Tengen TGQ1NP automatic transfer switches
Original title Tengen TGQ1NP product technical table
Tengen
Tengen TGQ1NP is an IEC 60947-6-1 PC-class automatic transfer switch in utilisation category AC-33B, rated 16-250 A (TGQ1NP-125 and -250), 2P/3P/4P, for 230/400 V 50 Hz networks.
On this page
Overview
The product page describes the TGQ1NP automatic transfer switch from Zhejiang Tengen Electric. The series is designed to transfer a load automatically between two sources in two-phase or three-phase four-wire, 50 Hz dual-supply networks. Target sites are industrial and commercial premises, high-rise and residential buildings and other important locations.
The technical table lists two frames. TGQ1NP-125 has rated currents of 16, 20, 25, 32, 40, 50, 63, 80, 100 and 125 A; TGQ1NP-250 has 125, 140, 160, 180, 200, 225 and 250 A. Rated operating voltage is AC 230 V for 2P and AC 400 V for 3P/4P at 50 Hz, with 2P, 3P or 4P poles. The utilisation category is AC-33B.
Rated insulation voltage is 800 V on the 125 A frame and 1000 V on the 250 A frame, with impulse withstand of 8 and 12 kV respectively. Service conditions are -5 to +40 °C ambient (24-hour mean not above 35 °C), altitude up to 2000 m and pollution degree 3. Relative humidity must not exceed 50% at 40 °C.
Construction features digital electronic control, a dual-spring fast mechanism, rotating contacts with an arc chute, and double mechanical interlocking. Beyond the model table the page gives no transfer time or short-circuit withstand figures; those are in the catalogue PDF.
Key points
- Two frames: TGQ1NP-125 (16-125 A) and TGQ1NP-250 (125-250 A).
- TGQ1NP-125 ratings: 16/20/25/32/40/50/63/80/100/125 A; TGQ1NP-250: 125/140/160/180/200/225/250 A.
- Rated voltage AC 230 V for 2P and AC 400 V for 3P/4P; 50 Hz.
- Insulation voltage 800 V (125 A frame) and 1000 V (250 A frame); impulse withstand 8 kV and 12 kV.
- Utilisation category AC-33B, standard IEC 60947-6-1, PC class (short-circuit making and carrying).
- Ambient -5 to +40 °C, altitude up to 2000 m, pollution degree 3.
- Pole count 2P, 3P or 4P.
Using it in design
- For auxiliary and building loads up to 250 A with generator/mains transfer, choose the TGQ1NP-125 or -250 frame on load current.
- State in the specification that the category is AC-33B, meaning it can transfer mixed resistive and inductive loads.
- Consult the manufacturer for altitude above 2000 m and ambient below -5 °C; pollution degree 3 must match the switchboard environment.
- Request the catalogue PDF separately for short-circuit withstand and transfer time; the page does not give them.
Who should read it
Designers and panel builders specifying automatic transfer up to 250 A in low-voltage distribution boards.
Document contents
- TGQ1NP general description
- Overview and construction features
- Normal service and installation conditions
- Model, rated current, voltage and utilisation category table
Publication details
- Authors
- Tengen
- Publisher
- Tengen
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Tengen Tengen TGQ1NP product technical table. Tengen. https://tengenglobal.com/proPowAut/21.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.