ONLINE USV-Systeme XANTO 6000-20000 user manual (June 2025)
Original title XANTO 6000–20000 Benutzerhandbuch 06/2025
ONLINE USV-Systeme AG
The ONLINE USV-Systeme XANTO manual covers a VFI-SS-111 class 6-20 kVA double-conversion UPS series with installation, parallel operation and technical tables; ECO efficiency 97-98%.
On this page
Overview
The manual, dated June 2025, covers the XANTO series from German manufacturer ONLINE USV-Systeme AG (active since 1988). Four models are covered: XANTO 6000 (6000 VA / 4800 W), XANTO 10000 (10000 VA / 8000 W), XANTO 10000 3/1 (10000 VA / 9000 W) and XANTO 20000 3/1 (20000 VA / 18000 W). The 6000 and 10000 are single-phase and combined rack-tower (2U); the 3/1 models are three-phase in, single-phase out. The series is true double conversion and VFI-SS-111 class per EN 62040-3.
The manual divides into installation (tower and rack mounting, battery connection, electrical installation), operation (control panel, LED and menu settings, operating states), communication (RS-232, USB, SNMP/AS400 card slot, emergency power-off EPO, DataWatch software), maintenance (battery replacement, testing), fault codes and technical data. For redundancy and parallel operation up to three units can be connected as n+1; if load exceeds nominal power the group switches automatically to parallel mode and redundancy is lost.
According to the technical table, nominal input is 230 V (6000 and 10000) or 400 V (3/1); the input voltage range depends on load, 110-300 V at 50% load and 176-300 V at full load (176-276 V L-N on the 3/1). Normal-mode efficiency is above 94% (6000, 10000) and above 92% (3/1); high-efficiency (ECO) mode is above 98% and 97%; battery mode is above 91%, 87% and 88%. Maximum losses are 600, 1000, 1440 and 2880 W. Output is 230 V ±1% (battery mode), adjustable to 208/220/230/240 V; at 208 V power derates by 20%.
On batteries: the 6000 uses a pack of 16 x 12 V / 7 Ah and the 10000 a pack of 16 x 12 V / 9 Ah (192 V); the 3/1 models use 240 V (20 x 12 V / 9 Ah). Typical bridging times are given at 50% and 100% load (cos φ 0.7) by model and number of extra battery packs; for example the XANTO 6000 gives 17 / 6 minutes with one pack and 139 / 58 minutes with five. Ambient is 0-40 °C, 0-95% humidity, IP21 protection and a 3-year warranty including battery.
Key points
- Models: XANTO 6000 (6000 VA/4800 W), 10000 (10000 VA/8000 W), 10000 3/1 (10000 VA/9000 W) and 20000 3/1 (20000 VA/18000 W).
- Class VFI-SS-111 (EN 62040-3); safety EN 62040-1, EMC EN 62040-2, CE.
- Efficiency: normal mode above 94% and 92%, ECO above 98% and 97%, battery mode above 91%, 87% and 88%.
- Maximum losses: 600 W, 1000 W, 1440 W and 2880 W.
- Input range 110-300 V at 50% load; 176-300 V at full load (176-276 V L-N on 3/1).
- Output adjustable to 208/220/230/240 V; 20% power derating at 208 V.
- Up to 3 units in n+1 redundancy or parallel; in parallel for example 3 x XANTO 6000 = 18000 VA.
- Battery pack 192 V (6000, 10000) or 240 V (3/1); XANTO 6000 bridging time is 17/6 min with 1 pack and 139/58 min with 5 packs (50%/100% load).
- MTBF 47,000 hours (6000, 10000) and 45,000 hours (3/1), excluding battery; IP21; 3-year warranty.
Using it in design
- In the 6-20 kVA range take kW capacity per model: 4800 W for the XANTO 6000, 8000 W for the 10000 (9000 W for 3/1) and 18000 W for the 20000 3/1; kVA is not equal.
- For n+1 redundancy use up to three units of equal power, and make it a design rule that redundancy is lost if load exceeds a single unit's power.
- In the energy budget keep normal-mode and ECO-mode efficiency apart; assess the protection level of ECO mode against load sensitivity.
- Take battery autonomy from the manual's 50% and 100% load (cos φ 0.7) table and add the extra battery pack weight (47-125 kg) to floor loading.
- On the 3-phase in, 1-phase out model distribute phase load evenly; input current is 3 x 24.9 A and 3 x 49.8 A.
Who should read it
Electrical designers installing UPS in small and mid-size data rooms, and installation and maintenance teams.
Document contents
- Introduction
- Safety warnings
- Installation
- Operation
- Communication and interfaces
- Maintenance
- Troubleshooting
- Support
- Technical data
- Warranty
Publication details
- Authors
- ONLINE USV-Systeme AG
- Publisher
- ONLINE USV-Systeme AG
- Year
- Year not stated
- Document language
- German
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ONLINE USV-Systeme AG XANTO 6000–20000 Benutzerhandbuch 06/2025. ONLINE USV-Systeme AG. https://www.online-usv.de/sites/default/files/2025-06/2506-benutzerhandbuch-usv-xanto-6000-20000.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.