NorthStar NSB UPS Battery Family Brochure (January 9, 2024)
Original title NorthStar NSB UPS Battery Family Brochure: January 9, 2024, p.3
EnerSys
An EnerSys brochure for the pure-lead, high-rate 12 V NSB UPS monobloc battery family, giving dimensions, weight, 15-minute power and electrical parameters for seven models.
On this page
Overview
The document presents the NSB series for data centre, industrial, energy storage and UPS applications. The manufacturer states that the batteries perform well at high discharge rates down to under 15 minutes and, thanks to a 99.9% pure-lead design, reach a design life of more than 15 years at 20 degrees C (Very Long Life, over 12 years, in the EUROBAT classification). The operating temperature range is minus 40 to plus 65 degrees C and shelf life is up to 24 months.
Construction features include thin plates for large surface area and low resistance, corrosion-resistant brass terminals, a high-modulus PPO plastic case (non-halogenated, UL 94 V0 and LOI of at least 28%) and front-access terminals. The batteries are classed as non-hazardous cargo under DOT 49CFR173.159. An integrated BMS platform, integrated breakers and fuses and data communication are offered as part of cabinet solutions.
The technical table gives seven 12 V models: NSB12-170RT, 245RT, 365RT, 425RT, 540, 650RT and 730RT. For each model it lists dimensions, weight, terminal torque (8.0 Nm for all), 15-minute (4C) power to 1.67 V per cell, float voltage, conductance, 1 kHz impedance, short-circuit current and the silver-equivalent product name. The 15-minute power values are stated separately for 20 and 25 degrees C and are not Ah capacities.
The brochure also gives a sizing example comparing a front-terminal cabinet system with a monobloc system: from 1 to 5 cabinets for UPS ratings of 240, 480 and 720 kW, with width, depth, height and weight. It is a marketing document that names Telcordia SR4228, IEC 60896, UL approval and UN2800 certification, plus ISO 9001 and ISO 14001 registration.
Key points
- Seven 12 V models: NSB12-170RT, 245RT, 365RT, 425RT, 540, 650RT, 730RT.
- 15-minute (4C) power at 20 / 25 degrees C to 1.67 V per cell: 154/164, 233/248, 342/365, 385/410, 506/540, 608/649 and 682/728 W.
- Weights are 15, 22, 33, 35, 45, 54 and 62 kg respectively; terminal torque is 8.0 Nm on all.
- Float voltage 2.28 / 2.27 V per cell (20 / 25 degrees C values).
- Short-circuit current ranges from 1,500 A (170RT) to 6,000 A (730RT); 1 kHz impedance from 2.25 to 4.1 mOhm.
- Design life above 15 years at 20 degrees C; operating range minus 40 to plus 65 degrees C; shelf life up to 24 months.
- Case material is non-halogenated PPO, UL 94 V0 with LOI of at least 28%; terminals are front access.
- Standards: Telcordia SR4228, IEC 60896, Bellcore GR-63-Core, UL approval, UN2800.
Using it in design
- Size UPS runtime from the power table, not from Ah: take the 15-minute W per block from the 20 or 25 degrees C column that matches battery room temperature.
- For each UPS rating, take the number of series blocks and total weight from the document's table and check floor loading and rack strength; one cabinet in the example weighs 2824 kg.
- Carry the short-circuit current and the 8.0 Nm terminal torque into battery breaker selection and the installation procedure.
- Match the float voltage setting to 2.27-2.28 V per cell and verify temperature compensation separately.
- Limit the family to the seven published models and do not derive unpublished dimensions or performance values.
Who should read it
Electrical designers sizing UPS battery systems and engineers cataloguing battery models.
Document contents
- Features and benefits
- Front terminal cabinet sizing example
- NSB12 model tables
- Compliance and standards
Publication details
- Authors
- EnerSys
- Publisher
- EnerSys
- Year
- 2024
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document