backup.
  5. Settings: over-voltage 230-280 V, under-voltage 140-220 V, delays 1-255 s (default 3 s), double break 0-10 s.
  6. Electrical life 1000; mechanical life 5000 (125 and 250), 3000 (400), 2000 (630) operations.
  7. Minimum changeover action time is at most 3 s (delay can be added); working temperature -5 to +40 °C.
  8. Fire-linkage input AC/DC 12-36 V; six-way voltage calibration.

Using it in design

  • Compare the frame's Icn with the prospective short-circuit current at the ATS busbar and pick the L/M/H type accordingly.
  • Because grid-to-generator allows only R (automatic return) mode, build the operating scenario around that constraint.
  • Set the 3 s default delay to suit generator start and UPS battery autonomy.
  • Compare the 1000-operation electrical life with the periodic transfer-test frequency.
  • Carry the fire-linkage input into the project and connect it to the building fire alarm system.

Who should read it

Electrical engineers designing generator and dual-utility transfer.

Document contents

  1. Short description
  2. Guidance of Selection
  3. Normal Working Condition and Installation Environment
  4. Structure and Characteristics
  5. Controller Operation
  6. Main Technical Parameter
  7. Shape and installation dimension

Publication details

Authors
People Electric
Publisher
People Electric
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

People Electric People Electric RDQH5 series ATS, main technical parameter tables. People Electric. https://people-electric.com/rdqh5-rdxq5-series-automatic-generator-transfer-switch-electric-equipment-product

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.