LADIS LM30-210KVA modular UPS selection guide
Original title LADS Modular UPS Selection Guide LM30–210KVA, PDF p.1–2
LADIS
LADIS's LM series guide covers a 400 Vac three-phase, true double-conversion modular UPS built from 30 kW power modules, scaling from 30 kW to 210 kW with up to 96% efficiency and unity output power factor.
On this page
Overview
The two-page selection guide presents a seven-model modular UPS family from LM30K to LM210K. Each power module delivers 30 kW and the model number reflects 1 to 7 modules. The system is a true double-conversion on-line design with unity output power factor (kVA = kW), and the power module, the static transfer switch (STS) module and the battery module are replaceable separately, which the guide offers as a way to lower mean time to repair.
Input is 3 x 400 Vac (3Ph+N), 305-477 Vac at full load and 208-304 Vac below 70% load; frequency range 40-70 Hz, input power factor above 0.99 at full load and input THD below 3% at full load. Output is 3 x 400 Vac with typical steady-state regulation of +/-1% on balanced and +/-2% on unbalanced load, and +/-5% transient. Efficiency is 96% above 50% load and 95% above 25% load. Overload capability is 110% for 1 hour, 120% for 10 minutes and 150% for 1 minute.
On the battery side, nominal voltage is +/-216 V (36 x 12 V), maximum +/-240 V (40 pcs) and minimum +/-192 V (32 pcs), with 2.25 V/cell float, 2.35 V/cell boost and temperature compensation. Charging current is user-adjustable up to 8 A per power module. Cabinets come as 30U (medium) and 42U (full size); redundancy options run from 1+1, 2+1 and 3+1 up to N+1 in the long-backup cabinet.
One limit of the guide is that the capacity row in the table does not match the model suffix: it gives 40 kVA / 30 kW for LM30K and 250 kVA / 210 kW for LM210K. Module power also derates when ambient temperature rises above 30 C. Cabinet dimensions are listed per cabinet size; which cabinet fits which configuration is left to the user.
Key points
- Seven models: LM30K, 60K, 90K, 120K, 150K, 180K, 210K; 1-7 power modules of 30 kW each.
- The table's total capacity row runs from 40 kVA / 30 kW to 250 kVA / 210 kW and does not map one to one to the model suffix.
- Input 3 x 400 Vac, 40-70 Hz, power factor above 0.99 (full load), THDi below 3%.
- Efficiency: 96% above 50% load, 95% above 25% load.
- Overload: 110% for 1 hour, 120% for 10 minutes, 150% for 1 minute, 200 ms above 150%.
- Above 30 C module power derates: 27 kW at 31-35 C, 24 kW at 36-40 C.
- Battery 32-40 blocks of 12 V (+/-192 to +/-240 V); float 2.25 V/cell, boost 2.35 V/cell; adjustable charge current up to 8 A.
- Operating 0-40 C, up to 95% non-condensing humidity, below 1000 m for nominal power, IP20.
- Cabinets: 30U (1100 x 600 x 1485 mm) and 42U (1100 x 600 x 2030 mm, D x W x H).
- Standards: IEC/EN 60950-1, IEC/EN 62040-1, EMC to IEC/EN 62040-2 Category C3.
Using it in design
- Compare load power in kW with the capacity row; base capacity on power modules x 30 kW, not on the model suffix or the kVA value.
- For N+1 select one module more than the load kW needs and confirm the cabinet option offers that redundancy (for example the 30U cabinet has none at 3 modules).
- In rooms where ambient may exceed 30 C, run the capacity check with the derated module power of 27 kW and 24 kW.
- Select the battery string within 32-40 blocks and set charge current to the battery capacity.
- Enter cabinet dimensions (D x W x H) and the IP20 rating into the electrical room layout; request weight from the manufacturer.
Who should read it
Electrical designers and specifiers choosing modular UPS for mid-size data rooms and critical facilities.
Document contents
- LM Series Features
- Modular UPS Selection Guide (model, input, output, battery/charger, physical, environment, management, standards)
- System Cabinet Selection (complete system cabinet, long backup cabinet)
Publication details
- Authors
- LADIS
- Publisher
- LADIS
- Year
- Year not stated
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
LADIS LADS Modular UPS Selection Guide LM30–210KVA, PDF p.1–2. LADIS. http://www.ladis.com.cn/down/LADS%20Modular%20UPS%20LM30-210KVA%20Guide.pdf