MTPU - Modular Three Phase UPS

CEG Elettronica Industriale

CEG Elettronica Industriale's MTPU is a double-conversion three-phase modular UPS with hot-swap modules, up to 12 modules in parallel, efficiency above 96.5%, input power factor 0.99 and THDi below 3%.

On this page

Overview

The MTPU (Modular Three Phase UPS) is a hot-swap modular UPS family with double-conversion technology. Each system can manage up to 12 modules connected in parallel, so the architecture can be expanded or changed on site without affecting footprint or installation. The manufacturer lists transport, telecommunications, oil and gas, IT and data centres as application sectors.

Efficiency exceeds 96.5% in double-conversion operation thanks to 3-level (3L) technology in both the PFC stage and the inverter. Modularity allows N+X or 2N redundant configurations for particularly critical loads, and power can be increased or the redundancy level changed directly on site. The design has no single point of failure: the loss of one module does not affect the other units.

Low MTTR and the hot-swap structure mean a module can be replaced without disconnecting loads and without shutting down the system. Power quality is high on input and output: power factor is 0.99 and THDi is below 3%. The page also describes the manufacturer's after-sales services (scheduled maintenance, spare parts, 24/7 phone support, commissioning and training) and its EPC contractor role. The source is the manufacturer's product page; module kW ratings and technical tables are not on the page.

Key points

  1. Hot-swap modular three-phase UPS, double conversion.
  2. Up to 12 modules in parallel per system.
  3. Efficiency above 96.5% in double conversion (3-level technology in PFC and inverter).
  4. N+X and 2N redundant configurations; power and redundancy changeable on site.
  5. No single point of failure; a module fault does not affect other units.
  6. Low MTTR; a module can be replaced with loads connected and without shutting the system down.
  7. Input power factor 0.99; THDi below 3%.
  8. Application sectors: transport, telecommunications, oil and gas, IT, data centres.

Using it in design

  • For N+X redundancy, calculate the module count from the load and use the 12-module limit in system scale calculations.
  • For critical loads needing 2N, plan two independent MTPU systems.
  • Define the hot-swap procedure in the maintenance plan; modules are changed without cutting the load.
  • With input power factor 0.99 and THDi below 3%, use these values in generator sizing.
  • Request the manufacturer's brochure for module power and battery structure.

Who should read it

Data-centre and industrial-facility designers seeking a modular, scalable UPS architecture.

Document contents

  1. MTPU overview
  2. Strengths
  3. After-sales services
  4. Certifications

Publication details

Authors
CEG Elettronica Industriale
Publisher
CEG Elettronica Industriale
Year
Year not stated
Document language
Italian
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

CEG Elettronica Industriale MTPU - Modular Three Phase UPS. CEG Elettronica Industriale. https://www.cegelettronica.com/it/soluzioni/power-electronic-division/mtpu-modular-three-phase-ups.html

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.