IPPON Innova RT II New 6000/10000 UPS User Manual
Original title IPPON Innova RT II New 6000–10000 manual V4.2023, pp.41–44
IPPON
IPPON's 2023 manual gives installation, EBM battery module, paralleling and 160-275 V input data for the 6 and 10 kVA single-phase Innova RT II New online UPS.
On this page
Overview
The document is the Russian-language user manual (V4, 2023) for the IPPON Innova RT II New 6000 and 10000 UPS and its external battery module (EBM), made in China by Nippon Klick Systems Limited. Its sections cover safety rules, appearance, installation, power cable connection, optional parallel installation, operation, communication interfaces, maintenance, troubleshooting, specifications, warranty, and extending runtime with external battery modules.
The manual describes the unit as an online double-conversion UPS with full digital control, unity output power factor, a high-power charger and automatic detection of the number of external battery modules. It protects against outages, sags, surges, line noise, frequency variation and harmonic distortion. Modbus TCP, RS232, USB, IoT and optional smart-card connections are defined.
The specification table gives models of 6 kVA/6 kW and 10 kVA/10 kW; output is 220/230/240 V, regulation ±1%, frequency 50 or 60 Hz ±0.1 Hz, THD 1%, crest factor at least 3:1 and transfer time 0 ms. The input is accepted at 160-275 V at 100% load and 110-275 V at 50% load, 45-66 Hz. Efficiency is above 95% in line mode and above 98% in ECO mode. Automatic and mechanical bypass are fitted; up to 3 units can be paralleled for power redundancy.
The battery is sixteen 12 V sealed lead-acid blocks, 7 Ah on the 6000 and 9 Ah on the 10000; runtime at full load is 4.5 and 1.9 minutes respectively, and charging to 90% from full discharge takes 3 hours. In line-mode overload at 105-125% the unit transfers to automatic bypass after 10 minutes. Dimensions are stated for UPS plus EBM, and net weight for UPS plus EBM plus MBP, so the table footnotes matter when calculating installation space.
Key points
- Models: Innova RT II New 6000 (6 kVA/6 kW) and 10000 (10 kVA/10 kW), single phase, 220/230/240 V output.
- Output regulation ±1%; frequency 50 or 60 Hz ±0.1 Hz; THD 1%; crest factor at least 3:1; transfer time 0 ms.
- Input range: 160-275 V at 100% load, 110-275 V at 50% load; frequency 45-66 Hz.
- Efficiency: above 95% in line mode, above 98% in ECO mode.
- Battery: sixteen 12 V blocks; 7 Ah (6000), 9 Ah (10000); full-load runtime 4.5 min and 1.9 min.
- Charge to 90% from full discharge takes 3 hours.
- Line-mode overload: 100-105% continuous; 10 min then bypass at 105-125%; 30 s at 125-150%; 500 ms above 150%.
- Up to 3 units in parallel for power redundancy; automatic and mechanical bypass standard.
- Surge protection: 405 J line-neutral, 445 J line/neutral-earth.
Using it in design
- When adding external battery modules, use the runtime-extension appendix (Appendix 1) and note that the number of EBMs is detected automatically.
- In space calculations, remember that dimensions are for UPS+EBM and weight is for UPS+EBM+MBP.
- On networks with a narrow input voltage window, check the 160 V lower limit at 100% load.
- For a parallel redundant installation, plan for the 3-unit limit and the parallel signal cable.
- If ECO mode will be used, compare its reduced protection with load sensitivity.
Who should read it
Technicians installing single-phase UPS in small and medium IT rooms, and designers working with Russian-language sources.
Document contents
- Introduction and features
- Safety rules
- Appearance and layout
- Installation
- Connecting power cables
- Parallel system installation and operation (optional)
- Operation
- Communication interfaces
- UPS maintenance
- Troubleshooting
- Technical specifications
- Warranty terms
- Appendix 1: Extending runtime with external battery modules
Publication details
- Authors
- IPPON
- Publisher
- IPPON
- Year
- Year not stated
- Document language
- Russian
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
IPPON IPPON Innova RT II New 6000–10000 manual V4.2023, pp.41–44. IPPON. https://static.ippon.ru/data/download/UPS_Innova_RT_II_New_6000-10000_manual.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.