GVN-DSP Series UPS Technical Specifications
Original title GVN-DSP Serisi UPS teknik özellikleri
Güveniş
The Güvenis GVN-DSP is a 10-400 kVA three-phase IGBT-rectifier double-conversion UPS with efficiency up to 95%, input THDI of 3% or less, input PF 0.99 and IEC 62040-3 class VFI-SS-111.
On this page
Overview
The document is the Turkish-language technical specification page for Güvenis's GVN-DSP three-phase-in, three-phase-out UPS. The series uses an IGBT rectifier, IGBT inverter and DSP-controlled processor in true on-line double conversion; active input power factor correction (PF 0.99), active harmonic correction (THDI 3% or less), generator compatibility and an ECOMODE energy-saving mode are among its features.
The table lists 14 models (GVN-DSP 33010 to 33400): 10, 15, 20, 30, 40, 60, 80, 100, 120, 160, 200, 250, 300 and 400 kVA. Nominal active power depends on output power factor, for example 8/9 kW at 10 kVA and 320/360 kW at 400 kVA (power factor 0.8 or 0.9 optional). Input tolerance is -25%/+27% at 100% load, -45%/+27% at 64% load and -64%/+27% at 42% load. Static voltage regulation is under 1%, voltage THD on linear load is 2% or less, and overload is 10 minutes at 125% and 1 minute at 150%.
The static bypass works within ±10% voltage and 47-53 Hz (adjustable). The battery section lists maintenance-free dry-type batteries, 62 units (2x31) or 60 units (2x30), deep-discharge protection and temperature-compensated charging. Operating temperature is 0-40 °C, maximum altitude 1000 m, IP20; standards are EN 62040-1, EN 62040-2 and EN 62040-3 (VFI-SS-111). Options are a parallel kit, SNMP, external bypass, isolation transformer, battery cabinet and IP21.
Key points
- Range 10-400 kVA across 14 models (GVN-DSP 33010-33400); input 3F+N+PE, 380/400/415 V.
- Nominal active power depends on output PF: 8/9 kW at 10 kVA, 320/360 kW at 400 kVA (PF 0.8 or 0.9).
- Input PF 0.99 and input current THD of 3% or less; input voltage tolerance -25%/+27% at 100% load.
- Efficiency up to 95% (depends on unit power and ambient); output frequency tolerance ±0.01%.
- Overload: 10 min at 125%, 1 min at 150%; crest factor 3:1.
- Static bypass operates within ±10% voltage and 47-53 Hz; static and manual bypass are standard.
- Battery count 62 (2x31) or 60 (2x30), maintenance-free dry type; deep-discharge protection and temperature-compensated charging.
- Standards: EN 62040-1, EN 62040-2, EN 62040-3 (VFI-SS-111); 0-40 °C, 1000 m, IP20.
Using it in design
- Check critical load in kW against the output PF (0.8 or 0.9) and select the model on kW, not kVA.
- Use the 3% input THDI and 0.99 PF in generator sizing and supply transformer calculations.
- Plan N+1 redundancy or capacity growth with the parallel kit option.
- Check derating separately above 1000 m altitude and above 40 °C ambient.
Who should read it
Electrical designers selecting mid-size and large UPS systems and engineers writing specifications in Turkey.
Document contents
- Series features
- Technical specifications (input, output, static bypass, battery)
- Display and communication
- Environment, standards and options
Publication details
- Authors
- Güveniş
- Publisher
- Güveniş
- Year
- Year not stated
- Document language
- Turkish
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Güveniş GVN-DSP Serisi UPS teknik özellikleri. Güveniş. https://www.guvenisregulator.com.tr/userfiles/files/GVN-DSP%20SER%C4%B0S%C4%B0%20UPS%20TR.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.