WEG SSE Transfer Switch Brochure (50139510 Rev00, March 2024)
Original title WEG Chave de Transferencia SSE50139510 Rev00, March2024, p.6
WEG
A Portuguese-language WEG brochure for the SSE bypass switch, covering features, connection examples and a technical table for three models rated 25, 50 and 100 A that supply a load from two separate sources.
On this page
Overview
The brochure describes the WEG SSE as a transfer switch that gives stable supply from two different sources. The manufacturer highlights flexible voltage support (120 Vac or 220 Vac), fast transfer, automatic fault detection, RISC-microprocessor monitoring and visual status signals. It claims that the quick, smooth transition between sources extends the life of sensitive equipment and lowers maintenance cost.
The connections section contains four application diagrams: generator input, bypass mode, bypass with a transformer (127 V to 220 V) and UPS with an alternative mains input. The diagram identifies four points: preferred supply, alternative supply, load connection and signalling. Listed applications are hospitals, emergency systems, security cameras and data centres.
The technical table gives three models: SSE-NBM0025 (25 A, 8.5 kg), SSE-NBM0050 (50 A, 8.5 kg) and SSE-NBM0100 (100 A, 13.5 kg). All three have manually selected dual-voltage input (120/220 V), transfer time under 16 ms, an under and over-voltage threshold of plus or minus 15%, circuit-breaker protection, LED signalling and IP20 protection. Alarms cover mains loss, under-voltage and over-voltage. Frequency is stated as 50/60 Hz, but a footnote makes it available on request.
Environmental conditions are minus 10 to 45 degrees C in operation, minus 25 to 70 degrees C in storage and below 95% non-condensing humidity. The connection type is BTWP terminal blocks and height is 309.8 mm. Because this is a product brochure, it does not state whether the transfer between sources uses static semiconductors or electromechanical switching; the product should be treated as an automatic transfer switch with a transfer time below 16 ms, not as a continuous no-break device.
Key points
- Three models: SSE-NBM0025 (25 A), SSE-NBM0050 (50 A) and SSE-NBM0100 (100 A).
- Transfer time is below 16 ms on all three models.
- Input voltage is manually selected dual 120 V / 220 V; under and over-voltage threshold plus or minus 15%.
- Alarms: mains loss, under-voltage, over-voltage; LED signalling with circuit-breaker protection.
- Weight 8.5 kg (25 and 50 A) and 13.5 kg (100 A); height 309.8 mm, width 227 mm (25 and 50 A) and 290 mm (100 A).
- Operating temperature minus 10 to 45 degrees C, storage minus 25 to 70, relative humidity below 95% non-condensing, IP20.
- Frequency is given as 50 Hz / 60 Hz; per a footnote, on request.
- Application examples: generator input, bypass, bypass with transformer, UPS with alternative mains.
Using it in design
- Use only the three discrete current rows (25, 50, 100 A) and do not propose this family for loads above 100 A or at 400 V class.
- Compare the sub-16 ms transfer time with the load's tolerance; it may suit small loads such as servers, modems and cameras.
- In protection coordination, account for the fixed plus or minus 15% under and over-voltage threshold, which is not stated as adjustable.
- Add the manual voltage selection (120/220 V) to the commissioning checklist.
- Use the UPS with alternative mains and generator input diagrams as references for the supply topology of small critical loads.
Who should read it
Electrical designers selecting transfer switches for small critical loads and engineers cataloguing products.
Document contents
- Features
- Diagram
- Connections and application examples
- Applications
- Technical specifications
Publication details
- Authors
- WEG
- Publisher
- WEG
- Year
- 2024
- Document number
- 50139510 Rev00
- Document language
- Portuguese
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
WEG (2024). WEG Chave de Transferencia SSE50139510 Rev00, March2024, p.6. WEG. 50139510 Rev00. https://static.weg.net/medias/downloadcenter/h75/h79/WEG-SSE-brochure-50139510-pt.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.