Heliar 2019 product catalogue: Linha Estacionaria, printed p.14
Heliar
The 2019 product catalogue published by Heliar (Johnson Controls) for the Brazilian market carries, on page 14, the selection table for the Freedom DF series of stationary monobloc batteries. Ten models span 26 Ah to 225 Ah at the C20 rate and 25 °C, with a float voltage of 13.2 to 13.8 V.
On this page
Overview
The document is the Heliar brand's Portuguese-language product catalogue for 2019 and deals mostly with automotive batteries: the Super Free, Original, EFB, AGM, Frota (heavy vehicle) and motorcycle lines, plus an extensive application catalogue that matches batteries to vehicle models. Heliar batteries are made by Johnson Controls. The part relevant to data-centre and critical-power design is the stationary line (Linha Estacionária) table on printed page 14. The catalogue describes these batteries as suited to deep discharge and highlights approval by ANATEL, the Brazilian telecommunications agency.
The stationary table sets ten models side by side: DF300, DF500, DF700, DF1000, DF1500, DF2000, DF2500, DF3000, DF4100 and DF4000. For each one it gives three capacities at 25 °C: the 10-hour (C10), 20-hour (C20) and 100-hour (C100) discharge. The smallest model, DF300, is rated 24, 26 and 30 Ah respectively; the two largest, DF4100 and DF4000, are rated 200 Ah (C10), 220 and 225 Ah (C20) and 240 Ah (C100). The same table lists length, width, height, weight and the minimum and maximum terminal tightening torque.
Charging parameters appear beneath the table. Float voltage is 13.2 to 13.8 V at 25 °C, and charge and equalisation voltage is 14.4 to 15.5 V. Temperature compensation is given as an explicit rule: subtract 0.033 V for each 1 °C above 25 °C and add 0.033 V for each 1 °C below it. The applications listed include UPS, PABX and telephone exchanges, emergency lighting, solar and wind energy, electrical substations, banks, telecommunications and data banks.
The table describes individual 12 V monoblocs; cabinet-level or string-level capacity, short-duration constant-power discharge values in the range of minutes, and the end voltage behind the capacity ratings are not on this page. The page therefore suits preliminary sizing and layout for long-duration telecom, solar and small UPS applications, while high-current UPS discharges of 5 to 15 minutes call for the manufacturer's detailed discharge tables.
Key points
- Ten models: DF300, DF500, DF700, DF1000, DF1500, DF2000, DF2500, DF3000, DF4100 and DF4000; capacities are stated at 25 °C.
- C20 capacities are 26, 36, 45, 60, 80, 105, 150, 170, 220 and 225 Ah respectively.
- C10 capacities are 24, 30, 41, 54, 76, 94, 130, 156, 200 and 200 Ah; C100 capacities are 30, 40, 50, 70, 93, 115, 165, 185, 240 and 240 Ah.
- Weights range from 8.8 kg (DF300) to 60.3 kg (DF4100); DF1000 weighs 14.7 kg, DF2000 27.1 kg and DF3000 48.3 kg.
- Dimensions (length × width × height): DF300 175 × 175 × 175 mm, DF2000 330 × 172 × 240 mm, DF3000 511 × 213 × 230 mm, DF4100 525 × 275 × 250 mm.
- Float voltage is 13.2 to 13.8 V at 25 °C; charge and equalisation voltage is 14.4 to 15.5 V.
- Temperature compensation: 0.033 V for each 1 °C of deviation from 25 °C (subtracted when warmer, added when colder).
- Terminal torque: 9 Nm minimum and 11 Nm maximum on most models; 13.6 to 20.3 Nm for DF1500 and DF2000.
- The line is ANATEL approved and is described for deep-discharge stationary duty.
Using it in design
- Size the battery from the capacity column that matches the discharge time: the same DF2000 monobloc gives 94 Ah at C10, 105 Ah at C20 and 115 Ah at C100.
- Set the rectifier or UPS charger to the 13.2 to 13.8 V float range per monobloc and apply the 0.033 V/°C compensation for the battery room temperature.
- For rack and floor loading, multiply the monobloc weight in the table by the number of blocks per string, and plan handling and service clearance separately for the 60 kg class DF4100 and DF4000.
- State terminal torque by model in the installation instructions: 13.6 to 20.3 Nm for DF1500 and DF2000, 9 to 11 Nm for the other models.
- For UPS autonomies measured in minutes, use this table only for preselection and request the constant-power discharge table from the manufacturer.
Who should read it
Electrical designers selecting stationary batteries for telecom, solar and small UPS systems, and engineers procuring in the Brazilian market.
Document contents
- Johnson Controls; Baterias Heliar: Benefícios exclusivos
- Tecnologia PowerFrame; Proteção 24 Horas
- Linha Super Free, Linha Original, Linha EFB, Linha AGM, Linha Frota, Linha Moto
- Linha Estacionária: aplicações, modelos, tensão de flutuação, compensação de temperatura
- Modelos e características elétricas
- Catálogo de aplicação
Publication details
- Authors
- Heliar
- Publisher
- Heliar
- Year
- 2019
- Document language
- Portuguese
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Heliar (2019). Heliar 2019 product catalogue: Linha Estacionaria, printed p.14. Heliar. https://leaodasbaterias.com.br/wp-content/uploads/2020/01/Catalogo-Heliar-2019.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.