Industronic UPS-IND 1300 (80-120 kVA) Three-Phase UPS Datasheet
Original title Industronic UPS-IND 1300 80-120kVA, V052020, p.2
Industronic
Industronic's 2020 datasheet gives input, output and battery data for the 80, 100 and 120 kVA three-phase double-conversion UPS-IND 1300 series, which has an output isolation transformer.
On this page
Overview
The document is a two-page datasheet (V052020) for the UPS-IND 1300 three-phase UPS series from Industronic, a brand of Nortec in Mexico. The series comprises models 1376, 1378 and 13120: 80/72, 100/90 and 120/108 kVA/kW respectively. Output power factor is 0.9. Separate columns cover three voltage groups: 127/220 V, 254/440, 266/460 and 277/480 V, and 220/380 and 230/400 V.
The unit is an online double-conversion design with DSP control and an IGBT inverter, a 6-pulse SCR rectifier with a harmonic filter targeting 2% RMS distortion at the input, and a dry-type isolation transformer at the output. It has two bypasses: an automatic electronic bypass and a manual maintenance bypass. Up to 4 units can run in parallel, n+1, for capacity or redundancy.
The input accepts ±20% voltage at 100% load, ±25% at 75% and ±30% at 50%. Input power factor is 0.90 at no load and above 0.95 at full load. Output regulation is ±1%, frequency 60 Hz ±0.2% (50 Hz optional), and THD does not exceed 1% on linear load or 3% on non-linear load. Overload is 130% for 1 minute and 150% for 10 seconds.
The battery bank is external, nominal 348 Vdc (384 Vdc optional), with 5 minutes of backup at full load. Operating temperature is 0-40 °C and maximum altitude is 2,000 m at 100% power and 3,000 m at 96%. MTBF is 233,000 hours and noise is below 65 dB at 1 m. Cabinet weight ranges from 520 to 1,280 kg depending on voltage group. The document is dated 2020.
Key points
- Models: 1376 (80 kVA/72 kW), 1378 (100/90), 13120 (120/108); output power factor 0.9.
- Topology: online double conversion, 6-pulse SCR rectifier, IGBT inverter, dry-type isolation transformer at the output.
- Input voltage tolerance ±20% at 100% load, ±25% at 75%, ±30% at 50%; input power factor above 0.95 at full load.
- Output regulation ±1%; THD at most 1% on linear load and at most 3% on non-linear load.
- Overload: 130% for 1 min, 150% for 10 s.
- External battery bank 348 Vdc (384 Vdc optional), 5 min backup at full load.
- Paralleling: n+1, up to 4 units; bypass: automatic electronic and manual maintenance bypass.
- MTBF 233,000 hours; noise below 65 dB at 1 m; full power up to 2,000 m altitude.
- Cabinet weight 520-1,280 kg depending on voltage group.
Using it in design
- Confirm the input voltage group (127/220, 254/440 or 220/380 V class) before ordering; cabinet size and weight vary by group.
- Calculate floor loading separately for cabinets up to 1,280 kg and for the external battery bank.
- Include the effect of the output isolation transformer (separate earth reference, neutral creation) in the earthing and selectivity study.
- Compare the 5-minute backup with generator start-up time and shutdown procedure.
- Account for the input current harmonics of a 6-pulse SCR rectifier when sizing the generator.
Who should read it
Electrical engineers specifying mid-range three-phase UPS, and designers comparing products in the Latin American market.
Document contents
- Features and applications
- Power-quality issues solved
- UPS-IND 1300 specifications: input, output, battery bank
- Physical and mechanical data
- Technology (rectifier, inverter, filter, isolation transformer, bypass, paralleling)
Publication details
- Authors
- Industronic
- Publisher
- Industronic
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Industronic Industronic UPS-IND 1300 80-120kVA, V052020, p.2. Industronic. https://grupoindustronic.com/wp-content/uploads/2020/04/17-Datasheet-UPS-1300-80-120.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.