SEC Microlyte MRT Series brochure: pp.4-6 dimensional tables

Original title SEC Microlyte MRT Series brochure: pp.4–6 dimensional tables

SEC Industrial Battery

SEC's Microlyte MRT is a sealed AGM VRLA battery from 3.3 to 275 Ah; the brochure's pp.4-6 tables give capacity, weight, dimensions, internal resistance, short-circuit and maximum charge current for 6 V and 12 V blocks (12-MRT-275: 248 Ah, 73 kg).

On this page

Overview

The brochure presents the SEC Microlyte MRT series as a sealed AGM rechargeable lead-acid battery that operates safely in any position. The series is designed for both cycling and float service: the positive grid is gravity cast from a high-tin lead-calcium alloy and achieves 250 cycles at 80% depth of discharge. Capacity ranges from 3.3 Ah to 275 Ah; applications named are UPS systems, telecommunications and emergency lighting.

On maintenance, over 99% of gases generated in normal operation recombine inside the battery, so no electrolyte topping or gravity readings are needed. A one-way valve (VRLA) opens on excess pressure; the battery is spill-proof with explosion-proof vents, and a Japanese-made triple-post seal protects against leakage. Low internal resistance, cooler running and faster recharge and low self-discharge for long storage are cited. SEC says product consistency lowers the risk of batteries going out of phase in series and parallel strings and mentions ISO 9001:2015 certification.

The dimension tables give, for each block type, nominal capacity (C/10 at 1.75 V per cell), weight (kg and lb), length, width and height (mm and inch), short-circuit current (A), maximum charge current (A), internal resistance (mOhm) and female terminal type. 6 V models run from 6-MRT-10 (9.5 Ah) to 6-MRT-230 (210 Ah), and 12 V models from 12-MRT-3.3 (3 Ah) to 12-MRT-275 (248 Ah). For example, 12-MRT-100 is 90 Ah, 25.8 kg, 307 x 170 x 227 mm, 2650 A and 4.3 mOhm; 12-MRT-275 is 248 Ah, 73.0 kg, 522 x 269 x 245 mm, 6464 A and 1.9 mOhm.

Key points

  1. Sealed AGM VRLA; capacity 3.3-275 Ah; 6 V and 12 V blocks; cyclic and float service.
  2. 250 cycles at 80% DOD; positive grid of high-tin lead-calcium alloy.
  3. Over 99% of gases recombine; no water addition or gravity readings.
  4. 12-MRT-100: 90 Ah, 25.8 kg, 307 x 170 x 227 mm, short circuit 2650 A, max charge 17.5 A, 4.3 mOhm, terminal FT4.
  5. 12-MRT-200: 180 Ah, 52.0 kg, 532 x 207 x 240 mm, 4700 A, 2.3 mOhm.
  6. 12-MRT-275: 248 Ah, 73.0 kg, 522 x 269 x 245 mm, 6464 A, max charge 48.2 A, 1.9 mOhm.
  7. 6-MRT-230: 210 Ah, 31.5 kg, 243 x 188 x 275 mm, 5500 A, 2.2 mOhm; 6-MRT-10: 9.5 Ah, 1.69 kg.
  8. 12-MRT-3.3: 3 Ah, 1.24 kg, 85 A short circuit, 60 mOhm.
  9. Applications: UPS systems, telecommunications, emergency lighting.

Using it in design

  • In UPS backup design the nominal Ah is at the C/10 rate; use the manufacturer's 15-minute or relevant discharge tables, as these pages give only dimensional and electrical summary data.
  • Use each model's short-circuit current (for example 2650 A for 12-MRT-100) and internal resistance in DC protection and fuse selection; string resistance adds up with block count.
  • Match charger current limits to the maximum charge current (for example 17.5 A for 12-MRT-100).
  • Use model dimensions and weight (up to 73 kg) as inputs to handling and rack load checks in the rack and cabinet layout.
  • Match the terminal type (ST1, ST2, FT2-FT5) to the busbar and cable connection design.

Who should read it

Electrical engineers selecting VRLA batteries for UPS and telecom backup and designing DC protection and battery room layouts.

Document contents

  1. Microlyte MRT series
  2. Product features
  3. Applications
  4. Battery dimensions and data (6 V and 12 V models)

Publication details

Authors
SEC Industrial Battery
Publisher
SEC Industrial Battery
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only. Original publisher HTTP URL retained as a bibliographic link. Its HTTPS counterpart could not be verified on 2026-11-16; no content was downloaded or redistributed.

Citation

SEC Industrial Battery SEC Microlyte MRT Series brochure: pp.4–6 dimensional tables. SEC Industrial Battery. http://secbattery.com/wp-content/uploads/2015/04/MICROLYTE-Red-Top-6-12MRT-SERIES-Brochure.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.