EVO DSP PLUS TM 10-15-20 kVA PF 0.9
Original title EVO DSP PLUS TM 10–15–20 kVA PF 0.9
Tecnoware
Tecnoware's EVO DSP PLUS TM is a transformerless double-conversion VFI-SS-111 UPS in 10, 15 and 20 kVA (9, 13.5, 18 kW), three-phase in and single-phase out, with 94% full-load efficiency.
On this page
Overview
Tecnoware's 2020 data sheet presents the EVO DSP PLUS TM series as a double-conversion, transformerless on-line UPS recommended for LAN, data-centre, industrial and electromedical equipment. Power factor is 0.9: 10 kVA/9 kW, 15 kVA/13.5 kW and 20 kVA/18 kW. The classification is VFI-SS-111, the rectifier uses IGBTs, transfer time in on-line mode is 0 ms, and the unit is generator-compatible.
Input is three-phase plus neutral, phase-to-phase 360/380/400/415 V and phase-to-neutral 208/220/230/240 V. The input voltage range is 176-300 V at 100% load and 110-300 V at 50% load (phase-to-neutral); the input frequency range is +/-7%, THDi is 4% or less and input power factor is 0.99. The output is single-phase plus neutral at 208-240 V with +/-1% regulation, +/-0.1 Hz frequency stability, 3:1 crest factor and voltage THD below 3% on linear and below 5% on distorting load.
Overload capability differs by model. In on-line mode the 10 kVA model gives 110% for 30 minutes and 130% for 5 minutes; the 15 kVA gives 110% for 15 minutes and 130% for 30 seconds; the 20 kVA gives 110% for 5 minutes and 130% for 1 second. Above 130% it is 1 second or instant for all. Battery-mode times are shorter. Efficiency is defined as 94% in double conversion at 100% load per IEC 62040-3.
Physically the 10 and 15 kVA units are 19 x 68.8 x 44.2 cm (W x H x D) and the 20 kVA unit is 25 x 82.6 x 81.5 cm; weights run from 25 to 140 kg depending on code. The /00 version has no internal battery; the /C, /D, /E and /2D, /2E versions carry 16 or 32 internal lead-acid elements. An external battery box is available for extended autonomy. Operating temperature is 0-55 C (20-25 C recommended for battery life), humidity below 95%, altitude 3000 m and protection IP20.
Key points
- Three ratings: 10 kVA/9 kW, 15 kVA/13.5 kW, 20 kVA/18 kW; power factor 0.9; VFI-SS-111 (IEC EN 62040-3).
- Efficiency is 94% (double conversion, 100% load, IEC 62040-3); on-line transfer time is 0 ms.
- Input is 3Ph+N, phase-to-phase 360/380/400/415 V; range 176-300 V (100% load) and 110-300 V (50% load) phase-to-neutral; THDi 4% or less; input power factor 0.99.
- Output is 1Ph+N, 208/220/230/240 V; regulation +/-1%; frequency +/-0.1 Hz; crest factor 3:1; THD below 3% on linear load.
- Overload (on-line): 10 kVA 110%/30 min and 130%/5 min; 15 kVA 110%/15 min and 130%/30 s; 20 kVA 110%/5 min and 130%/1 s.
- Size: 10-15 kVA is 19 x 68.8 x 44.2 cm; 20 kVA is 25 x 82.6 x 81.5 cm; weight is 25-140 kg by code.
- No internal battery (/00) or 16 or 32 elements; the external battery box is a 192 V class unit with selectable charge current of 0.7-4.4 A.
- Operation at 0-55 C, humidity below 95%, 3000 m, IP20; CE; RS232, USB, EPO and a slot for SNMP, dry contact or MODBUS.
Using it in design
- Size capacity in kW (9, 13.5, 18 kW); with power factor 0.9 a 15 kVA UPS carries only 13.5 kW.
- Use the input THDi (4% or less) and 0.99 power factor in generator compatibility checks and cable sizing.
- Compare the overload time table (especially 1 s at 130% for the 20 kVA) with load inrush.
- Separate internal battery scope using the code suffix (/00 has none) and calculate the number of external battery boxes from the runtime requirement.
- Check load balance and phase allocation when this single-phase-output UPS is used in three-phase distribution.
Who should read it
Electrical designers selecting single-phase-output UPS for mid-size IT rooms and data-centre loads.
Document contents
- Main specifications
- UPS specifications
- Accessories
- Battery box specifications
Publication details
- Authors
- Tecnoware
- Publisher
- Tecnoware
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Tecnoware EVO DSP PLUS TM 10–15–20 kVA PF 0.9. Tecnoware. https://tecnoware.com/Downloads/EVO_DSP_PLUS_10-20_TM/EVO_DSP_PLUS_10-20_TM_ENG.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.