ENAG ALMIV Bureau Veritas Type Approval 07671/F0 BV
Bureau Veritas
A three-page type approval certificate issued by Bureau Veritas Marine & Offshore on 7 July 2023 for ENAG's ALMIV AC/AC UPS and ONS DC/AC inverters, based on its rules for classification of steel ships.
On this page
Overview
The certificate attests that ENAG of Quimper, France found ALMIV type AC/AC UPS and ONS type DC/AC inverters compliant with the Bureau Veritas Rules for the Classification of Steel Ships. It expires on 7 July 2028 and supersedes certificate 07671/E0 BV of 7 November 2017. It is not valid without the full attached schedule.
The schedule lists 50/60 Hz single- or three-phase UPS models by power factor. At cos phi 0.7: ALMIV 500, 700, 900, 1200, 1500 and 2000 VA. At cos phi 0.8: ALMIV 2600, 3500, 5000, 7500, 10000, 12500, 15000 and 20000 VA. For inverters at cos phi 1: ONS 400, 750, 1200, 2300, 3000, 4000, 6000, 8000, 10000, 12000, 15000 and 20000 VA.
The application and limitation section states that the approval also applies to ships with AUT-UMS, AUT-CCS, AUT-PORT and AUT-IMS notations, that equipment was tested to IACS UR E10 rev 8, and that the dry heat test was at 55 C. It also notes the product is a priori not suitable for mounting in consoles or housings together with other heat-dissipating power equipment. The product falls in category HBV of NR320 and needs no separate BV product certificate.
The document is a product type approval; it does not mean equipment acceptance testing or suitability of a particular installation. For a data-centre designer its value is as a reference for the discrete rated powers of the ALMIV and ONS series and the marine test conditions (EMC, heat).
Key points
- Certificate no. 07671/F0 BV, file AP 3018, product code 2897H; issued 7 July 2023, expires 7 July 2028.
- ALMIV UPS at cos phi 0.7: 500, 700, 900, 1200, 1500, 2000 VA.
- ALMIV UPS at cos phi 0.8: 2600, 3500, 5000, 7500, 10000, 12500, 15000, 20000 VA.
- ONS inverter at cos phi 1: 400, 750, 1200, 2300, 3000, 4000, 6000, 8000, 10000, 12000, 15000, 20000 VA.
- Equipment was tested to IACS UR E10 rev 8; the dry heat test was at 55 C.
- Mounting in consoles or housings with other heat-dissipating power equipment is a priori not suitable.
- The product is in category HBV of NR320 and needs no BV product certificate.
- Test reports include EMC (KENTA, July 2007) and ENAG and EMITECH reports from 2022-2023.
Using it in design
- Record ALMIV and ONS models by discrete rated power and power factor; do not assume a continuous range.
- For ship or marine applications, attach the certificate expiry date and full schedule to the project documents.
- Verify in the layout that the unit is not housed with heat-dissipating equipment in the same enclosure.
- Treat the certificate as type approval; do not use it in place of installation or acceptance testing.
Who should read it
Designers and procurement engineers needing documentation for ALMIV and ONS series UPS and inverters in marine, offshore or special environments.
Document contents
- Certificate page
- Product description (ALMIV, ONS models)
- Documents and drawings
- Test reports
- Application and limitation
- Production survey requirements
- Marking of product
- Others
Publication details
- Authors
- Bureau Veritas
- Publisher
- Bureau Veritas
- Year
- 2023
- Document number
- 07671/F0 BV
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Bureau Veritas (2023). ENAG ALMIV Bureau Veritas Type Approval 07671/F0 BV. Bureau Veritas. 07671/F0 BV. https://www.enag.fr/wp-content/uploads/2024/04/CERTIFICAT-BV-ALMIV_07671_F0-valide-280707.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.