Shtil STR1106SL / STR1110SL Operation Manual (6-10 kVA Single-Phase UPS)
Original title Штиль STR1106SL / STR1110SL руководство по эксплуатации
Shtil (Штиль)
The Russian maker Shtil's manual for 6 and 10 kVA single-phase on-line UPS: output power factor 0.9, 95% online efficiency, 99% in ECO mode, 0 ms battery transfer, 192 V internal battery and up to 78 kg.
On this page
Overview
The manual gives the description, operation, installation, maintenance and technical values of the Shtil STR1106SL (5.4 kW/6 kVA) and STR1110SL (8 kW/10 kVA) single-phase, IGBT-switched double-conversion UPS. The unit can be used as a tower or in a 19-inch rack. The document starts with safety and important-information sections, then description and operation, main specifications, connection and operation, possible faults, maintenance, storage, warranty and the internal battery specifications (Annex A).
The operation section covers product appearance, delivery contents, principle of operation, operating modes (online, ECO, battery, bypass), the control panel and monitoring tools (RS-232, RS-485, mini-USB, USB, Ethernet options). In ECO mode the load is fed directly from the mains, bypassing the rectifier and inverter; when mains voltage leaves the allowed range the unit returns to the rectifier-inverter path. The bypass and ECO thresholds are adjustable up to +/-25% of output voltage (default 15% upper, 20% lower).
Specifications: nominal input 220 V, 50 Hz, input power factor 0.992; operating range 165-310 V at 100% load, 135-310 V at 80% and 90-310 V at 60%; output 220-240 V (5 V steps), accuracy +/-2%, THDv under 2% on linear and under 4% on non-linear load, crest factor 3:1. Efficiency is 95% online, 99% via bypass or ECO and 94% on battery; transfer to battery is 0 ms, and 7 ms from ECO mode. The internal battery is 16 x 9 Ah (192 V) with 4 A charging and hot-swap.
This is a product manual and gives values for these two models only. Values that affect design are in the table: ambient 5-40 degrees C, humidity 0-80% (non-condensing), IP20, service life 10 years, warranty 24 months.
Key points
- Models: STR1106SL 5.4 kW/6 kVA and STR1110SL 8 kW/10 kVA; output power factor 0.9; on-line (double conversion), IGBT switches, tower or rack.
- Input: single phase 220 V, 50 Hz; input power factor 0.992; operating range 165-310 V at 100% load, 135-310 V at 80% and 90-310 V at 60%; maximum input current 38 A (6 kVA) and 55 A (10 kVA); maximum bypass current 60 A.
- Output: 220-240 V adjustable, accuracy +/-2%; THDv under 2% (linear) and under 4% (non-linear); crest factor 3:1; maximum output current 27 A and 45 A.
- Efficiency: 95% online, 99% via bypass or ECO, 94% on battery.
- Transfer time: online to battery 0 ms, from ECO mode to battery 7 ms.
- Overload: no time limit at 101-105%, at least 5 s at 105-150%, under 5 s above 150%.
- Batteries: 16 x 9 Ah (192 V), two internal battery blocks, hot-swappable; charging current 4 A; cold start and LVD deep-discharge protection; 10-second, timed and full-discharge tests.
- Dimensions 176 x 483 x 691 mm (horizontal in rack, with brackets) or 446 x 295 x 691 mm (vertical); weight up to 78 kg; fan cooled.
- Ambient 5-40 degrees C, storage -40 to 40 degrees C, humidity 0-80%; IP20; service life 10 years; warranty 24 months.
Using it in design
- With an output power factor of 0.9, base load calculation on active power limited to 5.4 kW for the 6 kVA model and 8 kW for the 10 kVA model.
- Judge the wide input range (down to 90 V as load falls) against weak-grid or generator conditions; the lower limit is 165 V at 100% load.
- If ECO mode is used, weigh the 7 ms battery transfer against load tolerance and the thresholds adjustable up to +/-25%.
- For rack mounting check the 176 mm (4U) height, 691 mm depth and 78 kg weight against rack load capacity; also use the rack mounting kit.
- Put the hot-swap internal battery blocks, the 10-year service life and the 5-40 degrees C ambient limit into the battery and maintenance plan.
Who should read it
Electrical designers, field technicians and operations staff installing and running 6-10 kVA single-phase UPS in small IT rooms, networks and automation systems.
Document contents
- Safety and important information
- Description and operation (appearance and dimensions, delivery contents, principle of operation, operating modes, control panel, monitoring tools)
- Main specifications
- Connection and operation (preparation, installation, commissioning, EPO connector, emergency conditions)
- Possible faults
- Maintenance
- Storage and transport
- Manufacturer's warranties
- Annex A: internal battery specifications
Publication details
- Authors
- Shtil (Штиль)
- Publisher
- Shtil (Штиль)
- Year
- Year not stated
- Document language
- Russian
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Shtil (Штиль) Штиль STR1106SL / STR1110SL руководство по эксплуатации. Shtil (Штиль). https://www.shtyl.ru/upload/iblock/b69/rk7b1vjki3on5kt04sc7526kh6kh3ske/rukovodstvo_po_ehkspluatacii_ibp_str_6_10.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.