ES-TECH SUN-USR-S rack UPS: Specifications
ES-TECH International
A product page from South Korean manufacturer ES-TECH International describing the SUN-USR-S single-phase 19-inch rack UPS series for communication and network equipment in three capacities: 700 VA / 450 W, 1000 VA / 650 W and 2200 VA / 1430 W, with a typical switching time of 4 ms and efficiency above 95% at full load.
On this page
Overview
The page presents the SUN-USR-S series that ES-TECH International builds to supply stabilised power to indoor communication and network equipment. The product is designed for standard 19-inch racks and offers two outlets of 220 VAC true sine-wave output. The manufacturer stresses that repair and replacement can be carried out without dropping the load when the inverter's internal circuit fails or the battery is replaced. The page heading names the series SUN-USR-S and describes it as rack-mount 1 kVA class.
The specification table has three capacity columns. Input is single-phase (2 poles plus earth), 220 VAC ±20% at 50/60 Hz ±5%. Output is 220 VAC: 3.18 A / 450 W on the 700 VA model, 4.54 A / 650 W on the 1000 VA model and 10 A / 1430 W on the 2200 VA model. The ratio of active to apparent power is about 0.65 on all three. Crest factor is above 3:1, output frequency 50/60 Hz ±0.1 Hz and switching time typically 4 ms. Voltage regulation is ±10% in normal operation and ±3% on battery.
The operating principle is line-interactive: while the mains is normal an intelligent automatic voltage regulator (AVR) passes mains power with reduced noise and surge to the load, and when over- or undervoltage is detected the unit switches to inverter operation. Input frequency (50 or 60 Hz) is detected automatically and the output is synchronised. On the battery side the table lists 2 blocks of 12 V 7 Ah for 700 VA and 1000 VA and 3 blocks of 12 V 15 Ah for 2200 VA. Backup time is given as 5 minutes and recharge to above 90% as within 24 hours.
To extend battery life the battery end voltage is varied with load and full discharge at light load is prevented; battery condition is self-tested periodically. The chassis is 2U for 700 VA and 1000 VA and 3U for 2200 VA. Operating temperature is 0-40 °C, storage 0-50 °C, relative humidity 0-95% non-condensing, operating altitude up to 3 km and noise within 43 dB at 1 m. Serial data output (D-SUB 9-pin) is optional. The page gives no dimensions in millimetres and no weight.
Key points
- Capacities: 700 VA / 450 W (3.18 A), 1000 VA / 650 W (4.54 A), 2200 VA / 1430 W (10 A).
- Input: single phase, 220 VAC ±20%, 50/60 Hz ±5%; output 220 VAC true sine wave, 50/60 Hz ±0.1 Hz.
- Switching time typically 4 ms; crest factor above 3:1.
- Voltage regulation ±10% in normal operation, ±3% on battery.
- Efficiency above 95% at 100% load.
- Battery: 2 x 12 V 7 Ah at 700 VA and 1000 VA, 3 x 12 V 15 Ah at 2200 VA; backup time 5 minutes; recharge to above 90% within 24 hours.
- Chassis: 19-inch 2U for 700 VA and 1000 VA, 19-inch 3U for 2200 VA.
- Environment: operating 0-40 °C, storage 0-50 °C, 0-95% humidity non-condensing, altitude up to 3 km, noise within 43 dB at 1 m.
- The battery can be replaced without disconnecting output power.
Using it in design
- Compare the load against the W column, not VA: the 2200 VA model carries only 1430 W, which is the governing limit for current IT power supplies.
- Given the 4 ms typical switching time and ±10% normal-mode regulation, use the series for network access and communication equipment; choose a double-conversion (VFI) UPS for critical server load.
- Compare the 5-minute backup time with generator start time or controlled shutdown time, and confirm with the manufacturer the load at which it is stated.
- With recharge taking up to 24 hours, record in the operations plan that autonomy drops on repeated outages.
- Allow 2U or 3U in the rack plan and request depth and weight from the manufacturer; the page does not give them.
- Where remote monitoring is needed, add the optional serial data output to the order.
Who should read it
IT infrastructure engineers selecting a small UPS for network and communication racks and field teams operating edge nodes.
Document contents
- SUN-USR-S Series (Rack Mount 1KVA) introduction
- Features & Benefits
- Specifications: Input, Output, Efficiency, Battery, Connection, Dimension, Environment
Publication details
- Authors
- ES-TECH International
- Publisher
- ES-TECH International
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
ES-TECH International ES-TECH SUN-USR-S rack UPS: Specifications. ES-TECH International. https://es-tech.co.kr/eng_web/power_item02.php
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.