KEMAPOWER XG6-10K(S)-TX(B) 6-10 kVA High-Frequency Single-Phase Online UPS Technical Specification Table
Original title KEMAPOWER XG6-10K(S)-TX(B) official technical specification table
KEMAPOWER
KEMAPOWER's official table defines the 6 and 10 kVA high-frequency single-phase online UPS models of the transformer-equipped XG-TX series, with a 192 VDC battery and 0 ms transfer.
On this page
Overview
The page presents the 6-10 kVA XG-TX series high-frequency single-phase online UPS from the Chinese manufacturer KEMAPOWER. The unit contains a built-in transformer, which the manufacturer presents as suited to the American market. Input is 220 V and output can be 110 V or 220 V. DSP digital control, zero transfer time and a wide input voltage and frequency range (40-60 Hz) stand out.
Four models are defined: XG6K-TXB (6 kVA/5.4 kW) and XG10K-TXB (10 kVA/9 kW) as the standard type with internal battery and transformer; XG6KS-TX (6 kVA/4.8 kW) and XG10KS-TX (10 kVA/8 kW) as the long-backup type with external battery and transformer. Output power factor is adjustable to 0.8 or 0.9. Input power factor is above 0.99 at 220 VAC full resistive load, and generator input is supported (generator rating at least twice the UPS rating).
Output voltage is set by software to 200/208/220/230/240 VAC; a 10% derating applies at 208 and 200 VAC and must be confirmed before ordering. Transfer time is 0 ms between line and battery mode and 4 ms between line and bypass. Output THD is below 2% on full resistive load and below 6% on full RCD load; crest factor is at most 3:1. Overload is 1 minute at 105-125%, 30 seconds at 125-135% and 100 ms above 135%.
The battery is 192 VDC VRLA: 16×7 Ah internal on the standard type and 16×9 Ah external on the long-backup type. Charge current is normally 1 A and at most 5-7 A; charging to 90% takes 7 hours. Operation is 0-40 °C and 0-95% non-condensing humidity. Product size and weight are 540×260×720 mm and 85 kg for the XG6K-TXB, 260×533×560 mm and 53 kg for the XG6KS-TX, 540×260×720 mm and 93 kg for the XG10K-TXB, and 260×533×560 mm and 55 kg for the XG10KS-TX; dimensions are given in the order published in the document.
Key points
- Models: XG6K-TXB (6 kVA/5.4 kW), XG6KS-TX (6 kVA/4.8 kW), XG10K-TXB (10 kVA/9 kW), XG10KS-TX (10 kVA/8 kW).
- TXB: internal battery and transformer; KS-TX: external battery and transformer (long backup).
- Input 220 VAC (or L1 110 + L2 110); turn-on range (120±5)-(274±5) VAC; frequency 40-60 Hz.
- Input power factor above 0.99; generator input supported, generator at least twice the UPS rating.
- Output 200/208/220/230/240 VAC; 10% power derating at 208 and 200 VAC.
- Transfer 0 ms (line-battery), 4 ms (line-bypass); THD at most 2% (R load), 6% (RCD load).
- Overload: 1 min at 105-125%, 30 s at 125-135%, 100 ms above 135%.
- Battery 192 VDC VRLA; 16×7 Ah internal or 16×9 Ah external; 90% charge in 7 hours.
- Operation 0-40 °C; product weight 53-93 kg.
Using it in design
- Confirm output voltage selection and the 10% derating at 208/200 VAC against load voltage and power requirement before ordering.
- On generator-fed systems, size the generator at least twice the UPS rating.
- Base usable power on the kW value (4.8-9 kW) rather than kVA.
- If long backup is required, plan the external-battery KS-TX type and a 192 VDC battery cabinet.
- Take product weight and size, separate from carton size and gross weight, into installation-space calculations.
Who should read it
Engineers selecting single-phase UPS for small and mid-size IT loads, and designers who need transformer-equipped UPS with 110/220 V output.
Document contents
- Key features
- Technical specification table: capacity, input, output, battery, display, environment, physical
- Wire connection: input 110 V or 220 V, output 220 V; and input 220 V, output 110 V or 220 V
- Downloadable datasheets
Publication details
- Authors
- KEMAPOWER
- Publisher
- KEMAPOWER
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
KEMAPOWER KEMAPOWER XG6-10K(S)-TX(B) official technical specification table. KEMAPOWER. https://www.kemapower.com/sys-pd/84.html
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.