Enertech UPS catalogue: Concord technical specifications
Original title Enertech UPS catalogue: Concord technical specifications, PDF p.4
Enertech UPS
The 1-250 kVA product catalogue of Indian manufacturer Enertech UPS Pvt. Ltd. describes on page 4 the Concord series online double-conversion UPS: 10, 15, 20, 25, 30 and 40 kVA (8-32 kW at power factor 0.8), three-phase input with single-phase 230 V output, a built-in galvanic isolation transformer and typical overall efficiency of 85-93%.
On this page
Overview
The six-page catalogue presents the range of Enertech UPS Pvt. Ltd., in business since 1990 and manufacturing at Pirangut near Pune. The company is certified to ISO 9001:2008 and the catalogue refers to more than 6000 customers and to installations in demanding defence and railway environments. There are three UPS series: Nano (1-10 kVA), Concord (10-40 kVA) and Atlas (60-250 kVA). The catalogue dates from the ISO 9001:2008 era and its milestone list ends in 2010 with a 250 kVA three-phase online UPS; current model status should be confirmed with the manufacturer.
The Concord series is an IGBT-based, microprocessor-controlled, PWM double-conversion UPS with a built-in galvanic isolation transformer. Six ratings are given in kVA and kW: 10 kVA / 8 kW, 15 / 12, 20 / 16, 25 / 20, 30 / 24 and 40 / 32. Input is 415 VAC three-phase (360-480 V) at 50 Hz ±3%; input power factor is above 0.9 and input current distortion is typically 10%. Output is 230 VAC ±1% single-phase with voltage distortion of at most 3% and a 3:1 crest factor.
Battery bus voltage is 324, 360 or 384 V depending on rating. The battery type can be sealed maintenance-free VRLA or tubular lead-acid, and charging current is 10% of the battery Ah capacity. Overload capability is 125% for 1 minute and 150% for 10 seconds, and bypass transfer time is 0 ms. Overall efficiency is given as typically 85-93% and inverter efficiency as typically 90-93%. Noise stays within 50 dB above ambient and cooling is forced air.
Options include mobile connectivity, a redundant UPS for 24x7 operation (hot standby or load sharing), an active or passive harmonic filter at the input and SNMP/MODBUS connectivity. Weights are 90, 110, 125, 150, 170 and 180 kg; dimensions are given as approximate for two cabinets, 600 x 700 x 750 mm and 700 x 750 x 750 mm. Target applications are servers, small offices, SMEs and banking. The typical 10% input current distortion and the transformer-based build place the series in an older design generation than current transformerless UPSs.
Key points
- Concord ratings: 10 kVA / 8 kW, 15 / 12, 20 / 16, 25 / 20, 30 / 24, 40 kVA / 32 kW.
- Three-phase input (415 VAC, 360-480 V, 50 Hz ±3%), single-phase output (230 VAC ±1%).
- Input power factor > 0.9; input THDi typically 10%.
- Output THD ≤ 3%, crest factor 3:1, transfer time 0 ms.
- Overload: 125% for 1 minute, 150% for 10 seconds.
- Overall efficiency typically 85-93%; inverter efficiency typically 90-93%.
- Battery bus 324, 360 or 384 V; VRLA or tubular lead-acid; charging current 10% of Ah capacity.
- Weight: 90, 110, 125, 150, 170 and 180 kg; built-in galvanic isolation transformer is standard.
- Other series in the catalogue: Nano 1-10 kVA and Atlas 60-250 kVA.
Using it in design
- With a 0.8 power factor, compare the IT load against the kW row: a 32 kW load needs the 40 kVA model.
- Single-phase output at 40 kVA means about 174 A; size the output cable, breaker and distribution board for that current.
- Allow for the typical 10% input current distortion in generator and transformer sizing, and add the input harmonic filter option to the specification where needed.
- Use the lower end of the efficiency range (85%) for the heat load: losses can reach 5.6 kW at 32 kW load.
- Design the battery string for the 324, 360 or 384 V bus of the chosen rating and calculate recharge time at a current of 10% of Ah capacity.
- Because the catalogue is dated, request a current datasheet, a dimensioned drawing and the weight with batteries at the bid stage.
Who should read it
Electrical designers assessing a 10-40 kVA UPS in the Indian market and maintenance teams operating or replacing existing Enertech installations.
Document contents
- Introduction and Company Profile
- Manufacturing and R & D facilities, Quality, Certificates & Approvals
- Success Stories & Milestones
- Nano Series (1-10 kVA)
- Concord Series (10-40 kVA)
- Atlas series (60-250 kVA)
- Other products: Stabilisers, Inverters, Battery Chargers
Publication details
- Authors
- Enertech UPS
- Publisher
- Enertech UPS
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Enertech UPS Enertech UPS catalogue: Concord technical specifications, PDF p.4. Enertech UPS. https://www.enertechups.com/wp-content/uploads/2021/06/ENERTECH-UPS-CATALOGUE-2.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.