Salicru SPS.16.STS data sheet JM809B01, November 2015, p.2
Salicru
Salicru's data sheet JM809B01 of November 2015 specifies the SPS.16.STS, a single-phase 16 A automatic transfer system with two AC inputs: 230 V nominal in a 1U chassis, transfer time under 15 ms and break-before-make operation.
On this page
Overview
The two-page document is the data sheet for the rack-mounted SPS.16.STS automatic transfer system from the Spanish manufacturer Salicru. The unit is a single-phase switch that selects one of two sine-wave supply sources to feed the load. As shipped, mains 1 is the priority and mains 2 the reserve; the user can change this with the communication software, and the unit starts each time with the last programmed setting. A front-panel pushbutton allows manual switching between sources. When the voltage or frequency of the priority source leaves its limits, the load is moved to the other source.
The first page gives the operating principle and features. Transfer is break before make, and the unit has automatic backfeed protection to EN 62310-1. Overload and short-circuit protection on both mains is provided by accessible fuses and 10 A thermal relays. The internal power supply is redundant, fed from both mains. The unit can transfer even with phase and neutral swapped on an input, and the two inputs may be different phases of the same three-phase supply. An auxiliary contact is provided for an external remote power off (RPO).
The specification table on the second page holds the numeric limits. Nominal voltage is 230 V (220, 230 or 240 V selectable), input voltage range 160 to 290 Vac, nominal current 16 A and frequency 50 or 60 Hz. The acceptable voltage window is adjustable from ±12% to ±20% (±12% as standard) and the frequency window from ±5% to ±15% (±15% as standard). Transfer time is under 15 ms. On overload the input relay disconnects in steps: 12 s at 101% to 125%, 8 s at 126% to 150%, 4 s at 151% to 210% and 2 s at 211% to 300%.
Inputs are IEC 320 C20, and outputs are IEC 320 C19 and C13, with 10 A thermal protection on the C13 outputs. The unit is naturally cooled, produces less than 25 dB at 1 metre, is rated IP30 and weighs 8 kg. Communication is through RS-232 and a dry-contact interface. Break-before-make operation and a transfer time of up to 15 ms set this unit apart from static (semiconductor) transfer switches. The sheet covers one model only, with no higher-current or three-phase options.
Key points
- One model: SPS.16.STS, single-phase, 16 A nominal current, 230 V nominal voltage (220/230/240 V selectable), 50/60 Hz auto-selected.
- Transfer time is under 15 ms; operation is break before make.
- Input voltage range 160 to 290 Vac; transfer window ±12% to ±20% on voltage (±12% standard) and ±5% to ±15% on frequency (±15% standard).
- Overload steps: 101% to 125% (20 A) 12 s, 126% to 150% (24 A) 8 s, 151% to 210% (33.6 A) 4 s, 211% to 300% (48 A) 2 s; fuse protection on short circuit.
- Automatic backfeed protection to EN 62310-1 and a redundant internal power supply fed from both mains.
- Connections: IEC 320 C20 inputs, C19 and C13 outputs, with 10 A thermal protection on the C13 outputs.
- Dimensions 315 x 430 x 44 mm (depth x width x height, 1U), weight 8 kg, IP30, natural cooling, noise under 25 dB.
- Operating conditions: 0 to +40 °C, 20% to 85% relative humidity (non-condensing), altitude up to 1,000 m.
- Standards: safety EN 62310-1, EMC IEC 62310-2.
Using it in design
- Compare the transfer time of up to 15 ms with the power-supply hold-up time of the connected equipment; for loads with a shorter hold-up, select a faster static switch.
- Check total rack load against the 16 A nominal current and the C13 outlet groups against the 10 A thermal protection limit.
- Set the voltage and frequency transfer windows (standard ±12% and ±15%) to suit the output tolerances of the upstream UPS or generator; a narrow window causes needless transfers.
- Feed the two inputs from different sources or from different phases of the same three-phase system, and carry that choice into the phase load balance.
- Wire the RPO contact and dry-contact outputs into the emergency power off and monitoring systems.
Who should read it
Rack power designers who need to connect single-corded devices to two sources, and operators of small computer rooms.
Document contents
- SPS.16.STS: Redundancy in power supply sources
- Performance
- Applications: A reliable, cheap and simple solution
- Technical specifications
- Range
- Display
- Services
Publication details
- Authors
- Salicru
- Publisher
- Salicru
- Year
- 2015
- Document number
- JM809B01
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Salicru (2015). Salicru SPS.16.STS data sheet JM809B01, November 2015, p.2. Salicru. JM809B01. https://d7rh5s3nxmpy4.cloudfront.net/CMP1313/files/3/ficha-pdf-56caf57017710_ingles.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
