Chicago Digital Power UPO11-2 AX catalogue, technical data
Original title Chicago Digital Power UPO11-2 AX catalogue, technical data p.4
Chicago Digital Power
Technical table for the CDP UPO11-2 AX single-phase double-conversion UPS: 2000 VA / 1800 W, 120 VAC, six 12 V/7 Ah batteries, 90% AC-mode and 97% eco-mode efficiency, 23.2 kg.
On this page
Overview
The catalogue page carries the technical table of the Chicago Digital Power (CDP) UPO11-2 AX online UPS. The unit is a single-phase double-conversion model rated 2000 VA / 1800 W at 120 VAC nominal. Its input voltage range is 55 to 150 VAC (+/-3%), frequency range 40-70 Hz and power factor 0.99 or higher at full load.
Output voltage is selectable at 100, 110, 115, 120 or 127 VAC with +/-1% regulation, 50 or 60 Hz +/-0.1 Hz in battery mode, 3:1 crest factor and pure sine wave. THD is at most 2% on linear and 4% on non-linear load, and transfer from AC to battery mode is zero. Overload gives an alarm at 100-110%; between 110% and 130% the unit shuts down in 30 seconds on battery, or goes to bypass when the utility is normal.
Efficiency is 90% in AC mode and 97% in eco mode. The battery is 6 x 12 V/7 Ah, charge voltage 82.1 VDC +/-1%, typical recharge 3 hours to 95%; backup time is given as 6 minutes at full charge and 15 minutes at half charge. Net weight is 23.2 kg, ambient 0-45 C at 0-90% RH, noise below 50 dBA at 1 m. Certifications listed include NOM, ISO 9001, ISO 14001, CIDET, TUV and UL.
The dimension row reads 190 x 318 x 421 mm and is labelled D x H x W; its consistency with the product orientation should be confirmed. The charge-current row is written in Ah, so it should not be taken as a design input. The efficiency rows name no load point, so no efficiency curve can be drawn.
Key points
- Capacity 2000 VA / 1800 W, 120 VAC input, input window 55-150 VAC +/-3%.
- Output selectable 100/110/115/120/127 VAC; +/-1% regulation, pure sine, crest factor 3:1.
- THD at most 2% (linear) and 4% (non-linear); zero transfer time.
- Efficiency: 90% in AC mode, 97% in eco mode.
- Battery 6 x 12 V/7 Ah; charge voltage 82.1 VDC; typical 3 h to 95%.
- Backup: 6 min at full charge, 15 min at half charge.
- Net weight 23.2 kg; 0-45 C, 0-90% RH, below 50 dBA.
- Communication: smart RS232 or USB, optional SNMP.
Using it in design
- For small critical loads (network, telecom) compare the 1800 W real-power limit with the load list; the VA figure can mislead.
- Weigh the 6 and 15 minute backup times against generator start time and controlled-shutdown needs.
- When using eco mode (97%), assess the protection level in that mode against load sensitivity.
- Confirm the dimension row with the manufacturer before using it as a firm layout figure.
- Carry the RS232/USB and optional SNMP card into the BMS or DCIM plan.
Who should read it
Electrical engineers selecting small UPSs and telecom or network-room designers.
Document contents
- Capacity
- Input
- Output
- Efficiency
- Batteries
- Physical
- Environment
- Control and certifications
Publication details
- Authors
- Chicago Digital Power
- Publisher
- Chicago Digital Power
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Chicago Digital Power Chicago Digital Power UPO11-2 AX catalogue, technical data p.4. Chicago Digital Power. https://www.cdpenergy.com/Content_Elements/downloads/Catalogs/26-Catalog%20UPO11-2%20AX%20ENG.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.