Technical guideFree to readYear not stated

GVN-DSP Series UPS Technical Specifications

Original title GVN-DSP Serisi UPS teknik özellikleri

Güveniş

The Güvenis GVN-DSP is a 10-400 kVA three-phase IGBT-rectifier double-conversion UPS with efficiency up to 95%, input THDI of 3% or less, input PF 0.99 and IEC 62040-3 class VFI-SS-111.

On this page

Overview

The document is the Turkish-language technical specification page for Güvenis's GVN-DSP three-phase-in, three-phase-out UPS. The series uses an IGBT rectifier, IGBT inverter and DSP-controlled processor in true on-line double conversion; active input power factor correction (PF 0.99), active harmonic correction (THDI 3% or less), generator compatibility and an ECOMODE energy-saving mode are among its features.

The table lists 14 models (GVN-DSP 33010 to 33400): 10, 15, 20, 30, 40, 60, 80, 100, 120, 160, 200, 250, 300 and 400 kVA. Nominal active power depends on output power factor, for example 8/9 kW at 10 kVA and 320/360 kW at 400 kVA (power factor 0.8 or 0.9 optional). Input tolerance is -25%/+27% at 100% load, -45%/+27% at 64% load and -64%/+27% at 42% load. Static voltage regulation is under 1%, voltage THD on linear load is 2% or less, and overload is 10 minutes at 125% and 1 minute at 150%.

The static bypass works within ±10% voltage and 47-53 Hz (adjustable). The battery section lists maintenance-free dry-type batteries, 62 units (2x31) or 60 units (2x30), deep-discharge protection and temperature-compensated charging. Operating temperature is 0-40 °C, maximum altitude 1000 m, IP20; standards are EN 62040-1, EN 62040-2 and EN 62040-3 (VFI-SS-111). Options are a parallel kit, SNMP, external bypass, isolation transformer, battery cabinet and IP21.

Key points

  1. Range 10-400 kVA across 14 models (GVN-DSP 33010-33400); input 3F+N+PE, 380/400/415 V.
  2. Nominal active power depends on output PF: 8/9 kW at 10 kVA, 320/360 kW at 400 kVA (PF 0.8 or 0.9).
  3. Input PF 0.99 and input current THD of 3% or less; input voltage tolerance -25%/+27% at 100% load.
  4. Efficiency up to 95% (depends on unit power and ambient); output frequency tolerance ±0.01%.
  5. Overload: 10 min at 125%, 1 min at 150%; crest factor 3:1.
  6. Static bypass operates within ±10% voltage and 47-53 Hz; static and manual bypass are standard.
  7. Battery count 62 (2x31) or 60 (2x30), maintenance-free dry type; deep-discharge protection and temperature-compensated charging.
  8. Standards: EN 62040-1, EN 62040-2, EN 62040-3 (VFI-SS-111); 0-40 °C, 1000 m, IP20.

Using it in design

  • Check critical load in kW against the output PF (0.8 or 0.9) and select the model on kW, not kVA.
  • Use the 3% input THDI and 0.99 PF in generator sizing and supply transformer calculations.
  • Plan N+1 redundancy or capacity growth with the parallel kit option.
  • Check derating separately above 1000 m altitude and above 40 °C ambient.

Who should read it

Electrical designers selecting mid-size and large UPS systems and engineers writing specifications in Turkey.

Document contents

  1. Series features
  2. Technical specifications (input, output, static bypass, battery)
  3. Display and communication
  4. Environment, standards and options

Publication details

Authors
Güveniş
Publisher
Güveniş
Year
Year not stated
Document language
Turkish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Güveniş GVN-DSP Serisi UPS teknik özellikleri. Güveniş. https://www.guvenisregulator.com.tr/userfiles/files/GVN-DSP%20SER%C4%B0S%C4%B0%20UPS%20TR.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.