Technical guideFree to readYear not stated

Enertech UPS catalogue: Concord technical specifications

Original title Enertech UPS catalogue: Concord technical specifications, PDF p.4

Enertech UPS

The 1-250 kVA product catalogue of Indian manufacturer Enertech UPS Pvt. Ltd. describes on page 4 the Concord series online double-conversion UPS: 10, 15, 20, 25, 30 and 40 kVA (8-32 kW at power factor 0.8), three-phase input with single-phase 230 V output, a built-in galvanic isolation transformer and typical overall efficiency of 85-93%.

On this page

Overview

The six-page catalogue presents the range of Enertech UPS Pvt. Ltd., in business since 1990 and manufacturing at Pirangut near Pune. The company is certified to ISO 9001:2008 and the catalogue refers to more than 6000 customers and to installations in demanding defence and railway environments. There are three UPS series: Nano (1-10 kVA), Concord (10-40 kVA) and Atlas (60-250 kVA). The catalogue dates from the ISO 9001:2008 era and its milestone list ends in 2010 with a 250 kVA three-phase online UPS; current model status should be confirmed with the manufacturer.

The Concord series is an IGBT-based, microprocessor-controlled, PWM double-conversion UPS with a built-in galvanic isolation transformer. Six ratings are given in kVA and kW: 10 kVA / 8 kW, 15 / 12, 20 / 16, 25 / 20, 30 / 24 and 40 / 32. Input is 415 VAC three-phase (360-480 V) at 50 Hz ±3%; input power factor is above 0.9 and input current distortion is typically 10%. Output is 230 VAC ±1% single-phase with voltage distortion of at most 3% and a 3:1 crest factor.

Battery bus voltage is 324, 360 or 384 V depending on rating. The battery type can be sealed maintenance-free VRLA or tubular lead-acid, and charging current is 10% of the battery Ah capacity. Overload capability is 125% for 1 minute and 150% for 10 seconds, and bypass transfer time is 0 ms. Overall efficiency is given as typically 85-93% and inverter efficiency as typically 90-93%. Noise stays within 50 dB above ambient and cooling is forced air.

Options include mobile connectivity, a redundant UPS for 24x7 operation (hot standby or load sharing), an active or passive harmonic filter at the input and SNMP/MODBUS connectivity. Weights are 90, 110, 125, 150, 170 and 180 kg; dimensions are given as approximate for two cabinets, 600 x 700 x 750 mm and 700 x 750 x 750 mm. Target applications are servers, small offices, SMEs and banking. The typical 10% input current distortion and the transformer-based build place the series in an older design generation than current transformerless UPSs.

Key points

  1. Concord ratings: 10 kVA / 8 kW, 15 / 12, 20 / 16, 25 / 20, 30 / 24, 40 kVA / 32 kW.
  2. Three-phase input (415 VAC, 360-480 V, 50 Hz ±3%), single-phase output (230 VAC ±1%).
  3. Input power factor > 0.9; input THDi typically 10%.
  4. Output THD ≤ 3%, crest factor 3:1, transfer time 0 ms.
  5. Overload: 125% for 1 minute, 150% for 10 seconds.
  6. Overall efficiency typically 85-93%; inverter efficiency typically 90-93%.
  7. Battery bus 324, 360 or 384 V; VRLA or tubular lead-acid; charging current 10% of Ah capacity.
  8. Weight: 90, 110, 125, 150, 170 and 180 kg; built-in galvanic isolation transformer is standard.
  9. Other series in the catalogue: Nano 1-10 kVA and Atlas 60-250 kVA.

Using it in design

  • With a 0.8 power factor, compare the IT load against the kW row: a 32 kW load needs the 40 kVA model.
  • Single-phase output at 40 kVA means about 174 A; size the output cable, breaker and distribution board for that current.
  • Allow for the typical 10% input current distortion in generator and transformer sizing, and add the input harmonic filter option to the specification where needed.
  • Use the lower end of the efficiency range (85%) for the heat load: losses can reach 5.6 kW at 32 kW load.
  • Design the battery string for the 324, 360 or 384 V bus of the chosen rating and calculate recharge time at a current of 10% of Ah capacity.
  • Because the catalogue is dated, request a current datasheet, a dimensioned drawing and the weight with batteries at the bid stage.

Who should read it

Electrical designers assessing a 10-40 kVA UPS in the Indian market and maintenance teams operating or replacing existing Enertech installations.

Document contents

  1. Introduction and Company Profile
  2. Manufacturing and R & D facilities, Quality, Certificates & Approvals
  3. Success Stories & Milestones
  4. Nano Series (1-10 kVA)
  5. Concord Series (10-40 kVA)
  6. Atlas series (60-250 kVA)
  7. Other products: Stabilisers, Inverters, Battery Chargers

Publication details

Authors
Enertech UPS
Publisher
Enertech UPS
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Enertech UPS Enertech UPS catalogue: Concord technical specifications, PDF p.4. Enertech UPS. https://www.enertechups.com/wp-content/uploads/2021/06/ENERTECH-UPS-CATALOGUE-2.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.