Magellan Power MEA900RT G4 6-10kVA Rack/Tower Online UPS Brochure (2022)
Original title Magellan MEA900RT G4 6-10kVA, 2022 brochure, p.2
Magellan Power
Magellan MEA900RT G4 is a 6 and 10 kVA/kW online UPS with unity output power factor; efficiency is 94 to 94.5%, up to 98% in ECO mode, transfer time is 0 ms and up to 4 units parallel.
On this page
Overview
The Magellan Power MEA900RT G4 is an online UPS series using advanced DSP and three-level technology, with 6 kVA / 6 kW (MEA906RT) and 10 kVA / 10 kW (MEA9010RT) models. Output power factor is 1.0 and, with active power factor correction, input power factor is 0.99 or higher. Input voltage range is 110 to 288 Vac and frequency range 40 to 70 Hz; below 176 Vac, load is derated linearly between 50% and 100%.
Efficiency is at least 94% at 100% load, up to 94.5% at 60% load and at least 98% in ECO mode. THDv is below 1% on linear load and below 4% on non-linear load. Overload is 10 minutes at 102 to 110%, 1 minute at 110 to 125% and 30 seconds at 125 to 150%. Up to 4 units can be paralleled. 50/60 Hz auto-sensing and 50 Hz in/60 Hz out frequency conversion are supported.
On the battery side, DC voltage is 192 Vdc (192 to 240 Vdc settable) with 16 batteries (16 to 20 settable), hot-swappable batteries, a digitally controlled charger and intelligent battery management that the manufacturer says extends battery life by 50%. Charging current is 1 A on the standard model and 5 A by default on the long-time model (1 to 5 A settable, 12 A optional). On the standard model, 90% capacity is restored in 8 hours. The document is a two-page brochure.
Key points
- Models: MEA906RT 6 kVA / 6 kW and MEA9010RT 10 kVA / 10 kW; output power factor 1.
- Input 110 to 288 Vac, 40 to 70 Hz, power factor ≥0.99, THDi ≤5%.
- Efficiency: ≥94% at 100% load, up to 94.5% at 60% load, ≥98% in ECO mode.
- Transfer time 0 ms; up to 4 units in parallel.
- Overload: 10 min at 102 to 110%, 1 min at 110 to 125%, 30 s at 125 to 150%.
- DC voltage 192 Vdc (192 to 240 settable), 16 batteries (16 to 20 settable); charging current up to 12 A.
- Operation 0 to 40 °C, altitude below 1000 m with 1% derating per additional 100 m; IP20.
- Noise 55 dB (6 kVA) and 58 dB (10 kVA) at 1 m; weight 12 to 14 kg long-time model, 58 to 63 kg standard model.
Using it in design
- With a power factor of 1.0, select the 6 and 10 kVA models directly for 6 and 10 kW loads.
- At sites with input voltage below 176 Vac, include the linear load derating in capacity calculations.
- On the long-time (H) model, match external battery capacity to the 5 A (12 A optional) charging current.
- For redundancy, put a parallel set of up to 4 units and the parallel port into the specification.
- Apply the 1% per 100 m derating at sites above 1000 m.
Who should read it
Engineers comparing 6 to 10 kVA online UPS units for server rooms and small data centres.
Document contents
- Features
- Options
- Specification: input, output, batteries, system, others
Publication details
- Authors
- Magellan Power
- Publisher
- Magellan Power
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Magellan Power Magellan MEA900RT G4 6-10kVA, 2022 brochure, p.2. Magellan Power. https://magellanpower.com.au/wp-content/uploads/2022/09/MEA900RT-G4-6-10kVA-2022.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.