Suntree SQ8W series automatic transfer switch electrical technical reference
Original title Suntree SQ8W Series Automatic Transfer Switch electrical technical reference
Suntree
The Suntree SQ8W is an AC230/400 V dual-power automatic transfer switch in nine current ratings from 6 to 63 A: Icn 4.5 kA, 4 kV impulse withstand, transfer time up to 3 s.
On this page
Overview
The page gives the features and electrical technical reference of China Suntree Electric's SQ8W series automatic transfer switch (ATS). The product is presented for important supply points where power failure is not allowed; it is described as small, with firefighting and power generation functions. The design is for automatic changeover between two sources such as mains and a generator.
Highlights: operation across a work voltage range of 120 V to 280 V without coil burn-out, overload and short-circuit protection, strong interference immunity and quick, reliable transfer. The controller is Type A (basic type) with a rated control supply voltage of 230 V 50 Hz.
Technical table: rated currents 6, 10, 16, 20, 25, 32, 40, 50 and 63 A; rated operating voltage AC 230 V / AC 400 V; rated insulation voltage AC 690 V; rated impulse withstand voltage 4 kV; rated short-circuit making capacity Icm 6 kA; rated short-circuit breaking capacity Icn 4.5 kA. The electrical equipment class is CB Class.
Operating transfer time without delay is up to 3 s and service life is 5000 operations. The page lists the SQ3W, SQ8P, SQ5 and SQ3 dual-power automatic transfer switches in the same family as recommended products. A 3-second transfer is not uninterrupted; CB-class ATS units suit loads that tolerate interruption and generator backup.
Key points
- Rated currents: 6, 10, 16, 20, 25, 32, 40, 50 and 63 A.
- Rated operating voltage AC 230 V / AC 400 V; insulation voltage AC 690 V.
- Rated impulse withstand voltage 4 kV.
- Icm 6 kA (short-circuit making), Icn 4.5 kA (short-circuit breaking).
- Transfer time without delay up to 3 s; service life 5000 operations.
- Electrical equipment class CB Class; controller Type A (basic), control supply 230 V 50 Hz.
- Works across 120-280 V without coil burn-out; overload and short-circuit protection.
- Recommended family products: SQ3W, SQ8P, SQ5, SQ3.
Using it in design
- For loads that cannot tolerate interruption, note that a transfer time up to 3 s is not sufficient; choose an STS or UPS, and use the ATS only for generator backup.
- Select the rated current (6-63 A) against load current, and verify that Icn 4.5 kA exceeds the installation's fault level.
- Compare the 5000-operation service life with the periodic test frequency (for example monthly generator tests) to plan renewal.
- The control supply is 230 V 50 Hz, so show on the diagram which source feeds the control supply.
Who should read it
Electrical engineers designing low-voltage distribution boards and project teams selecting ATS units for small generator-backed installations.
Document contents
- SQ8W features
- Electrical technical reference
- Recommended products (SQ3W, SQ8P, SQ5, SQ3)
Publication details
- Authors
- Suntree
- Publisher
- Suntree
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Suntree Suntree SQ8W Series Automatic Transfer Switch electrical technical reference. Suntree. https://www.chinasuntree.com/pv-ats/sq8w-series-automatic-transfer-switch.htm
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.