Ragtech DUE brochure Rev.ABR/22, p.3
Ragtech
Ragtech's DUE brochure lists a 6000 VA and 10000 VA single and split-phase online double-conversion UPS series: THDi 4%, input power factor 0.99, 94.6% line-mode efficiency, up to 4 units in parallel.
On this page
Overview
The brochure presents Ragtech's DUE series, from the Brazilian manufacturer, as a high-frequency online double-conversion UPS (nobreak) with pure sine output for corporate, industrial and telecom environments. It comes in 6000 VA/6000 W and 10000 VA/10000 W, with product codes 4500 to 4512. The document is the April 2022 revision.
On the input, active power factor correction (PFC) gives an input power factor of 0.99 and current distortion (THDi) of 4% at full load, which the document cites as the basis for generator compatibility. Input voltage is 110/127 V (M1 models, 102-152 V window) or 220/240 V (M2 models, 176-264 V window) and the frequency range is 40-70 Hz. Configuration is single-phase or split-phase (FFT or FNT).
On the output, voltage variation is ±1%, frequency ±0.1%, THDv is below 1% on resistive load and below 5% on nonlinear load, and crest factor is 3:1. The inverter tolerates 105-110% overload for 10 min, 111-125% for 1 min and 126-150% for 30 s before transferring to bypass; bypass carries up to 125% without shutdown. Mains-to-battery transfer time is zero. M2-ISO models have galvanic isolation and M2-AT models an autotransformer.
Batteries are internal: 16 or 32 units of 12 V 7 Ah in the 6000 VA models and 16 or 32 units of 12 V 9 Ah in the 10000 VA models; XT models are the 32-battery extended-autonomy versions. Charge current is up to 2 A and recharge to 90% takes 8 hours. The unit measures 665 x 250 x 590 mm (H x W x D), weighs 70-133 kg net and produces 58 dB at 1 m. The document is product literature with manufacturer values only.
Key points
- Ratings: 6000 VA/6000 W and 10000 VA/10000 W; pure sine, online double conversion, DSP control.
- Input power factor 0.99 (100% load), THDi 4%, input frequency 40-70 Hz.
- Input voltage: M1 models 110/127 V (102-152 V), M2 models 220/240 V (176-264 V).
- Output: ±1% voltage, ±0.1% frequency, THDv below 1% (resistive) and 5% (nonlinear), crest factor 3:1.
- Line-mode efficiency: 94.6% at 100% load and 95% at 60% load (batteries fully charged).
- Inverter overload: 105-110% 10 min, 111-125% 1 min, 126-150% 30 s; bypass 125% continuous, 126-130% 5 min, 131-150% 1 min, above 150% 200 ms.
- Mains-to-battery transfer time zero; recharge to 90% in 8 hours, charge current up to 2 A.
- Internal batteries: 16 or 32 units of 12 V 7 Ah (6000 VA) or 9 Ah (10000 VA); up to 4 units in parallel (Parallel Kit on request).
- Size 665 x 250 x 590 mm; net weight 70-133 kg; noise 58 dB at 1 m; SNMP card optional.
Using it in design
- For small technical rooms or edge loads, match the 6-10 kVA single-phase choice to the input series (M1 or M2) and output voltage (127, 220, 110/220 V); pick ISO where isolation is needed and AT for voltage adaptation.
- Behind a generator, use the input PF of 0.99 and THDi of 4% as inputs to generator sizing, and compare the 176-264 V input window with generator regulation.
- Meet the autonomy target with the 16 or 32 internal battery options; with large external battery additions, check the 8-hour recharge time against the 2 A charge limit.
- Use the overload and bypass ratings (inverter 30 s up to 150%, bypass 125% continuous) as inputs to upstream protection selectivity and inrush checks.
- State the 4-unit parallel limit and the separate Parallel Kit requirement in capacity and redundancy calculations.
Who should read it
Electrical designers and purchasing engineers selecting single-phase UPS for small data rooms, telecom and industrial control loads.
Document contents
- General introduction and highlights
- Features (display, SNMP, cold start, 20 A outlets)
- Front and rear panel
- Technical specification table
- Product codes and model table
- Options
Publication details
- Authors
- Ragtech
- Publisher
- Ragtech
- Year
- Year not stated
- Document language
- Portuguese
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Ragtech Ragtech DUE brochure Rev.ABR/22, p.3. Ragtech. https://ragtech.com.br/laminas/lamina-due.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.