ZLPOWER 6-10 kVA rack mount online UPS official table

Original title ZLPOWER 6–10kVA Rack mount Online UPS official table

ZLPOWER

The ZLPOWER RM series is a 3U rack-mount high-frequency pure sine wave online UPS in four models of 6 kVA/4800 W and 10 kVA/8 kW, with a 176-276 VAC input window, zero transfer time and an external battery pack.

On this page

Overview

The ZLPOWER product page presents the RM series of rack-mount high-frequency pure sine wave online UPS for servers, critical data-centre network devices, telecom, bank, hospital and ATM applications. Four models are listed: RM6K-C, RM6KL-C (6 kVA / 4800 W) and RM10K-C, RM10KL-C (10 kVA / 8 kW). The K models use the standard battery and the KL models an external battery pack.

Input is single phase plus ground, nominal 220/230/240 Vac, voltage range 176-276 VAC, frequency 46-54 Hz and power factor 0.98, with a terminal block connection. Output is single phase, 110/115/120 Vac or 220/230/240 Vac ±1%, frequency 46-54 Hz in line mode and 50 Hz ±0.05 Hz in battery mode, pure sine wave, crest factor 3:1. Overload capability is 105-130% for 10 minutes and 130% for 1 minute. Bypass transfers automatically on overload and UPS failure; bypass voltage range is 176-261 VAC; transfer time is zero.

The battery pack is 192 VDC nominal, 16 pieces of 12 V / 7 Ah. Full-load backup time in the standard models is 4 minutes for RM6K-C and 3 minutes for RM10K-C; in the long-run models it depends on the external battery pack. Recharge time is 5 hours to 90%; maximum charging current is 2 A (standard) or 5A/7A ±1 A (KL). Charging voltage is 219.50 VDC ±1%. Communication is RS-232 and an intelligent slot (WEBPOWER SNMP/WEB card, AS400 card or WinPower CMC optional). Operation is 0-40 °C and 20-90% humidity; main unit weight is 17.7-20.3 kg and size 484 x 653 x 134 mm (3U).

Key points

  1. Models RM6K-C, RM6KL-C (6 kVA/4800 W) and RM10K-C, RM10KL-C (10 kVA/8 kW).
  2. Input 220/230/240 Vac, 176-276 VAC, 46-54 Hz, power factor 0.98.
  3. Output 110/115/120 or 220/230/240 Vac ±1%; 50 Hz ±0.05 Hz in battery mode; crest factor 3:1.
  4. Overload: 105-130% for 10 minutes, 130% for 1 minute; bypass transfer time zero.
  5. Battery pack 192 VDC, 16 x 12 V/7 Ah; full-load backup 4 min (RM6K-C) and 3 min (RM10K-C).
  6. Recharge time 5 hours to 90%; maximum charging current 2 A (standard) or 5A/7A ±1 A (KL).
  7. Main unit 484 x 653 x 134 mm (3U), 17.7-20.3 kg; operation 0-40 °C, 20-90% humidity.

Using it in design

  • On the 10 kVA model power is 8 kW, so take kW capacity per model; for 6 kVA it is 4800 W (power factor 0.8).
  • For several minutes of autonomy choose the KL model with external battery packs; standard-model backup is 3-4 minutes.
  • The 176-276 VAC input window reduces battery transfers on mains fluctuation; plan fixed wiring and protection for the terminal-block connection.
  • Charging current (2 A or 5A/7A) sets recharge time on long battery strings; assess it together with the backup time requirement.

Who should read it

Designers selecting 6-10 kVA rack-mount UPS for server rooms and small data centres.

Document contents

  1. Overview and features
  2. Specifications: input, output, bypass
  3. Battery pack and charging
  4. Environment, weight and size

Publication details

Authors
ZLPOWER
Publisher
ZLPOWER
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

ZLPOWER ZLPOWER 6–10kVA Rack mount Online UPS official table. ZLPOWER. https://www.zlpower.com/products_details/6-10KVA_Rack_mout_Online_UPS.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.