PowerFlo Static Transfer Switch (STS) Product Datasheet 803-00011 Rev A00

Original title PowerFlo Static Transfer Switch product datasheet 803-00011 Rev A00, pp.1-2

PowerFlo Solutions

A two-page manufacturer datasheet for the PowerFlo static transfer switch, giving electrical, mechanical and communication data for seven current options from 400 to 2000 A.

On this page

Overview

The document presents the product data of a static transfer switch (STS), which feeds a single-input load from two independent sources, in category tables. The general section lists fully rated semiconductors, redundant fans with failure sensing, copper busbar, triple-redundant power supplies, three redundant microprocessor boards and redundant SCR drivers. Output load switches are redundant as standard (6 MCS) and non-redundant as an option (5 MCS).

The electrical section gives voltage as 208 V, 480 V or custom, frequency as 60 Hz, and current as 400, 600, 800, 1000, 1200, 1600 and 2000 A. Short-circuit ratings are offered at 65 and 100 kAIC; input and output are three-phase, 3-wire plus ground. The unit is ETLus listed to UL 1008S, with a NEMA Type 1 enclosure and C2 EMC category. Surge protection of up to 100 kA is fitted on each source, and an upstream overcurrent protective device (OCPD) is required.

The most important operating values are the transfer times: sense plus transfer takes 4 ms between in-phase sources and at most 15 ms between out-of-phase sources, and loss of source is detected in 1 to 2 ms. Overload capacity is 110% for 60 minutes, 125% for 30 minutes, 150% for 2 minutes, 200% for 10 seconds and 1500% for one cycle. Full-load efficiency reaches up to 99.45% at 480 V. Inrush of downstream PowerFlo transformers must stay below 1.2 times the nominal transformer rating.

The sheet also lists a four-Kirk-key manual and guided bypass, Modbus TCP/IP and an RS232 service port, a 1000-event alarm log, six-plot waveform capture (source and output voltages and currents) and environmental limits: 0 to 40 degrees C operating temperature, 95% non-condensing relative humidity and 1000 m altitude without derating. Because it is a product summary and not a design guide, layout and coordination decisions need the manufacturer's project documentation.

Key points

  1. Seven current options: 400, 600, 800, 1000, 1200, 1600 and 2000 A; voltage 208 V, 480 V or custom, frequency 60 Hz.
  2. Short-circuit ratings of 65 and 100 kAIC are offered; surge protection up to 100 kA on each source.
  3. Sense plus transfer time is 4 ms in phase and 15 ms maximum out of phase; loss-of-source detection takes 1 to 2 ms.
  4. Overload: 110% for 60 min, 125% for 30 min, 150% for 2 min, 200% for 10 s, 1500% for 1 cycle.
  5. Full-load efficiency up to 99.45% at 480 V; downstream PowerFlo transformer inrush below 1.2 times nominal rating.
  6. Dimensions (W x D x H): 30 x 36 x 84 in for 400-600 A, 42 x 36 x 84 in for 800-1200 A, 84 x 36 x 90 in for 1600-2000 A.
  7. Triple-redundant power supplies, three redundant processor boards, redundant SCR drivers and fans; output load switches redundant as standard.
  8. Four Kirk-key bypass, 4 alarm relays, 2 building alarm inputs, remote EPO, Modbus TCP/IP and a 1000-event log.
  9. Operating range 0 to 40 degrees C, humidity up to 95% non-condensing, no altitude derating up to 1000 m; noise at 1 m below 60 dBA (400-600 A) and 65 dBA (800-1200 A).

Using it in design

  • Select from the seven discrete current rows by load current without interpolating models, and reserve floor space separately for the 84 in wide 1600-2000 A cabinet.
  • Compare the transfer time with the load's ride-through: allow up to 15 ms when the two sources are not in phase.
  • Because the sheet requires an upstream OCPD, match the OCPD choice for both source inputs and the 65 or 100 kAIC rating to the fault-current study.
  • If a transformer sits downstream, check that its inrush stays within 1.2 times the nominal transformer rating.
  • Note at specification stage that frequency is given only as 60 Hz, so the product does not fit 50 Hz networks directly.

Who should read it

Electrical designers selecting STS equipment for critical power distribution and engineers preparing a product catalogue.

Document contents

  1. General characteristics
  2. Standards and safety
  3. Communications
  4. Electrical characteristics
  5. Overload capacity
  6. Operational characteristics
  7. Power quality and metering
  8. Environmental

Publication details

Authors
PowerFlo Solutions
Publisher
PowerFlo Solutions
Year
2025
Document number
803-00011 Rev A00
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

PowerFlo Solutions (2025). PowerFlo Static Transfer Switch product datasheet 803-00011 Rev A00, pp.1-2. PowerFlo Solutions. 803-00011 Rev A00. https://powerfloltd.com/sts-datasheet

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.