Su-Kam IntelliQ online UPS leaflet: 1-phase/1-phase, 3-phase/1-phase and 3-phase/3-phase series

Original title Su-Kam Online UPS original leaflet, IntelliQ 1P/1P technical table p.7

Su-Kam

Su-Kam IntelliQ is a series of galvanically isolated, DSP-based double-conversion online UPS: 1-10 kVA single-phase, 7.5-25 kVA 3-phase/1-phase and 5-50 kVA 3-phase/3-phase models; output power factor 0.8.

On this page

Overview

A historical leaflet from India-based Su-Kam Power Systems explains what an online UPS is and why it suits critical loads, then gives the IntelliQ series technical tables. In an online UPS the load is always fed through the UPS; mains AC is converted to DC and back to AC (double conversion), which removes fluctuations and disturbances in the mains. When the mains fail the switchover time is zero, which the leaflet illustrates with hospital equipment, ATMs, satellite, air traffic control and bank transactions. A bypass switch is introduced for maintenance.

Su-Kam offers two online families: IntelliQ (low frequency) and Sinclair-I (high frequency). IntelliQ comes in three phase configurations: 1-phase in/1-phase out (IQ111K-IQ1110K: 1, 2, 3, 5, 7.5 and 10 kVA; 700, 1600, 2400, 4000, 6000 and 8000 W), 3-phase in/1-phase out (7.5-25 kVA; 6-20 kW) and 3-phase in/3-phase out (5-50 kVA; 4-40 kW). All use DSP-based IGBT PWM, double-conversion VFI technology and true galvanic isolation, with an output power factor of 0.8 lagging.

Technical values: single-phase models have input 170-280 V, 47-53 Hz, output 230 V +/-1%, 50 Hz +/-0.1%, THD up to 3%, loading capacity 110% for 2 min and overload up to 300% for 1 s. Three-phase models have input 310-480 V, 45-55 Hz; 3-phase/1-phase models give 110% for 5 min, 125% for 1 min and 150% for 10 s; 3-phase/3-phase models give 110% for 8 min, 125% for 1 min and 150% for 13 s; bypass is 125% continuous. Battery is 48, 180 or 192 V DC in single-phase models and 360 V DC (30 x 12 V) in three-phase models, charging current 1-10 A and recommended batteries 7.2-200 Ah.

General data: efficiency above 85% in single-phase models and above 90% in 3-phase/3-phase models; operating temperature 0-45 °C, noise below 45 dB at 1 m, IP20 and forced-air cooling. An LCD panel shows input/output voltage, frequency, power and current; there is an RS-232 interface and Windows-based monitoring software, and Su-Kam's Power Doc software offers remote monitoring. Options include a static bypass and hot standby. The leaflet is a historical publication and lists monitoring software for Windows 95/98/NT/2000/XP.

Key points

  1. IntelliQ 1-phase/1-phase: 1, 2, 3, 5, 7.5, 10 kVA; 700, 1600, 2400, 4000, 6000, 8000 W; weight 32-108 kg (without batteries).
  2. IntelliQ 3-phase/1-phase: 7.5-25 kVA (6-20 kW); IntelliQ 3-phase/3-phase: 5-50 kVA (4-40 kW).
  3. Output power factor 0.8 lagging; DSP/IGBT PWM, double-conversion VFI, true galvanic isolation.
  4. Input: 1-phase 170-280 V, 3-phase 310-480 V; output 230 V +/-1% (1-phase), 400 V +/-2% (3-phase).
  5. 3-phase/3-phase overload: 110% for 8 min, 125% for 1 min, 150% for 13 s; bypass 125% continuous.
  6. Battery: 48/180/192 V DC (1-phase) and 360 V DC (3-phase, 30 x 12 V); charging current 1-10 A.
  7. Efficiency above 85% (1-phase) and above 90% (3-phase/3-phase); 0-45 °C; IP20; noise below 45 dB.
  8. Zero switchover time; maintenance bypass available; RS-232 and Power Doc monitoring.

Using it in design

  • With output power factor 0.8, compare loads in kW (for example the 1 kVA model gives only 700 W); modern PF 0.9-1 loads may exceed capacity.
  • Consider IntelliQ where true galvanic isolation is required; add the weight (32-108 kg without batteries) and dimensions to the floor loading.
  • With efficiency above 85-90%, calculate annual energy loss and cooling load, and compare with modern high-frequency UPS.
  • Match the battery count (15, 16 or 30 x 12 V) and DC voltage (180, 192, 360 V) to the battery room and charging current limit.
  • Because the document is historical, verify the current model and dealer support before purchase.

Who should read it

Electrical engineers and facility operators evaluating older galvanically isolated online UPS systems in India and similar markets.

Document contents

  1. What is an Online UPS
  2. How an Online UPS protects the load
  3. How to choose a Su-Kam UPS
  4. IntelliQ 1 phase input - 1 phase output specifications
  5. IntelliQ 3 phase input - 1 phase output specifications
  6. IntelliQ 3 phase input - 3 phase output specifications

Publication details

Authors
Su-Kam
Publisher
Su-Kam
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Su-Kam Su-Kam Online UPS original leaflet, IntelliQ 1P/1P technical table p.7. Su-Kam. https://www.neelammicro.com/pdf/Su-kamonlineUPSLeaflet.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.