Techser TECHGLARE online UPS catalogue

Original title Techser TECHGLARE catalogue revision 01, 23 September 2015, p.2

Techser

Techser's TECHGLARE series is a single-phase 230 V online UPS family; the catalogue gives AC-AC efficiency of 95% or more, pure sine output, THD under 3% (linear load) and 125% overload for 10 minutes.

On this page

Overview

The Techser Power Solutions catalogue (India, active since 1988) collects the technical specifications of the TECHGLARE online UPS series on two pages. The series is single-phase, 230 V AC plus neutral plus earth at input and output. One table covers several model columns, but power ratings in kW are not published. The document is revision 01 dated 2015 and is still hosted on the manufacturer's site.

On the input side it gives a 40-70 Hz frequency range, low/high transfer thresholds below 160 VAC and above 290 VAC, and an adjustable UPS range of 160-290 VAC. Output is 230 V (+5% / -15% setting), voltage regulation of ±1%, free-running frequency of 50 Hz ±3%, crest factor 3:1 and a pure sine wave. THD is under 3% on a linear load and under 4% on a non-linear load.

AC-AC efficiency is stated as 95% or more; no load point is given, so no efficiency curve can be drawn. Output power factor is 0.8 lagging. Overload is 125% for 10 minutes and 150% for 1 minute. A standard static bypass gives uninterrupted transfer between mains and battery. Battery strings are 36 V or 72-240 V DC depending on the model column, with a float-boost charger.

Environment and interfaces are 0-45 °C operating, 0-95% RH non-condensing, noise 55 dBA at 1 m or 65 dBA, IP 20, an RS 232 interface and optional SNMP/web software. Parallel N+1 redundant and hot-standby configurations are optional.

Key points

  1. Single-phase 230 V online (double-conversion) UPS series; Techser active since 1988.
  2. Input frequency range 40-70 Hz; low/high voltage transfer below 160 VAC and above 290 VAC; UPS adjustable range 160-290 VAC.
  3. Output: 230 V, regulation ±1%, crest factor 3:1, pure sine, THD under 3% (linear) and under 4% (non-linear).
  4. AC-AC efficiency 95% or more, no load point stated; output power factor 0.8 lagging.
  5. Overload: 125% for 10 minutes and 150% for 1 minute; standard static bypass.
  6. Operating environment 0-45 °C, 0-95% RH, IP 20, noise 55 / 65 dBA.
  7. RS 232 interface, optional SNMP; parallel N+1 and hot-standby options.

Using it in design

  • Consider it only for single-phase, small critical loads such as network and control boards; since kW is not published, do not derive capacity from kVA and 0.8 power factor yourself, have the manufacturer confirm it.
  • Before using the efficiency as a design input, ask the manufacturer for load points (for example 50% and 100%); the catalogue gives a single 95%-or-more figure.
  • The wide input window (160-290 VAC) reduces battery transfers on poor mains, but ask separately about generator compatibility.
  • The IP 20 rating and 0-45 °C limit require the unit to sit in an air-conditioned electrical room.

Who should read it

Electrical designers and buyers selecting small single-phase UPS units.

Document contents

  1. TECHGLARE series technical specifications
  2. Input, output and efficiency
  3. Battery and charger
  4. Protection, indicators and interfaces

Publication details

Authors
Techser
Publisher
Techser
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Techser Techser TECHGLARE catalogue revision 01, 23 September 2015, p.2. Techser. https://techser.com/wp-content/uploads/2024/06/Techglare-catalogue-Updated-Rao.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.