Technical guideFree to readYear not stated

JYC HR Series: Product specifications for various models

JYC Battery

The HR series page from JYC Battery lists 27 high-rate 12 V VRLA battery models for UPS and EPS applications, with 15-minute ratings from 28 W to 870 W per cell; the manufacturer states that the series delivers 30% more power than its own GP series.

On this page

Overview

The page presents the HR series that Chinese manufacturer JYC Battery designs for applications needing high power output. The manufacturer states that improvements in grid design and plate paste formula let the series deliver 30% more power than its general-purpose GP series. The applications listed are UPS and EPS systems, generator starting and electronic toys. All models are 12 V blocks. The standards listed are GB/T 19639.1-2005, IEC 60896-21/22:2004, IEC 61056-1/2:2002 and BS 6290-4:1997.

The product features section gives the capacity range as 5-28 Ah at C20, 35-150 Ah at C10 and 21-510 W per cell at 25 °C. Designed floating life at 25 °C is 5 years for blocks of 14 Ah and below and 6 years for larger blocks. Self-discharge is 2% per month or less at 25 °C, gas recombination efficiency is 98% or more and the operating temperature range is -20 to 50 °C. These figures apply to the series as a whole; the model table carries no ampere-hour capacity.

The model table lists 27 blocks from HR1228W to HR12870W. Each model has a 15-minute rate in watts per cell that equals the number in the model name; the table does not state the end voltage to which that rate is defined. The table also gives length, width, height, total height including terminals, approximate weight and terminal type (F2, T1 to T5). The smallest block, HR1228W, measures 151 x 65 x 94 mm and weighs 2.3 kg; the largest, HR12870W, measures 522 x 268 x 220 mm and weighs 74.2 kg. The table's top value of 870 W per cell exceeds the 510 W per cell upper limit quoted in the features section.

Key points

  1. 27 models, all 12 V, from HR1228W to HR12870W; 15-minute rate 28-870 W/cell.
  2. Manufacturer's claim: the HR series delivers 30% more power than the JYC GP series.
  3. Designed floating life (25 °C): 5 years for 14 Ah and below; 6 years for 15 Ah and above.
  4. Self-discharge 2% per month or less (25 °C); gas recombination efficiency 98% or more; operating temperature -20 to 50 °C.
  5. Standards: GB/T 19639.1-2005, IEC 60896-21/22:2004, IEC 61056-1/2:2002, BS 6290-4:1997.
  6. Sample blocks: HR12200W 230 x 139 x 210 mm, 16.0 kg; HR12400W 330 x 172 x 218 mm, 30.3 kg; HR12560W 481 x 170 x 242 mm, 43.8 kg.
  7. HR12700W, 730W, 760W and 800W share one container (522 x 240 x 221 mm); weights 57.7, 59.9, 60.9 and 63.5 kg.
  8. HR12870W: 522 x 268 x 220 mm, 74.2 kg, T5 terminal.

Using it in design

  • For UPS battery sizing, multiply the W/cell figure by the 6 cells of a 12 V block to get block power; confirm the end voltage of the 15-minute rate with the manufacturer and compare it with the UPS DC cut-off voltage.
  • For autonomies other than 15 minutes, request the model's constant-power discharge table from the manufacturer; the page gives one duration only.
  • Hold the battery room near 25 °C; the 5 and 6 year design life is defined at that temperature.
  • Use the tabulated weights for floor loading and cabinet selection: a string of 40 HR12800W blocks weighs about 2540 kg.
  • The four models sharing the 522 x 240 mm footprint allow the power step to be chosen without changing the cabinet.

Who should read it

Electrical designers selecting high-rate UPS batteries and engineers laying out battery cabinets.

Document contents

  1. Applications
  2. Product Features
  3. Standard Compliant
  4. Product specifications for various models

Publication details

Authors
JYC Battery
Publisher
JYC Battery
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

JYC Battery JYC HR Series: Product specifications for various models. JYC Battery. https://jyc-battery.com/high-rate-battery-hr-series/

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.