Industronic UPS-IND 1300 (80-120 kVA) Three-Phase UPS Datasheet

Original title Industronic UPS-IND 1300 80-120kVA, V052020, p.2

Industronic

Industronic's 2020 datasheet gives input, output and battery data for the 80, 100 and 120 kVA three-phase double-conversion UPS-IND 1300 series, which has an output isolation transformer.

On this page

Overview

The document is a two-page datasheet (V052020) for the UPS-IND 1300 three-phase UPS series from Industronic, a brand of Nortec in Mexico. The series comprises models 1376, 1378 and 13120: 80/72, 100/90 and 120/108 kVA/kW respectively. Output power factor is 0.9. Separate columns cover three voltage groups: 127/220 V, 254/440, 266/460 and 277/480 V, and 220/380 and 230/400 V.

The unit is an online double-conversion design with DSP control and an IGBT inverter, a 6-pulse SCR rectifier with a harmonic filter targeting 2% RMS distortion at the input, and a dry-type isolation transformer at the output. It has two bypasses: an automatic electronic bypass and a manual maintenance bypass. Up to 4 units can run in parallel, n+1, for capacity or redundancy.

The input accepts ±20% voltage at 100% load, ±25% at 75% and ±30% at 50%. Input power factor is 0.90 at no load and above 0.95 at full load. Output regulation is ±1%, frequency 60 Hz ±0.2% (50 Hz optional), and THD does not exceed 1% on linear load or 3% on non-linear load. Overload is 130% for 1 minute and 150% for 10 seconds.

The battery bank is external, nominal 348 Vdc (384 Vdc optional), with 5 minutes of backup at full load. Operating temperature is 0-40 °C and maximum altitude is 2,000 m at 100% power and 3,000 m at 96%. MTBF is 233,000 hours and noise is below 65 dB at 1 m. Cabinet weight ranges from 520 to 1,280 kg depending on voltage group. The document is dated 2020.

Key points

  1. Models: 1376 (80 kVA/72 kW), 1378 (100/90), 13120 (120/108); output power factor 0.9.
  2. Topology: online double conversion, 6-pulse SCR rectifier, IGBT inverter, dry-type isolation transformer at the output.
  3. Input voltage tolerance ±20% at 100% load, ±25% at 75%, ±30% at 50%; input power factor above 0.95 at full load.
  4. Output regulation ±1%; THD at most 1% on linear load and at most 3% on non-linear load.
  5. Overload: 130% for 1 min, 150% for 10 s.
  6. External battery bank 348 Vdc (384 Vdc optional), 5 min backup at full load.
  7. Paralleling: n+1, up to 4 units; bypass: automatic electronic and manual maintenance bypass.
  8. MTBF 233,000 hours; noise below 65 dB at 1 m; full power up to 2,000 m altitude.
  9. Cabinet weight 520-1,280 kg depending on voltage group.

Using it in design

  • Confirm the input voltage group (127/220, 254/440 or 220/380 V class) before ordering; cabinet size and weight vary by group.
  • Calculate floor loading separately for cabinets up to 1,280 kg and for the external battery bank.
  • Include the effect of the output isolation transformer (separate earth reference, neutral creation) in the earthing and selectivity study.
  • Compare the 5-minute backup with generator start-up time and shutdown procedure.
  • Account for the input current harmonics of a 6-pulse SCR rectifier when sizing the generator.

Who should read it

Electrical engineers specifying mid-range three-phase UPS, and designers comparing products in the Latin American market.

Document contents

  1. Features and applications
  2. Power-quality issues solved
  3. UPS-IND 1300 specifications: input, output, battery bank
  4. Physical and mechanical data
  5. Technology (rectifier, inverter, filter, isolation transformer, bypass, paralleling)

Publication details

Authors
Industronic
Publisher
Industronic
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Industronic Industronic UPS-IND 1300 80-120kVA, V052020, p.2. Industronic. https://grupoindustronic.com/wp-content/uploads/2020/04/17-Datasheet-UPS-1300-80-120.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.