HBL OPTIMUZ Sealed Maintenance Free VRLA Batteries: Dec.2025, PDF p.4
HBL Engineering
A manufacturer leaflet giving construction, charge settings and a constant-power discharge table for a family of 12 V monobloc VRLA batteries from 7 to 200 Ah for UPS use.
On this page
Overview
HBL's OPTIMUZ family is a range of 12 V sealed maintenance-free valve-regulated lead-acid (VRLA) monoblocs for UPS, telecom, banking and IT applications. The leaflet lists the design features: cyclic lead alloy on the positive plate, radial grids, AGM separator, copper-alloy screw terminals, a high-impact PP/ABS container and a self-releasing EPDM pressure valve. The product claims conformance to JIS C 8702-1.
Charge settings are given at 27 °C: for float use boost 13.8-14.0 V and float 13.4-13.5 V, for cyclic use 13.8-14.0 V. The current limit is a minimum of 10% and a maximum of 30% of rated capacity. For temperature compensation the charge voltage is reduced by 18 mV for every 1 °C rise in temperature and increased when it falls.
Life information is given in two graphs: cycle life against depth of discharge (100%, 50% and 30%), and design float life, defined in calendar years at 27 °C with a float voltage of 2.25 V per cell; float life shortens as ambient temperature rises. C20 is the nominal capacity at the 20-hour discharge rate.
The product table gives, for 14 models, the 20-hour capacity (Ah), dimensions (mm), weight (kg) and constant-power values (watts per block to an end voltage of 10.5 V at 27 °C) from 10 minutes to 20 hours. For example the OPTI 100 is 100 Ah, 410 x 175 x 225 mm and 30 kg, and delivers 1625 W for 15 minutes.
Key points
- Family of 14 models from OPTI 7 to OPTI 200PLUS, 7-200 Ah (C20), 12 V monobloc.
- The power table is in watts per block, at 27 °C and 10.5 V end voltage; durations 10 min, 15 min, 30 min, 1, 3, 5, 10 and 20 hours.
- OPTI 100: 100 Ah, 410 x 175 x 225 mm, 30 kg; 1991 W at 10 min, 1625 W at 15 min, 1078 W at 30 min, 674 W at 1 hour.
- OPTI 200: 200 Ah, 525 x 225 x 225 mm, 56 kg; 3250 W at 15 min.
- A high-wattage model of 720 W (15 min at 10.2 V) and OPTIPLUS C10 models (100, 120, 150, 160, 200 Ah) are available separately; an FR container is optional.
- Float charge: boost 13.8-14.0 V, float 13.4-13.5 V (27 °C); current limit 10-30% of capacity.
- Temperature compensation: reduce by 18 mV per 1 °C rise.
- Design float life is defined at 27 °C and 2.25 V per cell; life shortens with temperature.
Using it in design
- In UPS battery sizing use the watts-per-block table only with its stated conditions, 27 °C and 10.5 V end voltage; if the UPS uses a different end voltage, match it to the manufacturer's table.
- Check the cell count (6-cell block) and the UPS DC bus voltage, then convert the 15-minute requirement into a block count from the table.
- Assess battery room temperature against the 27 °C reference; at high ambient the float life is shorter, and the charge voltage compensation (18 mV/°C) should be set in the charger.
- Compare block dimensions and weights (for example 30 kg and 56 kg) with floor loading and rack capacity in the layout.
- Use the table rows for short high-rate backup (10-15 min) and the C20 rows for longer duration, and compare against the voltage-time curve.
Who should read it
Electrical engineers sizing UPS battery banks and teams writing battery specifications.
Document contents
- Applications
- Design and construction features
- Charge settings
- Cycle life and float life
- Discharge characteristics
- Product specifications and constant-power table
Publication details
- Authors
- HBL Engineering
- Publisher
- HBL Engineering
- Year
- 2025
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
HBL Engineering (2025). HBL OPTIMUZ Sealed Maintenance Free VRLA Batteries: Dec.2025, PDF p.4. HBL Engineering. https://hblbatteries.com/12V-smf-vrla-optimuz-series-product-leaflet.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.