Clary DT Series operating manual, model selection guide p.16
Clary Corporation
Clary DT series 120 VAC on-line continuous power system (UPS) manual: five models of 800-2000 VA (560-1400 W), 88% typical efficiency, 110% overload for 10 min, 14-25 kg.
On this page
Overview
Clary Corporation's DT series owner's manual (P/N 510-11697, Rev H, 03/2012) covers the DT800, DT1000, DT1250, DT1500 and DT2000 and their rackmount (R) versions. The unit is described as a microprocessor-controlled, power-factor-corrected, true on-line UPS; on utility failure the battery circuit carries the load without interruption, and the input is reconnected once acceptable power returns.
Electrical data: input 120 VAC +10%/-20% (without battery discharge), 45-65 Hz; output 120 VAC +/-3%, 50/60 Hz software-selectable or line-synchronised. Crest factor is up to 4.8:1 at 50% load, 3.2:1 at 75% and 2.4:1 at 100%. THD is 3% typical and 5% maximum; dynamic response is +/-4% for a 100% load step with 0.5 ms recovery; efficiency is 88% typical; MTBF exceeds 100,000 hours.
Overload capability is 110% for 10 minutes and 200% for 0.5 seconds. Battery backup at 100%/50% load is 10.5/22 min for the DT800, 5/17 for the DT1000, 7/21 for the DT1250, 5/17 for the DT1500 and 5/18 for the DT2000; typical recharge to 85% takes 8 hours. Nominal VA/W is 800/560, 1000/700, 1250/875, 1500/1050 and 2000/1400; weights are 14, 14, 19, 19 and 25 kg.
The manual is an older document and is still linked from the current Clary DT product page, but the newer family brochure does not map all of these old models. Rackmount and tower dimensions differ and the DT2000's inch and cm heights conflict, so dimensions are not used in this summary.
Key points
- Five models: 800, 1000, 1250, 1500 and 2000 VA; maximum power 560, 700, 875, 1050, 1400 W.
- Input 120 VAC +10%/-20%, 45-65 Hz; output 120 VAC +/-3%, 50/60 Hz selectable.
- Efficiency 88% typical; THD 3% typical, 5% max; MTBF above 100,000 h.
- Overload: 110% for 10 min, 200% for 0.5 s.
- Backup (100%/50% load): 10.5/22, 5/17, 7/21, 5/17 and 5/18 min.
- Input current 5.7-14.3 A; output current 6.7-16.7 A.
- Weight 14, 14, 19, 19 and 25 kg; operation 0-40 C, up to 10,000 ft altitude.
- RS232 interface and optional SNMP; noise 47-49 dBA at 5 ft.
Using it in design
- For small critical loads (laboratory, network) size against the watt limit; the VA figure is higher than watts (560 W for 800 VA).
- Compare backup times (5-10.5 min at 100% load) with generator start time and shutdown needs.
- Check the 120 VAC input against the regional supply arrangement.
- Because the manual is old, confirm current model and product status with the manufacturer.
- Use a current drawing for dimensions; do not rely on this manual's figures.
Who should read it
Engineers selecting small 120 VAC UPS units or reviewing existing Clary installations.
Document contents
- Introduction
- Technical description
- Packaging
- Physical description
- Summary of indicators and controls
- Installation
- Operation
- Signals and interfacing
- Specifications
- Model selection guide
- Care and maintenance
- Service and repair
- Warranty
Publication details
- Authors
- Clary Corporation
- Publisher
- Clary Corporation
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Clary Corporation Clary DT Series operating manual, model selection guide p.16. Clary Corporation. https://www.clary.com/s/Manual-DT-series.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.