Maruson Ultima RT Series UPS, 2203 brochure

Original title Maruson Ultima RT Series UPS, 2203, PDF p.1

Maruson

The Maruson Ultima RT series spans 1-3 kVA (100-120 V) and 6-10 kVA (200-240 V): true double-conversion, 0.9 output power factor, 2U/3U rack and tower UPS with 94-97% ECO efficiency and extended-runtime (L) models.

On this page

Overview

The 2022 brochure gives two data tables. The first covers the ULT-1K, 1.5K, 2K and 3K RT models for the 120 V market; the second covers the 6K and 10K models in 200-240 V versions. The whole series is true double-conversion on-line with pure sine output and 0.9 output power factor, with ECO and advanced ECO modes, programmable power-management outlets, EPO, a 50/60 Hz frequency converter mode and an optional external PDU / maintenance bypass switch. Applications are server rooms, office equipment, telecom and networking, and surveillance systems.

In the 1-3 kVA group nominal input and output voltage is selectable at 100/110/115/120 Vac, input range 55-150 Vac +/-5%, frequency 40-70 Hz and input power factor 0.99 or higher. Output THD is 2% or less on linear load and crest factor is at most 5:1. Line-to-battery transfer is zero and inverter-to-bypass is typically 4 ms. Efficiency is 87-89% in AC mode, 85-87% in battery mode and 94-97% in ECO mode. Standard models include 2, 4 and 6 batteries of 12 V 9 Ah, with 4 hours to 90% recharge and a 1 A charging current.

The L suffix in a model name marks the extended-runtime model. These models need external batteries and their capacity is the lower value printed in their own column, not the number in the name: for example ULT-1KLRT is 900 VA / 810 W, ULT-1.5KLRT 1250 VA / 1125 W, ULT-2KLRT 1700 VA / 1530 W and ULT-3KLRT 2500 VA / 2250 W. Charging current on these models is selectable at 1/2/4/8 A. The non-L models are 1000/900, 1500/1350, 2000/1800 and 3000/2700 VA/W.

In the 6K and 10K group input is 200/208/220/230/240 Vac, with a range of 176-300 Vac at full load and load derating of up to 50% between 110 and 175 Vac. Power is 6000 VA / 5400 W and 10000 VA / 9000 W, crest factor is 3:1 and transfers are zero. Efficiency is 91% in line mode (85% for RTD versions) and 96% in ECO mode (87% for RTD). The standard battery is 20 units (18-20 programmable) of 12 V 7 Ah (6K) or 9 Ah (10K), with 7 and 9 hours to 90% recharge; on the long-run model charging current is 4 A. N+X parallel redundancy for up to three units is optional. The 1-3K models are 2U (410-630 mm deep) and the 6K and 10K models are 3U (UPS 668 x 438 x 133 mm; weight 20 and 23.5 kg; battery bank 57 and 63 kg). The efficiency values state no load point.

Key points

  1. 120 V market: ULT-1K, 1.5K, 2K, 3K RT; capacity 1000/900, 1500/1350, 2000/1800, 3000/2700 VA/W.
  2. L models are extended-runtime with external batteries; capacity 900/810, 1250/1125, 1700/1530, 2500/2250 VA/W.
  3. 1-3K input 55-150 Vac +/-5%; output 100/110/115/120 Vac; crest factor 5:1.
  4. 1-3K efficiency: 87-89% in AC mode, 85-87% in battery mode, 94-97% in ECO mode.
  5. Transfer: line-to-battery zero; inverter-to-bypass typically 4 ms (1-3K), zero (6K, 10K).
  6. 6K/10K: 6000 VA / 5400 W and 10000 VA / 9000 W; input 176-300 Vac at full load; crest factor 3:1.
  7. 6K/10K efficiency: 91% in line mode, 96% in ECO mode (85% and 87% for RTD versions).
  8. 1-3K size 410, 510, 630 x 438 x 88 mm (2U); 6K/10K UPS 668 x 438 x 133 mm (3U).
  9. Net weight 8.6-28 kg for the 1-3K models; 6K/10K UPS 20 and 23.5 kg.
  10. N+X parallel redundancy up to three units (6K and 10K, optional).

Using it in design

  • For L models take capacity from the lower VA/W value in the table, not from the model name, and size the external battery bank separately.
  • Use the 120 V version only at 100-120 V sites; for 200-240 V sites look at the 6K or 10K group.
  • Efficiency is given without a load point, so ask the manufacturer for it for the heat-load calculation.
  • In rack layout plan space and weight (57-63 kg) for the 2U or 3U unit and the separate 3U battery bank.
  • Carry the lower efficiency of the RTD versions (85% and 87%) into heat and energy calculations.

Who should read it

Designers and IT managers selecting rack and tower UPS for server room, telecom and network applications.

Document contents

  1. Features and applications (1-3 kVA)
  2. Ultima RT on-line UPS specification (ULT-1K to 3KLRT)
  3. Features (6-10 kVA)
  4. Ultima RT on-line UPS specification (ULT-6K to 10KLRT)

Publication details

Authors
Maruson
Publisher
Maruson
Year
Year not stated
Document language
Unverified
Source type
Manufacturer
Access
Free to read
Licence
Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note

No document-specific redistribution permission was established. Bibliographic reference only.

Citation

Maruson Maruson Ultima RT Series UPS, 2203, PDF p.1. Maruson. https://marusonusa.com/pub/media/Brochure/LV/Ultima_RT_Series_UPS-2203.pdf

All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.

Power design in SoSo CAD

Calculate supply paths, equipment loads and UPS failure scenarios as part of the design.

Single-line diagram in the SoSo CAD power and capacity workspace

Keep your reading list current

Once a month: new library sources, changes to Turkish regulations and upcoming data centre events.