Technical guideFree to readYear not stated

MAKPOWER EXODUS M Series 6-30 kVA Transformer-Based Online UPS Technical Specifications

Original title MAKPOWER EXODUS M 6-30kVA official technical specifications

MAKPOWER

MAKPOWER EXODUS M, 6 to 30 kVA with three-phase input and single-phase output, is a true online UPS with an output isolation transformer; output power factor is 0.7 and full-load efficiency 86 to 90%.

On this page

Overview

The MAKPOWER EXODUS series are true online double-conversion UPS systems built with PWM and IGBT technology and microprocessor-controlled pure sine wave output. The M series has three-phase input and single-phase output, with an isolation transformer at the output. There are six models: EX 206, 207, 210, 215, 220 and 230, rated 6, 7.5, 10, 15, 20 and 30 kVA with 4.2 to 21 kW active power (power factor 0.7).

Input is 230/400 Vac three-phase four-wire plus earth, bypass voltage 230 VAC ±10% and frequency 50 or 60 Hz. Output is 230 Vac at 50 or 60 Hz; efficiency is 86 to 90% at full load and crest factor is 3:1. Overload is 10 minutes at 100 to 125%, 1 minute at 125 to 150% and transfer to bypass above 150%. A built-in static bypass, maintenance bypass switch, adjustable power walk-in delay and a remote emergency power off input (REPO) are provided.

On the battery side, maintenance-free sealed lead-acid units number 20 or 30, with float/discharge voltage of 270/200 VDC or 405/300 VDC; the battery cabinet is internal and an optional automatic battery test runs every 72 hours. The alarm history stores 128 events or 4000 alarms. An RS232 interface, 3 dry-contact outputs and optional SNMP, MODBUS and RS485 adaptors are available. Weight without batteries is 106 to 230 kg. The source is the product page's feature list and technical table.

Key points

  1. Models EX 206, 207, 210, 215, 220, 230: 6, 7.5, 10, 15, 20, 30 kVA; 4.2 to 21 kW; output power factor 0.7.
  2. Input 230/400 Vac 3-phase 4-wire + earth; bypass 230 VAC ±10%; 50 or 60 Hz.
  3. Isolation transformer at the output; 230 Vac single-phase output; crest factor 3:1.
  4. Efficiency 86 to 90% at full load.
  5. Overload: 10 min at 100 to 125%, 1 min at 125 to 150%, bypass above 150%.
  6. Battery: 20 or 30 sealed lead-acid units; float/discharge 270/200 VDC or 405/300 VDC; automatic test every 72 h.
  7. Alarm log of 128 events (4000 alarms); 3 microprocessors (main control, rectifier, parallel).
  8. Operation 0 to 40 °C, humidity 0 to 90%, IP20; weight without batteries 106 to 230 kg.

Using it in design

  • With an output power factor of 0.7, select by kW rather than kVA: the 30 kVA model carries 21 kW.
  • The output isolation transformer gives galvanic separation and short-circuit limiting; include its losses in efficiency calculations.
  • With three-phase input and single-phase output, check phase currents and neutral loading in the distribution design.
  • Match the battery string to the model: 270/200 VDC (20 units) or 405/300 VDC (30 units).
  • Consider the 18-pulse rectifier option when an input harmonic target applies.

Who should read it

Electrical engineers looking for industrial, transformer-based UPS units to feed single-phase critical loads.

Document contents

  1. Features
  2. Technical specifications: input, output, battery, general
  3. Options

Publication details

Authors
MAKPOWER
Publisher
MAKPOWER
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

MAKPOWER MAKPOWER EXODUS M 6-30kVA official technical specifications. MAKPOWER. https://makpower.com/product/exodus-m-series-3-phase-input-1-phase-output-6-30-kva/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.