MD PRO 4.5-10k User Manual v1.2 (09/2024), multimatic EDELSTROM
Original title MD PRO 4.5–10k Benutzerhandbuch v1.2 (09/2024)
multimatic EDELSTROM GmbH
multimatic EDELSTROM MD PRO, at 4.5, 6 and 10 kVA/kW with unity power factor, is a single-phase VFI-SS-111 online UPS with efficiency up to 94% online and 97.5% in ECO mode, and up to 4 units in parallel.
On this page
Overview
The manual (in German, 09/2024) covers the multimatic EDELSTROM MD-4500PRO, MD-6000PRO and MD11-10000PRO models. The units are continuous online converters of class VFI-SS-111 under IEC/EN 62040-3. Highlights are power factor 1.0, a rotatable touch display, temperature-controlled smart charging, programmable output segments, hot-swap battery replacement, tower and rack mounting, paralleling of up to four units and a 36-month warranty on the unit and battery. Applications are server environments, network components, IT systems and industrial plants.
The document contains general information, safety, scope of delivery, product description (types, front and rear, input and output connections, communication interfaces, LCD panel, operating modes), installation and connection, operation, troubleshooting, maintenance, technical data, decommissioning and additional information. Outputs are a terminal block, IEC 320 C19 (16 A) and C13 (10 A); C19 segment 1 and C13 segment 2 are programmable.
Technical data: 4500, 6000 and 10000 VA / W, single-phase in and out. Input is 230 VAC (220/230/240 configurable), voltage range 110 to 286 VAC at 50% load and 176 to 264 VAC at 100% load, frequency 40 to 70 Hz. Output transfer time is 0 ms and THD is below 3% on linear and 5% on non-linear load. Efficiency reaches 94% online and 97.5% in ECO mode. Backup at 80% load on internal batteries is 20, 11 and 4 minutes; each additional battery pack adds 22, 19 and 10 minutes. Charging current is 10 A, heat dissipation 270, 360 and 600 W and noise at most 51 dBA.
Key points
- Models: 4500 VA / 4500 W, 6000 VA / 6000 W, 10000 VA / 10000 W; output power factor 1; VFI-SS-111.
- Input 230 VAC (220/230/240); 110 to 286 VAC (50% load), 176 to 264 VAC (100% load); 40 to 70 Hz; generator input adjustable.
- Transfer time 0 ms; THD <3% (linear), <5% (non-linear); crest factor 3:1.
- Overload in AC mode 60 s at 105 to 125%, 30 s at 125 to 130%; in battery mode 10 s at 125 to 130%, 200 ms above 130%.
- Efficiency: up to 94% online, up to 97.5% in ECO mode.
- Backup (80% load): internal batteries 20, 11, 4 minutes; each battery pack +22, +19, +10 minutes.
- Charging current 10 A; hot-swap battery; life 5 years per EUROBAT (10 years optional).
- IP20; heat dissipation 270/360/600 W; noise ≤51 dBA; tower 440 x 132 x 750 mm; weight 19 to 21 kg (battery pack 63 kg).
Using it in design
- Add the 270 to 600 W heat dissipation to the cooling load and keep front and rear ventilation clearances per the manual's siting requirements.
- Check autonomy with internal batteries (4 to 20 min at 80% load); for longer times, set the number of battery packs from the table; each pack weighs 63 kg.
- The 10 kVA model has only 4 minutes on internal batteries; plan external battery packs against generator start-up time.
- For parallel installations, up to 4 units; specify an additional maintenance bypass for the external bypass (PDU auxiliary contact).
- Select EPO and SNMP/relay card options according to monitoring and emergency-stop requirements.
Who should read it
Engineers installing and operating single-phase 4.5 to 10 kVA UPS units for server rooms, networks and industrial loads.
Document contents
- General
- Safety
- Scope of delivery
- Product description
- Installation and connection
- Operation
- Troubleshooting
- Maintenance
- Technical data
- Decommissioning and disposal
- Additional information
Publication details
- Authors
- multimatic EDELSTROM GmbH
- Publisher
- multimatic EDELSTROM GmbH
- Year
- Year not stated
- Document language
- German
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
multimatic EDELSTROM GmbH MD PRO 4.5–10k Benutzerhandbuch v1.2 (09/2024). multimatic EDELSTROM GmbH. https://edelstrom.de/media/mm_hb_md_pro_4.5-10k_v1.2_2.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.