Chicago Digital Power UPO11-2 AX catalogue, technical data

Original title Chicago Digital Power UPO11-2 AX catalogue, technical data p.4

Chicago Digital Power

Technical table for the CDP UPO11-2 AX single-phase double-conversion UPS: 2000 VA / 1800 W, 120 VAC, six 12 V/7 Ah batteries, 90% AC-mode and 97% eco-mode efficiency, 23.2 kg.

On this page

Overview

The catalogue page carries the technical table of the Chicago Digital Power (CDP) UPO11-2 AX online UPS. The unit is a single-phase double-conversion model rated 2000 VA / 1800 W at 120 VAC nominal. Its input voltage range is 55 to 150 VAC (+/-3%), frequency range 40-70 Hz and power factor 0.99 or higher at full load.

Output voltage is selectable at 100, 110, 115, 120 or 127 VAC with +/-1% regulation, 50 or 60 Hz +/-0.1 Hz in battery mode, 3:1 crest factor and pure sine wave. THD is at most 2% on linear and 4% on non-linear load, and transfer from AC to battery mode is zero. Overload gives an alarm at 100-110%; between 110% and 130% the unit shuts down in 30 seconds on battery, or goes to bypass when the utility is normal.

Efficiency is 90% in AC mode and 97% in eco mode. The battery is 6 x 12 V/7 Ah, charge voltage 82.1 VDC +/-1%, typical recharge 3 hours to 95%; backup time is given as 6 minutes at full charge and 15 minutes at half charge. Net weight is 23.2 kg, ambient 0-45 C at 0-90% RH, noise below 50 dBA at 1 m. Certifications listed include NOM, ISO 9001, ISO 14001, CIDET, TUV and UL.

The dimension row reads 190 x 318 x 421 mm and is labelled D x H x W; its consistency with the product orientation should be confirmed. The charge-current row is written in Ah, so it should not be taken as a design input. The efficiency rows name no load point, so no efficiency curve can be drawn.

Key points

  1. Capacity 2000 VA / 1800 W, 120 VAC input, input window 55-150 VAC +/-3%.
  2. Output selectable 100/110/115/120/127 VAC; +/-1% regulation, pure sine, crest factor 3:1.
  3. THD at most 2% (linear) and 4% (non-linear); zero transfer time.
  4. Efficiency: 90% in AC mode, 97% in eco mode.
  5. Battery 6 x 12 V/7 Ah; charge voltage 82.1 VDC; typical 3 h to 95%.
  6. Backup: 6 min at full charge, 15 min at half charge.
  7. Net weight 23.2 kg; 0-45 C, 0-90% RH, below 50 dBA.
  8. Communication: smart RS232 or USB, optional SNMP.

Using it in design

  • For small critical loads (network, telecom) compare the 1800 W real-power limit with the load list; the VA figure can mislead.
  • Weigh the 6 and 15 minute backup times against generator start time and controlled-shutdown needs.
  • When using eco mode (97%), assess the protection level in that mode against load sensitivity.
  • Confirm the dimension row with the manufacturer before using it as a firm layout figure.
  • Carry the RS232/USB and optional SNMP card into the BMS or DCIM plan.

Who should read it

Electrical engineers selecting small UPSs and telecom or network-room designers.

Document contents

  1. Capacity
  2. Input
  3. Output
  4. Efficiency
  5. Batteries
  6. Physical
  7. Environment
  8. Control and certifications

Publication details

Authors
Chicago Digital Power
Publisher
Chicago Digital Power
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Chicago Digital Power Chicago Digital Power UPO11-2 AX catalogue, technical data p.4. Chicago Digital Power. https://www.cdpenergy.com/Content_Elements/downloads/Catalogs/26-Catalog%20UPO11-2%20AX%20ENG.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.