Delta UPS EMEA catalogue EMACAQ-07-ZL: Ultron DPS Gen2, printed pp.37-38 / PDF p.20
Original title Delta UPS EMEA catalogue EMACAQ-07-ZL: Ultron DPS Gen2, printed pp.37–38 / PDF p.20
Delta
The Ultron DPS Gen2 pages of Delta's EMEA UPS catalogue describe a three-phase double-conversion UPS family from 300 to 1200 kVA: unity output power factor, efficiency up to 96.5% in online mode and up to 99% in ECO mode, and 9.6 MW of capacity with up to 8 units in parallel.
On this page
Overview
The source is the two-page spread on the Ultron DPS Gen2 series in Delta's EMEA catalogue (EMACAQ-07-ZL), which covers the company's whole UPS range. The series is positioned for large data centres and colocation facilities and has seven ratings: DPS G2-300K, 400K, 500K, 600K, 800K, 1000K and 1200K. Because output power factor is 1, kVA and kW ratings are equal. Paralleling of up to eight units gives up to 9.6 MW for redundancy or capacity expansion.
Nominal input and output voltage is 380/400/415 Vac, three-phase four-wire plus PE. The input window is 305 to 477 Vac at full load (305 to 324 Vac is a conditional application); between 229 and 305 Vac the load is derated to 70% to 100%. Input current distortion is below 3% with linear load and input power factor is above 0.99 at full load. Output voltage regulation is ±1%, frequency 50/60 ±0.05 Hz, and voltage distortion below 1.5% with linear load. Overload capability is 10 minutes up to 125% and 1 minute up to 150%.
Efficiency is given as up to 96.5% in online mode and up to 99% in ECO mode; the catalogue publishes upper values, not a load curve. The battery side supports VRLA and lithium-ion at 480 Vdc nominal. The number of 12 V VRLA blocks is configurable from 30 to 46, but 30 to 36 blocks require set-up by authorised personnel and load derating. Maximum charge current ranges from 90 A (300K) to 360 A (1200K) by rating. Short-circuit withstand rating is 65 kA on the smaller ratings and 100 kA on the larger ones.
Physical data: depth of 900 mm and height of 2000 mm are common to all ratings; width is 600 mm for 300K, 1200 mm for 400K to 600K, 1800 mm for 800K and 2450 mm for 1000K and 1200K. The 600 and 1200 mm widths include four built-in switches. Net weight runs from 515 kg (300K) to 2000 kg (1200K). Operating temperature is 0 to 40 °C, with 1% derating per 100 metres between 1001 and 2000 metres. Conformance: CE, UKCA, IEC 62040-2 and IEC 62040-3.
Key points
- Seven ratings: 300, 400, 500, 600, 800, 1000 and 1200 kVA; output power factor 1 (kVA = kW); up to 8 units in parallel, 9.6 MW total.
- Input and output: 380/400/415 Vac, 3P4W+PE; input window 305...477 Vac at full load, derating to 70...100% load between 229 and 305 Vac.
- Efficiency: up to 96.5% in online mode, up to 99% in ECO mode.
- THDi below 3% with linear load; input power factor above 0.99; THDv below 1.5% with linear load; regulation ±1%.
- Overload: 10 minutes up to 125%, 1 minute up to 150%, 1 second above 150%.
- Short-circuit withstand rating: 65 kA on the smaller ratings, 100 kA on the larger ones.
- Battery: VRLA or lithium-ion, 480 Vdc nominal; 30...46 blocks of 12 V (30...36 blocks need authorised set-up and load derating).
- Maximum charge current: 90 / 120 / 150 / 180 / 240 / 300 / 360 A (300K to 1200K).
- Dimensions (W x D x H): 600 x 900 x 2000 mm (300K), 1200 x 900 x 2000 mm (400K...600K), 1800 x 900 x 2000 mm (800K), 2450 x 900 x 2000 mm (1000K, 1200K).
- Net weight: 515 / 700 / 811 / 970 / 1270 / 1850 / 2000 kg; operating 0...40 °C; 1% derating per 100 m between 1001 and 2000 m.
Using it in design
- With unity power factor, select the UPS directly against the kW load, and set the unit count for an N+1 arrangement within the 8-unit parallel limit.
- Treat 96.5% as the upper bound in UPS heat-loss and PUE calculations, and request the part-load efficiency curve from the manufacturer.
- If ECO mode (up to 99%) will be used, assess separately the load's exposure to mains quality through bypass.
- Design the battery string on a 40-block (480 Vdc) basis; for 30...36 block strings, allow for load derating and authorised commissioning.
- Compare the prospective short-circuit current at the UPS input with the 65 kA or 100 kA withstand rating of the selected size.
- Use width and net weight in the room layout (2450 mm and 2000 kg for 1200K); external batteries are not included in these figures. Apply 1% per 100 m derating above 1000 metres.
Who should read it
Electrical designers selecting central UPSs for large data centres and colocation facilities, specification writers, and technical procurement teams.
Document contents
- Ultron DPS Gen2 Series UPS: Three-phase, 300-1200 kVA
- Ultimate Availability
- Excellent Performance
- Sophisticated Manageability and Flexibility
- Technical Specifications: Input, Output, Efficiency, Battery, Communication Interface, Physical, Environment, Conformance, Features
Publication details
- Authors
- Delta
- Publisher
- Delta
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Delta Delta UPS EMEA catalogue EMACAQ-07-ZL: Ultron DPS Gen2, printed pp.37–38 / PDF p.20. Delta. https://www.deltapowersolutions.com/media/download/Brochure_UPS_en-EMEA_EMACAQ-07-ZL.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
