TS Shara TS Tryon Trifásico 10–100kVA brochure, Rev00-08/2011, p.4

TS Shara

A four-page brochure dated August 2011 from Brazilian manufacturer TS Shara for the TS Tryon Trifásico double-conversion on-line UPS series from 10 to 100 kVA: output power factor 0.8, efficiency above 92%, input power factor of 0.99 or higher, and N+X redundant paralleling of up to 6 units.

On this page

Overview

The brochure is written in Portuguese and describes a three-phase UPS family for the Brazilian market. The unit is a true double-conversion on-line design under DSP control, with IGBT rectifier and inverter. Mains power is first converted to direct current and then back to sinusoidal alternating current, so that mains defects such as sags, swells, surges, frequency deviations and harmonics do not reach the load. Data centres, servers, networks and telecom systems, medical, security and industrial processes are named as applications.

The main architectural feature is the dual input and double bypass arrangement. The unit can run from a main and an alternative supply; the alternative line is connected to the bypass branch and raises availability. The static bypass moves the load to the alternative circuit without interruption if a fault occurs, while the maintenance bypass is operated together with the static bypass during repair so the unit can be serviced without dropping the output. The battery bank can be disconnected for maintenance while the UPS runs. In redundant parallel operation the load is shared equally and capacity can be added in steps.

Technical data are collected on the last page: input voltage tolerance ±15%, output voltage regulation ±1% on linear load, frequency 50 or 60 Hz ±10%, crest factor above 3:1. Output voltage distortion is below 2% on linear load and below 5% on non-linear load. Input and output can be configured as 480/277 V, 380/220 V, 220/127 V or 208/120 V, in star or delta connection; autotransformers are used for 220/127 V and 208/120 V, and an isolation transformer is optional for the delta configuration.

Physical data separate two cabinet sizes. Models from 10 to 80 kVA are 1060 mm high, 480 mm wide and 890 mm deep; weight is 185 kg for 10 to 40 kVA, 200 kg for 60 kVA and 205 kg for 80 kVA. The 100 kVA model measures 1220 x 480 x 890 mm and weighs 320 kg. The battery rack measures 1100 x 350 x 790 mm and weighs 77 kg. The 2011 brochure notes that its information can change without prior notice.

Key points

  1. Power range 10 to 100 kVA; output power factor 0.8.
  2. Efficiency above 92%; noise below 65 dB at 1 m.
  3. Input power factor of 0.99 or higher (active PFC), which the brochure says cuts apparent power and losses in the supply network by up to 50%.
  4. Input voltage range ±15%; output regulation ±1% on linear load; frequency 50/60 Hz ±10%.
  5. Output THD below 2% on linear load and below 5% on non-linear load; crest factor above 3:1.
  6. Redundant parallel operation of up to 6 units in N+X arrangement.
  7. Dimensions: 1060 x 480 x 890 mm (H x W x D) for 10 to 80 kVA, 1220 x 480 x 890 mm for 100 kVA.
  8. Weight: 185 kg for 10 to 40 kVA, 200 kg for 60 kVA, 205 kg for 80 kVA, 320 kg for 100 kVA; battery rack 77 kg.
  9. Batteries recharge in less than 24 hours; the LCD display logs the last 512 events.
  10. Communication: RS232, RS485, SNMP and dry contacts; the standards cited include EN 62040-1 and EN 62040-2.

Using it in design

  • Calculate active power at the 0.8 power factor: the 100 kVA model delivers 80 kW, and since modern IT loads sit near unity power factor the kW limit governs.
  • Derive the heat load from the 92% efficiency threshold and size UPS room cooling accordingly.
  • To benefit from the dual input, feed the bypass line from a source separate from the main rectifier input.
  • Where site voltage is 220/127 V or 208/120 V, add the autotransformer's footprint and losses to the layout and the efficiency calculation.
  • When building an N+X parallel system, respect the 6 unit limit and include the mass per unit (185 to 320 kg) in the floor loading.

Who should read it

Electrical engineers selecting mid-power three-phase UPS units for Latin American projects, and teams preparing product catalogue data.

Document contents

  1. Principais características
  2. Gerenciamento remoto (por Internet, rede local ou RS232/485)
  3. PFC Ativo: correção do fator de potência
  4. Topologia on line com duplo bypass sem interrupções
  5. Dupla conversão
  6. Bypass estático
  7. Bypass de manutenção sem interrupções
  8. Paralelo redundante (N + X)
  9. Especificações e recursos
  10. Dimensões e peso
  11. Aplicações

Publication details

Authors
TS Shara
Publisher
TS Shara
Year
2011
Document number
Rev00-08/2011
Document language
Portuguese
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

TS Shara (2011). TS Shara TS Tryon Trifásico 10–100kVA brochure, Rev00-08/2011, p.4. TS Shara. Rev00-08/2011. https://tsshara.com.br/wp-content/uploads/2019/08/nobreak-on-line-ts-tryon-trifasico-10-a-100kva.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.