ZLPOWER 6-10 kVA rack mount online UPS official table
Original title ZLPOWER 6–10kVA Rack mount Online UPS official table
ZLPOWER
The ZLPOWER RM series is a 3U rack-mount high-frequency pure sine wave online UPS in four models of 6 kVA/4800 W and 10 kVA/8 kW, with a 176-276 VAC input window, zero transfer time and an external battery pack.
On this page
Overview
The ZLPOWER product page presents the RM series of rack-mount high-frequency pure sine wave online UPS for servers, critical data-centre network devices, telecom, bank, hospital and ATM applications. Four models are listed: RM6K-C, RM6KL-C (6 kVA / 4800 W) and RM10K-C, RM10KL-C (10 kVA / 8 kW). The K models use the standard battery and the KL models an external battery pack.
Input is single phase plus ground, nominal 220/230/240 Vac, voltage range 176-276 VAC, frequency 46-54 Hz and power factor 0.98, with a terminal block connection. Output is single phase, 110/115/120 Vac or 220/230/240 Vac ±1%, frequency 46-54 Hz in line mode and 50 Hz ±0.05 Hz in battery mode, pure sine wave, crest factor 3:1. Overload capability is 105-130% for 10 minutes and 130% for 1 minute. Bypass transfers automatically on overload and UPS failure; bypass voltage range is 176-261 VAC; transfer time is zero.
The battery pack is 192 VDC nominal, 16 pieces of 12 V / 7 Ah. Full-load backup time in the standard models is 4 minutes for RM6K-C and 3 minutes for RM10K-C; in the long-run models it depends on the external battery pack. Recharge time is 5 hours to 90%; maximum charging current is 2 A (standard) or 5A/7A ±1 A (KL). Charging voltage is 219.50 VDC ±1%. Communication is RS-232 and an intelligent slot (WEBPOWER SNMP/WEB card, AS400 card or WinPower CMC optional). Operation is 0-40 °C and 20-90% humidity; main unit weight is 17.7-20.3 kg and size 484 x 653 x 134 mm (3U).
Key points
- Models RM6K-C, RM6KL-C (6 kVA/4800 W) and RM10K-C, RM10KL-C (10 kVA/8 kW).
- Input 220/230/240 Vac, 176-276 VAC, 46-54 Hz, power factor 0.98.
- Output 110/115/120 or 220/230/240 Vac ±1%; 50 Hz ±0.05 Hz in battery mode; crest factor 3:1.
- Overload: 105-130% for 10 minutes, 130% for 1 minute; bypass transfer time zero.
- Battery pack 192 VDC, 16 x 12 V/7 Ah; full-load backup 4 min (RM6K-C) and 3 min (RM10K-C).
- Recharge time 5 hours to 90%; maximum charging current 2 A (standard) or 5A/7A ±1 A (KL).
- Main unit 484 x 653 x 134 mm (3U), 17.7-20.3 kg; operation 0-40 °C, 20-90% humidity.
Using it in design
- On the 10 kVA model power is 8 kW, so take kW capacity per model; for 6 kVA it is 4800 W (power factor 0.8).
- For several minutes of autonomy choose the KL model with external battery packs; standard-model backup is 3-4 minutes.
- The 176-276 VAC input window reduces battery transfers on mains fluctuation; plan fixed wiring and protection for the terminal-block connection.
- Charging current (2 A or 5A/7A) sets recharge time on long battery strings; assess it together with the backup time requirement.
Who should read it
Designers selecting 6-10 kVA rack-mount UPS for server rooms and small data centres.
Document contents
- Overview and features
- Specifications: input, output, bypass
- Battery pack and charging
- Environment, weight and size
Publication details
- Authors
- ZLPOWER
- Publisher
- ZLPOWER
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ZLPOWER ZLPOWER 6–10kVA Rack mount Online UPS official table. ZLPOWER. https://www.zlpower.com/products_details/6-10KVA_Rack_mout_Online_UPS.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.