First National Battery EXCIS GroE Vented Lead Acid Planté Cells (pp.3–4)

Original title First National Battery EXCIS GroE Vented Lead Acid Batteries: pp.3–4

First Battery

First National Battery's EXCIS GroE range is a series of 2 V vented Planté standby cells from 92 to 1932 Ah (10 h rate), with a 2.25 V/cell float guideline and a stated life expectancy of 20 years or more.

On this page

Overview

The document is a product brochure for the EXCIS GroE range of vented lead-acid standby cells made in South Africa. The cells use Planté technology, produced since the early 1960s, and are stated to conform to BS 6290 (1999), IEC 60896-11:2002 and DIN 40738, built in an ISO 9001 and ISO 14001 facility. Listed duties include power stations, telephone exchanges, switchgear operation, telecommunications, emergency lighting and diesel starting.

The construction section describes a positive plate of 10 mm pure-lead grid, a negative plate of industrial pasted grid, separators of polyester mat reinforced phenolic resin and transparent SAN containers. The clear container allows visual inspection, and a hydrometer reading indicates state of charge. Optional Hydro-save recombination plugs lengthen top-up intervals.

The technical section gives about 2.25 V/cell float at 25 °C, a specific gravity of 1.225 for a fully charged cell, 2 V nominal per cell (55 cells for a 110 V battery) and capacity rated at the 10-hour rate. Ampere-hour efficiency is 90%, so recharge needs the discharged Ah plus 11%. The table that follows lists 10, 3 and 1 hour capacities, initial charge current, weight, acid quantity and dimensions for each type.

As a limit, the weights in the table are filled-cell mass and acid mass listed separately, and are not cabinet or rack weight. Stillage mass, cell centres and height must be added separately in the room layout.

Key points

  1. Nominal voltage 2 V per cell; a 110 V battery needs 55 cells.
  2. Rated capacity runs from 92 Ah (3 GroE) to 1932 Ah (18 GroE 1800) at the 10-hour rate.
  3. Example: the 6 GroE 150 type gives 174 Ah (10 h), 135 Ah (3 h) and 101 Ah (1 h).
  4. Float guideline is about 2.25 V/cell at 25 °C; fully charged specific gravity is 1.225.
  5. Ampere-hour efficiency is 90%; a full recharge needs the discharged amount plus 11%.
  6. The positive plate is 10 mm pure lead grid; the maker states no capacity fall-off with age and a life of 20 years or more.
  7. Sample weights: 3 GroE 15.2 kg (acid 5.4 kg, 4.4 L); 18 GroE 450 type 53.1 kg; the largest, 18 GroE 1800 type, 223.6 kg.
  8. Cells connect edge-to-edge or face-to-face with M8 fasteners; copper-inserted terminals are available for high-rate use.

Using it in design

  • For battery-room floor loading, use the table's filled-cell mass but add rack and connector mass separately, since the table does not give cabinet weight.
  • Set cell count from the DC bus voltage (2 V per cell) and set float at 2.25 V/cell with temperature compensation in the UPS charger.
  • Size autonomy from the column for the actual discharge time and final voltage, not from the 10-hour rating.
  • Vented cells emit hydrogen, so design room ventilation and electrolyte spill containment.

Who should read it

Electrical designers selecting stationary batteries and engineers calculating battery-room layout and floor loading.

Document contents

  1. Product and service benefits
  2. Design features
  3. Technical details (float charging, specific gravity, voltage, capacity, installation, recharging)
  4. GroE capacities, weights and dimensions table

Publication details

Authors
First Battery
Publisher
First Battery
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

First Battery First National Battery EXCIS GroE Vented Lead Acid Batteries: pp.3–4. First Battery. https://www.battery.co.za/file-downloads/Standby/Excis_GRoE_Vented_Lead_Acid_Plante_Cells.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.