OUTDO OT9-12 F1 datasheet (No. 302010005-00078)

Original title OUTDO OT9-12 F1 datasheet: No.302010005-00078, p.1

OUTDO (Zhangzhou Huawei Power Supply Technology)

Datasheet for the OUTDO OT9-12, a 12 V, 9 Ah (20-hour) VRLA-AGM small-series battery: 18 mohm internal resistance, 2.40 kg, 65 percent residual capacity after 12 months and 14.5-14.9 V cycle charge voltage.

On this page

Overview

The datasheet presents the OT9-12, one of the OUTDO-branded industrial VRLA-AGM small-series batteries from Zhangzhou Huawei Power Supply Technology. The battery is 12 V and 9 Ah at the 20-hour rate (0.45 A) at 25 °C; terminal type is F1 and the container colour is black or grey. UL, CE and a further approval mark appear on the sheet. The plane chart shows 151 ± 2 mm length, 65 ± 2 mm width, 94 ± 2 mm container height and 100 ± 2 mm total height.

The parameter chart gives discharge testing at two currents: 34 minutes at 20 I20 (9 A) and 8 minutes at 60 I20 (27 A). Internal resistance of a fully charged battery at 25 °C is 18 mohm. Temperature effect on capacity, taking 25 °C as 100 percent, is 104 percent at 40 °C, 83 percent at 0 °C and 65 percent at -15 °C. Residual capacity after storage is 91 percent at 3 months, 82 percent at 6 months and 65 percent at 12 months; the chart shows loss curves for 0, 10, 25, 30 and 40 °C up to 18 months.

Charging data prescribe an initial charging current below 2.7 A with constant voltage of 14.5 to 14.9 V for cycle use, and a charge voltage of 13.6 to 13.8 V for float use. Approximate weight is 2.40 kg. The sheet plots discharge curves from 0.05C to 3C as terminal voltage against time. A footnote states that the values are averages obtained from the first three charge-discharge cycles and are not minimum values.

The document is a single-sheet manufacturer datasheet. Small-format batteries of this kind serve small UPS units, alarm and security systems; they matter in auxiliary and small backup power applications rather than in large data-centre UPS strings.

Key points

  1. Model OT9-12; 12 V, 9 Ah (20-hour rate, 0.45 A, 25 °C).
  2. Discharge time at 25 °C: 34 min at 9 A, 8 min at 27 A.
  3. Internal resistance (fully charged, 25 °C) 18 mohm.
  4. Capacity by temperature: 40 °C 104 percent, 25 °C 100 percent, 0 °C 83 percent, -15 °C 65 percent.
  5. Residual capacity after storage: 3 months 91 percent, 6 months 82 percent, 12 months 65 percent (25 °C).
  6. Cycle charge: initial current below 2.7 A, 14.5-14.9 V; float charge 13.6-13.8 V.
  7. Approximate weight 2.40 kg; 151 x 65 x 100 mm (total height); terminal type F1.
  8. Values are averages of the first three cycles, not minimum values.

Using it in design

  • In cold environments (0 °C, -15 °C), use the capacity loss (83 and 65 percent) as a correction factor in backup time calculations.
  • Set float voltage within 13.6-13.8 V, and write the 14.5-14.9 V cycle charge voltage and sub-2.7 A initial current into the charger specification.
  • If batteries will sit in stock, allow for the 35 percent capacity loss over a year at 25 °C and plan refresh charging for long storage.
  • For small signal and alarm loads, check runtime by comparing the 9 A and 27 A discharge times with the load current.

Who should read it

Electrical designers selecting VRLA batteries for small UPS units, alarm and security systems, and teams cataloguing battery data.

Document contents

  1. Product name and model
  2. Plane chart
  3. Parameter chart
  4. Residual capacity
  5. Discharge current curves at 25 °C

Publication details

Authors
OUTDO (Zhangzhou Huawei Power Supply Technology)
Publisher
OUTDO (Zhangzhou Huawei Power Supply Technology)
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

OUTDO (Zhangzhou Huawei Power Supply Technology) OUTDO OT9-12 F1 datasheet: No.302010005-00078, p.1. OUTDO (Zhangzhou Huawei Power Supply Technology). https://www.winwinuni.com/images/column_1734312672/OT9-12%20(12V%209Ah).pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.