Technical guideFree to readYear not stated

Rahimafrooz Industry Battery RA Series: AGM VRLA model tables

Original title Rahimafrooz Industry Battery RA Series: PDF pp.3–4 model tables

Rahimafrooz

Model tables for Rahimafrooz's general-purpose RA series of AGM VRLA batteries in 2, 6 and 12 V: C10 and C20 capacities at 1.80 V per cell and 25 °C, with dimensions, weight and terminal type.

On this page

Overview

The document is a product catalogue from the Bangladeshi manufacturer Rahimafrooz introducing its RA family. The RA series is presented as a maintenance-free, general-purpose valve-regulated lead-acid (VRLA) AGM battery with a stated design life of 5 to 8 years. Listed applications include UPS, telecommunications and electrical equipment, fire alarm and security systems, automation, and emergency power in generating plants and substations.

The core of the document is the model-level technical table. 6 V monoblocs range from 3 to 14 Ah, 12 V monoblocs from 4 to 250 Ah, and 2 V cells from 65 to 3000 Ah. Each row gives nominal voltage, C10 and C20 capacity, length, width, height and total height, weight and terminal code. The capacity tables are based on 25 °C and a 1.80 V per cell end voltage.

The catalogue also compares AGM and gel electrolyte and gives design features for the high-capacity 2 V series. For these it states a 200 to 3000 Ah range, a 15-year design float life, a 15 to 40 °C operating range and recommended float voltages of 2.25 V per cell or 2.27 V per cell at 25 °C. It is a product introduction, so it supplies capacity and dimensions rather than discharge-current or power tables.

Whether a quoted capacity is C10 or C20 matters in selection: for the same model the C20 figure is about 5 percent higher than C10. A designer sizing UPS autonomy from Ah alone should confirm the discharge-time basis and end voltage separately rather than assuming the table matches the UPS cut-off.

Key points

  1. The RA family is AGM VRLA technology with a stated 5 to 8 year design life.
  2. Capacity is given as C10 and C20; the reference conditions are 25 °C and 1.80 V per cell.
  3. 6 V models run from RA6-3.0 to RA6-14, 2.84 to 13.3 Ah (C10).
  4. 12 V models run from RA12-4.0 to RA12-250; RA12-230 is 230 Ah (C10), 243.3 Ah (C20) and 63.5 kg.
  5. 2 V cells run from RA2-65 to RA2-3000; RA2-2000 is 2000 Ah (C10), 2130 Ah (C20) and 121 kg.
  6. The high-capacity 2 V series states a 15-year float design life and a 15 to 40 °C operating range.
  7. Recommended float voltage at 25 °C is 2.25 V per cell (VS series) and 2.27 V per cell (VT series); VT equalizing voltage is 2.40 V per cell.
  8. Certifications listed include ISO 9001, ISO 14001, UL, IEC 60896-21/22 and CE.

Using it in design

  • When sizing a UPS battery string, keep the C10 and C20 columns apart and use the one matching the discharge time.
  • Compare the 1.80 V per cell, 25 °C basis of the capacity table with the UPS end-of-discharge voltage and the room temperature.
  • Use the length, width, total height and weight columns for rack and cabinet layout, and the terminal code to specify connectors.
  • Carry the 25 °C float voltage, with temperature compensation, into the charger settings.
  • Reflect the 5 to 8 year design life of the general-purpose RA series in the replacement plan and lifecycle cost for critical backup.

Who should read it

Electrical designers sizing UPS battery banks, and teams preparing battery procurement or catalogue data.

Document contents

  1. General RA types and features
  2. Applications
  3. Product specification: 6 V, 12 V and 2 V model tables
  4. AGM versus gel comparison
  5. Design features of high-capacity 2 V series

Publication details

Authors
Rahimafrooz
Publisher
Rahimafrooz
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Rahimafrooz Rahimafrooz Industry Battery RA Series: PDF pp.3–4 model tables. Rahimafrooz. https://www.rahimafrooz-batteries.com/wp-content/uploads/2021/01/Telecom_VRLA_GEL_Battery.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.