HanGang ALLi UPS single-phase technical specification and dimensions tables

HanGang Mechatronics

The ALLi UPS tables from South Korea's HanGang Mechatronics describe eleven single-phase double-conversion models from 1 kVA to 50 kVA (102C to 503C): 220 V input and output, input power factor of 0.98 or better, and uninterrupted bypass transfer within 4 ms.

On this page

Overview

The source consists of two tables published as images on HanGang Mechatronics' ALLi UPS product page: a technical specification table and a table of outer dimensions and weight. The series covers eleven single-phase models: 102C (1 kVA), 202C (2), 302C (3), 502C (5), 752C (7.5), 103C (10), 152C (15), 203C (20), 303C (30), 403C (40) and 503C (50 kVA). All models are on-line double-conversion units rated for 100% continuous duty.

Input and output are single-phase 220 V at 60 or 50 Hz. The input frequency range is ±5%, input power factor is 0.98 or higher and input voltage distortion is within 3%. Output voltage stability is within 2%, frequency stability within ±0.5 Hz and transient voltage deviation within ±5%, with recovery to the ±2% band within 20 ms. The output waveform is sinusoidal with THD of 3% or less at 100% linear load. Overload capability is 10 minutes at 120% and 1 minute at 150%.

Overall efficiency is given as a lower bound per power band: 80% or more for the 1-3 kVA models, 85% or more for 5-15 kVA and 88% or more for 20-50 kVA. Noise at 1 metre is 50 dB or less for 1-7.5 kVA, 55 dB or less for 10-20 kVA and 60 dB or less for 30-50 kVA. Synchronous bypass transfer is uninterrupted and completes within 4 ms; the transfer conditions are a fault, output overload and DC undervoltage.

The dimension table labels width, depth and height explicitly. The 102C measures 330 x 630 x 700 mm and weighs 60 kg, and the 503C measures 780 x 950 x 1630 mm and weighs 780 kg; weights exclude options. On the battery side the nominal DC voltages 36, 96, 192, 240 and 360 V are listed without assigning a voltage to each model, and autonomy and battery type are defined at order. The tables give no kW rating and no output power factor. Installation is indoor, 0-40 °C, up to 95% humidity and below 1000 m altitude.

Key points

  1. Eleven models: 102C, 202C, 302C, 502C, 752C, 103C, 152C, 203C, 303C, 403C, 503C; 1, 2, 3, 5, 7.5, 10, 15, 20, 30, 40 and 50 kVA.
  2. Input and output single-phase 220 V, 60 or 50 Hz; input power factor 0.98 or higher, input voltage distortion within 3%.
  3. Output voltage stability within 2%, THD 3% or less at 100% linear load; transient deviation ±5%, recovery within 20 ms.
  4. Overload: 10 minutes at 120%, 1 minute at 150%.
  5. Efficiency lower bounds: 80% for 1-3 kVA, 85% for 5-15 kVA, 88% for 20-50 kVA.
  6. Noise (1 m): 50 dB or less for 1-7.5 kVA, 55 dB for 10-20 kVA, 60 dB for 30-50 kVA.
  7. Synchronous bypass transfer is uninterrupted, within 4 ms.
  8. Dimensions (W x D x H): 102C 330 x 630 x 700 mm; 202C to 752C 330 x 630 x 840 mm; 103C and 152C 380 x 740 x 900 mm; 203C 550 x 700 x 1140 mm; 303C 650 x 780 x 1320 mm; 403C and 503C 780 x 950 x 1630 mm.
  9. Weights (options excluded): 60, 70, 75, 80, 95, 105, 120, 140, 520, 670 and 780 kg.
  10. Battery DC voltage options 36, 96, 192, 240, 360 V; transformerless or double-wound transformer construction.

Using it in design

  • The tables give no kW or output power factor, so match loads on kVA and obtain the active power rating from the manufacturer in writing.
  • Use the efficiency lower bounds for heat load: 88% on the 20-50 kVA models means losses of up to 12% at full load, which sets cooling capacity in small rooms.
  • From the 303C upward the weight rises to 520-780 kg, so check floor loading and the delivery route.
  • The tables do not map battery DC voltage to model, so settle the DC voltage in the order before designing the battery string.
  • A single-phase 220 V output draws high current on models above 20 kVA; size the output cable and distribution board accordingly.

Who should read it

Electrical designers selecting single-phase UPSs and teams cataloguing Korean UPS products.

Document contents

  1. MODEL / 용량(KVA)
  2. 입력
  3. 출력
  4. 동기절체
  5. 일반특성
  6. 축전지
  7. 외함크기(mm)
  8. 중량(kg, option 별도)

Publication details

Authors
HanGang Mechatronics
Publisher
HanGang Mechatronics
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

HanGang Mechatronics HanGang ALLi UPS single-phase technical specification and dimensions tables. HanGang Mechatronics. http://hangangups.com/wp-content/uploads/2023/01/alli_1.png

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.