NOVA NPS1252 Series UPS product datasheet (015.TRF.022012)
Original title NOVA NPS1252 Series UPS, 015.TRF.022012, PDF p.2
NOVA Power Solutions
Datasheet for NOVA Power Solutions' NPS1252 series of rugged 2U online UPS: 1250 VA / 1000 W or 850 VA / 600 W, 80-265 V AC input, -18 to +50 °C operation and a hot-swappable battery pack.
On this page
Overview
The datasheet presents the NPS1252 series, designed for remote and mobile applications and for harsh physical and electrical environments. The series is a true online double-conversion design, 2U high, with nominal output of 850 VA or 1250 VA. The input range is 80-265 V AC and 47-400 Hz, with an optional 20-32 V DC input. Output is 115 V AC, 60 Hz; optional DC outputs are 24 V DC (250 W) or ±48 V DC (1000 W).
The design relies on a flow-through arrangement with air passing through a heat-sink tunnel, which cools while sealing components from moisture and airborne particles. The chassis is welded aluminium, gasket sealed with a filtered air intake, and operates in blown precipitation. Non-spillable, non-hazardous valve-regulated lead-acid batteries sit in a user-replaceable pack that can be hot swapped in the field. A cabling option supports an external battery module for extended run.
Electrical characteristics: input power factor typically 0.99, output voltage 115 V AC ± 5 percent, frequency 60 Hz ± 5 percent, true sine waveform, THD 1.5 percent with a 1000 W purely resistive load and continuous load crest factor 2.5. Continuous output power is 1250 VA / 1000 W or 850 VA / 600 W. Temperature limits are -18 to 50 °C operating and -32 to 66 °C storage; humidity is 10-95 percent (non-condensing) and operating altitude is 0-15,000 ft.
The batteries are four 12 V, 9 Ah VRLA units; typical runtime is 4 minutes at full load and recharge to 90 percent takes 4 hours. The document is an older datasheet with a 2012 revision; the part-number table lists the R, U, XR and U-XR variants of the 850 VA and 1250 VA family and a configuration with 48 V DC output. Although the cover reads 120 V AC, the part table gives 115 V AC nominal output.
Key points
- Capacity: 1250 VA / 1000 W or 850 VA / 600 W; 2U, true online double conversion.
- Input 80-265 V AC, 47-400 Hz; optional 20-32 V DC input; input power factor typically 0.99; 20 A input breaker.
- Output 115 V AC ± 5 percent, 60 Hz ± 5 percent, true sine; THD 1.5 percent (1000 W resistive); crest factor 2.5.
- Optional DC output: 24 V DC at 250 W or ±48 V DC at 1000 W.
- Operation -18 to +50 °C, storage -32 to +66 °C, humidity 10-95 percent, operating altitude 0-15,000 ft; operates in precipitation.
- Battery: four 12 V, 9 Ah VRLA, typically 4 minutes at full load; 90 percent recharge in 4 hours.
- Size 3.5 x 17 x 24 in (H x W x D), 66 lb including battery; aluminium chassis, flow-through forced-air cooling.
- Current: 850 VA models 9.4 A max input and 5.2 A nominal output; 1250 VA models 15.6 A and 8.7 A.
- Extended-run (XR) battery cabling option; slide-rail kits for 19-inch racks.
Using it in design
- In mobile, remote and field applications, treat the wide input range (80-265 V AC, 47-400 Hz) as an advantage for generators and unstable mains sources.
- Where runtime beyond the 4-minute internal figure is needed, plan the XR option and an external battery module.
- Write the field hot-swap of the battery pack into the maintenance procedure.
- Check that the 115 V AC / 60 Hz output suits the load side; it is not directly suitable for 50 Hz and 230 V loads.
- Because this is an older datasheet revision, confirm the current part number with the manufacturer before ordering.
Who should read it
Electrical and systems designers selecting small UPS units for mobile command posts and rugged remote systems.
Document contents
- Features
- Optional features
- Standard features
- Electrical specifications
- Environmental specifications
- Mechanical specifications
- Battery specifications
- Part number table
Publication details
- Authors
- NOVA Power Solutions
- Publisher
- NOVA Power Solutions
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
NOVA Power Solutions NOVA NPS1252 Series UPS, 015.TRF.022012, PDF p.2. NOVA Power Solutions. https://novapower.com/wp-content/uploads/2015/06/015-NPS1252.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.