B.B. Tech (Changsha) HR22-12 datasheet, p.1
Original title B.B. Tech (Changsha) HR22-12 datasheet: B/4 REV May 2021, p.1
B.B. Battery
A one-page datasheet for B.B. Battery's HR22-12, a 12 V, 20 Ah VRLA AGM battery designed for high-rate use including UPS, with specifications and constant-power and constant-current discharge tables.
On this page
Overview
The datasheet presents a maintenance-free VRLA battery with no water topping-up, no free acid, non-spillable and usable in any orientation except inverted. Absorbent Glass Mat technology gives efficient gas recombination. The battery is designed for high-rate use, and power density at 5-15 minute discharge rates is stated as 30 percent higher than the BP series. Service life is 5-7 years according to Eurobat (20 C), general purpose class.
Specifications: nominal voltage 12 V, 20 Ah at the 10-hour rate (final voltage 1.75 V per cell), approximate weight 6500 g, internal resistance below 9 milliohm fully charged, maximum discharge current 300 A for 5 s and maximum charge current 6.0 A. Charge temperature is 0-40 C, discharge -20 to 50 C and storage -20 to 40 C. The container is ABS (UL94 HB) as standard, with optional flame-retardant ABS (UL94 V-0, HR22-12FR).
The sheet contains two discharge tables. The constant-power table gives watts for times from 5 to 120 minutes at end voltages of 1.30-1.80 V per cell at 25 C; for example 902.0 W at 5 minutes and 161.7 W at 60 minutes to 1.80 V. The constant-current table gives amperes for the same conditions, for example 80.54 A at 5 minutes and 13.48 A at 60 minutes to 1.80 V.
Terminal type B1 (M5 bolt and nut) is standard and T2 and I1 are optional; initial tightening torque is 2.5 N-m for B1 and 4.0 N-m for I1 (±5 percent). Standards are IEC 61056-1, JIS C 8702-1 and GB/T 19639.1. The footer of the downloaded sheet reads B/4 REV May 2024, while the record cites a May 2021 revision.
Key points
- Nominal voltage 12 V; capacity 20 Ah at the 10-hour rate (1.75 V/cell); approximate weight 6500 g.
- Internal resistance below 9 milliohm fully charged; maximum discharge current 300 A (5 s); maximum charge current 6.0 A.
- Temperature: charge 0-40 C, discharge -20 to 50 C, storage -20 to 40 C.
- Constant power, 25 C, 1.80 V/cell: 5 min 902.0 W, 10 min 644.2 W, 15 min 446.1 W, 30 min 289.3 W, 60 min 161.7 W, 120 min 89.2 W.
- Constant current, 25 C, 1.80 V/cell: 5 min 80.54 A, 10 min 56.51 A, 30 min 24.52 A, 60 min 13.48 A, 120 min 7.43 A.
- Service life 5-7 years (Eurobat, 20 C, general purpose).
- Power density at 5-15 minute discharge is 30 percent higher than the BP series.
- Terminal B1 standard, T2 and I1 optional; initial torque B1 2.5 N-m, I1 4.0 N-m.
- Standards IEC 61056-1, JIS C 8702-1, GB/T 19639.1; container ABS (UL94 HB), UL94 V-0 for HR22-12FR.
Using it in design
- When sizing UPS batteries for short (5-15 min) discharge, use the constant-power table and match the per-cell end voltage to the UPS cut-off voltage.
- Reflect ambient temperature and the Eurobat 20 C life condition in the battery replacement plan.
- Check the 6.0 A charge current limit in charger and parallel string design.
- Treat the weight as an approximate value; obtain exact mass from the manufacturer for rack load calculation.
- Specify the HR22-12FR variant where a flame-retardant container is required.
Who should read it
UPS and DC system designers selecting VRLA batteries, and maintenance engineers.
Document contents
- Features and applications
- Specifications
- Dimensions and terminals
- Constant power discharge characteristics
- Constant current discharge characteristics
Publication details
- Authors
- B.B. Battery
- Publisher
- B.B. Battery
- Year
- 2021
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
B.B. Battery (2021). B.B. Tech (Changsha) HR22-12 datasheet: B/4 REV May 2021, p.1. B.B. Battery. https://bb-battery.rs/wp-content/uploads/2024/02/HR22-12.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.