Forza Atlas FDC-210K 10 kVA Double-Conversion UPS, Spanish Datasheet Rev1.4.19 (pp.1-2)

Original title Forza Atlas FDC-210K Spanish datasheet Rev1.4.19, pp.1-2

Forza

The Forza Atlas FDC-210K is a 10000 VA / 10000 W, 220 V full-IGBT double-conversion tower UPS that states above 94% efficiency in AC mode, above 91% on battery and 0 ms transfer time.

On this page

Overview

The document is the Spanish datasheet (Rev1.4.19) for the FDC-210K model of the Forza Atlas series. The series spans 1500 VA to 30000 VA; the FDC-210K is the 10000 VA / 10000 W tower unit with unity output power factor. The topology is stated as full-IGBT double-conversion on-line, and data centres, networks and call centres are named as target uses.

On the input side, nominal voltage is 220 VAC +20%/-30%. The low-line transfer threshold depends on load: 176 VAC at 100-80% load, 140 VAC at 80-60% and 110 VAC at 60-0% (all ±3%); the high-line transfer point is 300 VAC. Input power factor is at least 0.99 at 100% load and input THD is below 4% at 100% load and below 6% at 50%. Output is 208-240 VAC with ±1% regulation in battery mode and output THD of 1% or less on linear and 4% or less on non-linear load.

The battery section lists twenty sealed 12 V 9 Ah batteries, 273 VDC charge voltage, 1 A charge current and a 9-hour recharge to 90% capacity, with a 5-year battery life. AC-mode overload is 10 min at 100-110%, 1 min at 110-130% and 1 s above 130%; in battery mode 30 s, 10 s and 1 s. Parallel N+X redundancy, ECO operation and frequency conversion are listed as options.

As limits, the sheet is model-specific and gives no load-efficiency curve; the above-94% efficiency is a single stated value. Dimensions appear as one unlabelled sequence (592x250x576 mm) and weight is 81 kg. Values from another datasheet revision should not be merged with this one.

Key points

  1. Capacity 10000 VA / 10000 W with output power factor 1; full-IGBT double-conversion on-line topology.
  2. Efficiency above 94% in AC mode and above 91% in battery mode; ECO operation is an option.
  3. Input: 220 VAC +20%/-30%, low-line transfer at 176/140/110 VAC depending on load, high-line at 300 VAC; input PF 0.99 or better.
  4. Output THD 1% or less on linear and 4% or less on non-linear load; crest factor up to 3:1.
  5. Transfer time is 0 ms for both line-to-battery and inverter-to-bypass.
  6. AC-mode overload: 10 min at 100-110%, 1 min at 110-130%, 1 s above 130%.
  7. Battery: 12 V 9 Ah x 20, 273 VDC, 1 A charge, 90% in 9 h; warranty 2 years including batteries.
  8. Operating temperature 0-40 °C up to 2000 m; above that, 1% power derating per 100 m up to 4000 m. Weight 81 kg.

Using it in design

  • The internal 12 V 9 Ah x 20 batteries give only minutes of autonomy; use external battery banks for data-room runtime.
  • Consider the parallel N+X option to reduce the outage risk of a single 10 kVA module.
  • If the site altitude exceeds 2000 m, include the 1% per 100 m derating in the load calculation.
  • Use the 4-6% input THD and 0.99 input PF figures as inputs for generator compatibility and cable sizing.

Who should read it

Electrical designers selecting small and mid-size room or network-closet UPS units, and engineers writing specifications.

Publication details

Authors
Forza
Publisher
Forza
Year
Year not stated
Document language
Spanish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Forza Forza Atlas FDC-210K Spanish datasheet Rev1.4.19, pp.1-2. Forza. https://ww.forzaups.com/wp-content/uploads/2019/04/FDC-210K-SPA-BNRev1.4.19.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.