UTL Online UPS catalogue Rev-09: Deep Impact and Alfa PFC
Original title UTL Online UPS catalogue Rev09, Deep Impact specification p.5
UTL
The UTL (India) online UPS catalogue covers four series from 1 to 120 kVA; Deep Impact has a 110-300 V input window at 1-3 kVA and 120-276 Vac with input current harmonics below 3% at 6-10 kVA.
On this page
Overview
UTL is an Indian backup power manufacturer founded in 1996. The catalogue (Rev-09) states 4 manufacturing units, more than 60 R&D staff and capacity made up to 120 kVA. The document is a product brochure; no publication date is stated and some per-product specification tables are presented partly as images. The figures below are those clearly legible in the catalogue.
The Deep Impact series is a high-frequency, double-conversion online UPS. The 1-3 kVA models offer digital microprocessor control, a wide 110-300 V input range, input power factor correction, start-up without battery, cold start, ECO mode and generator compatibility; USB/RS232 is standard and SNMP optional. The 6-10 kVA models offer N+X parallel redundancy, DSP control, input current harmonics below 3%, a 120-276 Vac input window, ECO mode and a choice of 16/18/20 batteries. Operating conditions are 0-40 °C, 0-95% humidity and altitude below 1500 m, with derating above.
Alfa PFC (1 phase in, 1 phase out, 1-10 kVA) is described as a 'half electricity consuming' UPS; with unity power factor and active power factor correction, it claims savings of more than 4 kWh per hour compared with an SCR-based UPS. AC-AC efficiency is given as above 85% at full load. The Mars series is isolation-transformer based, in 3 phase in - 1 phase out (5-20 kVA) and 3 phase in - 3 phase out (5-15 kVA) versions; input is 400 V ±20% three-phase four-wire, the switching device is IGBT, and peak efficiency ranges from above 85% to above 90%.
The larger three-phase series are Star PFC (20-120 kVA) and Lift UPS (6-20 kVA). The catalogue mostly gives efficiencies as lower bounds ('above'); with no load point stated, no curve can be derived.
Key points
- UTL founded 1996; 4 manufacturing units, more than 60 R&D staff, capacity made up to 120 kVA.
- Deep Impact 1-3 kVA: high-frequency double conversion; input 110-300 V; ECO mode; generator compatible.
- Deep Impact 6-10 kVA: N+X parallel; input 120-276 Vac; input current harmonics below 3%; 16/18/20 battery option.
- Deep Impact operating environment 0-40 °C, 0-95% humidity, altitude below 1500 m; storage -25 to 55 °C.
- Alfa PFC 1-10 kVA (1 phase in, 1 phase out): AC-AC efficiency above 85% at full load; unity power factor.
- Mars isolation-transformer based: 3 phase input 400 V ±20%; 5-20 kVA (3-1 phase) and 5-15 kVA (3-3 phase); IGBT.
- Star PFC 20-120 kVA and Lift UPS 6-20 kVA three-phase series.
Using it in design
- For single-phase and small three-phase critical loads, use the wide input window (110-300 V or 120-276 Vac) as a criterion for fewer battery transfers on poor mains.
- Efficiency values are lower bounds ('above 85%'); ask the manufacturer for a load-point efficiency curve for energy cost calculations.
- For 6-10 kVA, consider the N+X parallel redundancy option in the architecture.
- At sites above 1500 m ask the manufacturer for derating data.
- Since the catalogue states no publication date, confirm current product status.
Who should read it
Designers and buyers looking for small and mid-range UPS units.
Document contents
- About UTL
- Deep Impact 1-3 kVA
- Deep Impact 6-10 kVA
- Alfa PFC online UPS
- Mars online UPS (3 phase in - 1 phase out)
- Mars online UPS (3 phase in - 3 phase out)
- Star PFC UPS
- Lift UPS
Publication details
- Authors
- UTL
- Publisher
- UTL
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only. The reviewed PDF cover says Rev-09; URL filename Rev-05 and internal PDF metadata Rev-08 are not the visible revision. Publication year remains unknown.
Citation
UTL UTL Online UPS catalogue Rev09, Deep Impact specification p.5. UTL. https://www.upsinverter.com/utl/wp-content/uploads/2019/07/New-Online-Book-Rev-05.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.