Technical guideFree to read2020

Tudor Stationary Catalogue 2020-2021: printed pp.5-6, PDF pp.3-4

Original title Tudor Stationary Catalogue 2020–2021: printed pp.5–6, PDF pp.3–4

Tudor Brazil

Catalogue pages from Brazil's Tudor giving capacity, weight, size, base and terminal configurations, voltage settings and handling warnings for its 12TE series 12 V stationary monobloc batteries.

On this page

Overview

The pages open with a matrix that maps solutions to operating conditions: high temperature, constant cycling, compatibility with electronic equipment, secure connections, external and internal short circuit, fluctuation, ripple frequency, acid gases, electrolyte leakage, vibration and long service life. It shows which design element (high-tin Ca-Ca alloy, free electrolyte, A.G.A. filter, grid fillets with alternating wires, enveloped separator, condensation chamber, protected threaded pole, stainless screws, sealing resin or O-ring) contributes to which resistance. A 24-part expanded view of the battery follows.

The electrical and dimensional table gives twelve 12 V models: 12TE25, 26, 36, 45, 60, 65, 86, 105, 150, 170, 180 and 220. C10, C20 and C100 capacities are separate columns; for example 24, 25 and 27 Ah for 12TE25, 95, 105 and 115 Ah for 12TE105, and 200, 220 and 230 Ah for 12TE220. Weights run from 10.00 kg (12TE25) to 60.90 kg (12TE220) and sizes from 196 x 128 x 187 mm to 515 x 275 x 245 mm.

Each model lists base type (B0, B1, B3), configuration (D1, D2, D3) and terminal type (X, F or T/M external thread). For all models the floating voltage is 13.40-13.80 V, load voltage 14.40-14.80 V and equalization voltage 15.20-15.80 V. Recommended torque is 7-10 N-m for X and F terminals and 20-25 N-m for T/M; washers go between the connection cable and the fixing nut, not between terminal and cable.

The last part gives warnings: explosive gases, sulfuric acid contact, first aid, installation order (positive cable first), no disposal in household waste and recycling. The data are not a contractual commitment and can change within normal manufacturing tolerances.

Key points

  1. The 12TE family has 12 models: 12TE25, 26, 36, 45, 60, 65, 86, 105, 150, 170, 180, 220; all 12 V.
  2. C10 / C20 / C100: 12TE25 24/25/27 Ah, 12TE60 54/60/65 Ah, 12TE105 95/105/115 Ah, 12TE150 142/150/160 Ah, 12TE220 200/220/230 Ah.
  3. Weight ranges from 10.00 kg (12TE25) to 60.90 kg (12TE220); for example 12TE105 26.70 kg, 12TE150 42.90 kg.
  4. Dimensions (L x W x H): 12TE25 196 x 128 x 187 mm, 12TE105 330 x 174 x 242 mm, 12TE220 515 x 275 x 245 mm.
  5. For all models floating 13.40-13.80 V, load 14.40-14.80 V, equalization 15.20-15.80 V.
  6. Terminal torque: 7-10 N-m for X and F, 20-25 N-m for T/M.
  7. Base types B0, B1, B3; configurations D1, D2, D3; terminal types X, F, T/M.
  8. Design elements include high-tin Ca-Ca alloy, free electrolyte, A.G.A. filter, condensation chamber, enveloped separator and stainless fasteners.

Using it in design

  • Do not mix the C10, C20 and C100 columns; use the capacity rate that matches the UPS discharge time.
  • Set charger parameters to the catalogue voltage ranges (13.40-13.80 V float, 15.20-15.80 V equalization).
  • Use weight and size values in rack layout and floor loading calculations.
  • Choose torque and cable lug by terminal type (7-10 or 20-25 N-m).
  • For high temperature or constant cycling, check the design elements in the matrix; consult the manufacturer for other conditions.

Who should read it

UPS and DC system designers selecting stationary batteries, and battery maintenance teams.

Document contents

  1. Solutions versus adversities matrix
  2. Expanded view
  3. Electrical and dimensional features
  4. Terminals
  5. Base
  6. Configuration
  7. Danger and environment warnings

Publication details

Authors
Tudor Brazil
Publisher
Tudor Brazil
Year
2020
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Tudor Brazil (2020). Tudor Stationary Catalogue 2020–2021: printed pp.5–6, PDF pp.3–4. Tudor Brazil. https://tudor.com.br/assets/upload/catalogo_estacion_ria_ingl_s_1.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.