LADIS LM30-210KVA modular UPS selection guide

Original title LADS Modular UPS Selection Guide LM30–210KVA, PDF p.1–2

LADIS

LADIS's LM series guide covers a 400 Vac three-phase, true double-conversion modular UPS built from 30 kW power modules, scaling from 30 kW to 210 kW with up to 96% efficiency and unity output power factor.

On this page

Overview

The two-page selection guide presents a seven-model modular UPS family from LM30K to LM210K. Each power module delivers 30 kW and the model number reflects 1 to 7 modules. The system is a true double-conversion on-line design with unity output power factor (kVA = kW), and the power module, the static transfer switch (STS) module and the battery module are replaceable separately, which the guide offers as a way to lower mean time to repair.

Input is 3 x 400 Vac (3Ph+N), 305-477 Vac at full load and 208-304 Vac below 70% load; frequency range 40-70 Hz, input power factor above 0.99 at full load and input THD below 3% at full load. Output is 3 x 400 Vac with typical steady-state regulation of +/-1% on balanced and +/-2% on unbalanced load, and +/-5% transient. Efficiency is 96% above 50% load and 95% above 25% load. Overload capability is 110% for 1 hour, 120% for 10 minutes and 150% for 1 minute.

On the battery side, nominal voltage is +/-216 V (36 x 12 V), maximum +/-240 V (40 pcs) and minimum +/-192 V (32 pcs), with 2.25 V/cell float, 2.35 V/cell boost and temperature compensation. Charging current is user-adjustable up to 8 A per power module. Cabinets come as 30U (medium) and 42U (full size); redundancy options run from 1+1, 2+1 and 3+1 up to N+1 in the long-backup cabinet.

One limit of the guide is that the capacity row in the table does not match the model suffix: it gives 40 kVA / 30 kW for LM30K and 250 kVA / 210 kW for LM210K. Module power also derates when ambient temperature rises above 30 C. Cabinet dimensions are listed per cabinet size; which cabinet fits which configuration is left to the user.

Key points

  1. Seven models: LM30K, 60K, 90K, 120K, 150K, 180K, 210K; 1-7 power modules of 30 kW each.
  2. The table's total capacity row runs from 40 kVA / 30 kW to 250 kVA / 210 kW and does not map one to one to the model suffix.
  3. Input 3 x 400 Vac, 40-70 Hz, power factor above 0.99 (full load), THDi below 3%.
  4. Efficiency: 96% above 50% load, 95% above 25% load.
  5. Overload: 110% for 1 hour, 120% for 10 minutes, 150% for 1 minute, 200 ms above 150%.
  6. Above 30 C module power derates: 27 kW at 31-35 C, 24 kW at 36-40 C.
  7. Battery 32-40 blocks of 12 V (+/-192 to +/-240 V); float 2.25 V/cell, boost 2.35 V/cell; adjustable charge current up to 8 A.
  8. Operating 0-40 C, up to 95% non-condensing humidity, below 1000 m for nominal power, IP20.
  9. Cabinets: 30U (1100 x 600 x 1485 mm) and 42U (1100 x 600 x 2030 mm, D x W x H).
  10. Standards: IEC/EN 60950-1, IEC/EN 62040-1, EMC to IEC/EN 62040-2 Category C3.

Using it in design

  • Compare load power in kW with the capacity row; base capacity on power modules x 30 kW, not on the model suffix or the kVA value.
  • For N+1 select one module more than the load kW needs and confirm the cabinet option offers that redundancy (for example the 30U cabinet has none at 3 modules).
  • In rooms where ambient may exceed 30 C, run the capacity check with the derated module power of 27 kW and 24 kW.
  • Select the battery string within 32-40 blocks and set charge current to the battery capacity.
  • Enter cabinet dimensions (D x W x H) and the IP20 rating into the electrical room layout; request weight from the manufacturer.

Who should read it

Electrical designers and specifiers choosing modular UPS for mid-size data rooms and critical facilities.

Document contents

  1. LM Series Features
  2. Modular UPS Selection Guide (model, input, output, battery/charger, physical, environment, management, standards)
  3. System Cabinet Selection (complete system cabinet, long backup cabinet)

Publication details

Authors
LADIS
Publisher
LADIS
Year
Year not stated
Document language
English
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

LADIS LADS Modular UPS Selection Guide LM30–210KVA, PDF p.1–2. LADIS. http://www.ladis.com.cn/down/LADS%20Modular%20UPS%20LM30-210KVA%20Guide.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.