COVER (COMEX) PS 10-40K 3U rack double-conversion UPS: 10, 20, 30, 40 kVA (kW), VFI-SS-111, input THDi below 3%, output PF 1.0, 96% on-line and 98% eco-mode efficiency.

On this page

Overview

The COVER brand is owned by COMEX S.A. (they are not two manufacturers). The PS series is a true online double-conversion UPS in 10, 20, 30 and 40 kVA, coded VFI-SS-111 under EN 62040-3. Phase configurations can be 1:1, 3:1, 3:3 and 1:3, enabled by a universal rectifier and inverter design. Ratings are 10 kVA/10 kW, 20 kVA/20 kW, 30 kVA/30 kW and 40 kVA/40 kW.

The input has an IGBT rectifier: voltage 220/230/240 V (L-N) or 380/400/415 V (L-L), a wide input window (L-N 100-160 VAC linearly at 50-100% load, 160-300 VAC at 100% load), 45-65 Hz frequency range, THDi below 3% and power factor 0.99 or higher. Separate feeds for rectifier and bypass (split bypass) raise reliability and allow cascaded systems. Up to 3 UPSs can run in N+1 parallel.

Output power factor is 1.0; static regulation +/-1%, dynamic +/-3%, frequency 50/60 +/-0.1 Hz, crest factor 3:1. Overload tolerance is 105% continuous, 125% for 10 min, 150% for 30 s and above 150% for 500 ms. Efficiency is 96% in on-line mode and 98% in eco mode. The battery string has 32-40 12 V blocks, charge current 1-13 A and charge time 3-8 hours to 90% capacity (configurable).

Physical data: the UPS module is 440 x 680 x 132 mm (3U, 10 and 20 kVA) and 440 x 750 x 132 mm (3U, 30 and 40 kVA); weights are 25, 32, 36 and 38 kg. These values cover the UPS electronics only, excluding battery modules: a battery module is 440 x 780 x 132 mm (3U, 20 batteries) at 65 kg, each UPS needs at least 2 battery modules, and together they take 6U. Noise is below 65 dB, operating temperature 0-40 C (recommended 15-25 C).

Key points

  1. Power: 10, 20, 30 and 40 kVA; output power factor 1.0 (kVA = kW).
  2. Class VFI-SS-111 (EN 62040-3); configurations 1:1, 3:1, 3:3, 1:3 (30 and 40 kVA only 3:3).
  3. Input: THDi below 3%, power factor 0.99 or higher, 45-65 Hz.
  4. Efficiency: 96% in on-line mode, 98% in eco mode.
  5. Overload: 125% for 10 min, 150% for 30 s, above 150% for 500 ms.
  6. Battery: 32-40 12 V blocks per string; charge current 1-13 A; 3-8 h to 90%.
  7. Size/weight (UPS only): 440 x 680 x 132 mm, 25-32 kg; 440 x 750 x 132 mm, 36-38 kg.
  8. Battery module: 440 x 780 x 132 mm, 65 kg, minimum 2 modules, 6U; up to 3 units in N+1 parallel.

Using it in design

  • Calculate rack space for the UPS module and battery modules separately: one UPS needs at least 6U of battery plus 3U for the UPS.
  • With output PF 1.0, compare the critical load directly in kW.
  • Match split bypass and N+1 parallel (up to 3 units) to the redundancy target.
  • If eco mode (98%) is used, assess the protection level in that mode against load sensitivity.
  • Carry the recommended 15-25 C into cold-aisle design for battery life.

Who should read it

Data-centre and server-room electrical designers selecting rack UPSs.

Document contents

  1. Technology, class, power range and configurations
  2. Typical applications
  3. Characteristics
  4. Technical data table
  5. Optional equipment

Publication details

Authors
COVER (COMEX S.A.)
Publisher
COVER (COMEX S.A.)
Year
Year not stated
Document language
Polish
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

COVER (COMEX S.A.) COVER PS 10–40K, PS_10-40K_KK_PL_24240. COVER (COMEX S.A.). https://comex.com.pl/wp-content/uploads/2026/06/PS_10-40K_KK_PL_24240.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.