S&C PureWave UPS System: Operation and Maintenance, Instruction Sheet 653-506
S&C Electric Company
Instruction Sheet 653-506 from S&C Electric Company, dated 9 October 2017, defines the operating states, bypass procedures, alarms and maintenance of the PureWave UPS System rated 250 kW to 2 MW (313 kVA to 2.5 MVA) at 208 to 600 V. On a utility disturbance the system moves the load to battery typically within 1 to 4 ms and carries it for one minute at full load.
On this page
Overview
PureWave is a large off-line system, not a continuously converting double-conversion UPS. In normal conditions the critical load is fed from the utility through the input circuit breaker, the power electronic switch (PES) and the output isolation breaker. A utility disturbance monitor (UDM) watches the supply voltage continuously. When it detects a disturbance the inverters start, battery energy reaches the load through a voltage-matching isolation transformer, and the PES is commanded open to separate the load from the faulted utility. The whole transfer typically takes 1 to 4 ms, less than a quarter cycle.
Stored energy is sized for short events: the system runs for one minute at full load, or up to three minutes at reduced power. The generator interface therefore decides how long outages are handled. An optional dry contact signals the transfer switch after the system has run for 5 seconds at full load, or 10 seconds at half load or less. Once the generator reaches rated voltage and frequency the load is soft-loaded onto it, the system returns to the Ready state, and it holds the transfer signal until the batteries have recharged. The system enters the Run state again while the load returns to the utility.
The state tables are the core of the sheet. Six primary states are defined: Ready, Run, Inhibit, Bypass, Bypass Isolate and Test in Bypass. In Inhibit the load is fed through the PES but the system cannot protect it. In Bypass the bypass breaker is closed while the input and output breakers stay closed. In Bypass Isolate the input and output breakers are open; maintenance is permitted only in that state and with the equipment de-energized. Five transition states (Reset, Force Off PES, Close Mechanical Bypass, Soft Transfer, Load Decelerate) are described separately.
Alarms fall into four types: Warning, Inhibit, Bypass and Bypass Isolate. With a Warning alarm the system stays in Ready and keeps protecting the load; in the other three the critical load is not protected against disturbances and the System Fault contact operates. Warnings are raised when the enclosure interior exceeds 40 °C or falls below 5 °C. Optional contacts include Low Battery, which operates once 50% of run time is used (at 30 seconds in a full-load run), and Load Overcurrent, which operates when load current exceeds 115% of the system's current rating.
The maintenance section provides quarterly and annual checklists with sign-off fields. Both require the system to be disabled, placed in Bypass Isolate and de-energized, and the work is reserved for S&C personnel or people trained by S&C. The quarterly check concentrates on the enclosure, door seals, hydrogen vents, air conditioners and air inlets and outlets. The annual check adds ground and connection tightness checks, dry cleaning of the transformer under lockout/tagout, and resistance measurement of the PES modules. Battery charging is automatic, with an equalize charge every two months.
Key points
- Product range is 250 kW to 2 MW (313 kVA to 2.5 MVA) at 208 to 600 V; each battery bay holds a 250 kW battery module and a power conversion module (PCM).
- In normal operation the load is fed from the utility through the PES; the inverters run only during a disturbance.
- Transfer typically completes in 1 to 4 ms (under a quarter cycle).
- Battery run time is one minute at full load, up to three minutes at reduced power.
- The generator transfer signal is issued after 5 seconds of running at full load, or 10 seconds at 50% load or less.
- In Bypass the input and output breakers remain closed; in Bypass Isolate both are open and the load is fed only through the bypass breaker.
- In Inhibit, Bypass and Bypass Isolate the critical load is not protected from utility disturbances; the System Fault contact reports it.
- Charging rule: two minutes of charge for each second of full-load discharge; the charger then stays on for one hour; an equalize charge runs every two months.
- Manual charging may be needed if the system is not commissioned within 60 days of shipment or sits in Bypass for more than 60 days.
- Up to 600 V DC and 15 kV AC are to be expected inside the enclosure in normal operation, and DC voltage is present even with the utility disconnected.
Using it in design
- Do not substitute this system for a battery-backed double-conversion UPS: autonomy is one minute at full load, so confirm the generator can accept the load within that minute after the 5 to 10 second signal delay.
- Check that downstream equipment rides through the 1 to 4 ms transfer (for example IT power-supply hold-up time).
- Show the input, output and bypass breakers separately on the single-line diagram, and require the Bypass Isolate state, not Bypass, for maintenance isolation.
- Wire the System Fault contact to the BMS/EPMS and classify Inhibit, Bypass and Bypass Isolate as a 'load unprotected' alarm.
- Size enclosure cooling and heating against the 5 °C and 40 °C alarm thresholds, and leave layout clearances that keep hydrogen vents and air inlets and outlets unobstructed.
- Put the quarterly and annual checklists in the maintenance plan, together with the manual-charge requirement after 60 days in bypass and the manufacturer-trained-personnel condition.
Who should read it
Electrical designers evaluating medium and large uninterruptible power systems, operations and maintenance engineers, and teams coordinating generators and transfer switches.
Document contents
- Introduction
- Safety Information
- Safety Precautions
- Shipping and Handling
- Components and Controls
- Operation: System Operation, Operating States, Transition States, Contacts, Remote Disable (Optional)
- Operating Modes and Procedures: Maintenance Bypass Procedure, Returning the PureWave UPS System to the Ready State, System Emergency Bypass Isolation Procedure, Battery Charging Modes, Generator Interface
- Alarms List and Troubleshooting Tips
- Monitoring
- Maintenance: Quarterly Maintenance, Annual Maintenance
Publication details
- Authors
- S&C Electric Company
- Publisher
- S&C Electric Company
- Year
- 2017
- Document number
- 653-506
- Document language
- English
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
S&C Electric Company (2017). S&C PureWave UPS System: Operation and Maintenance, Instruction Sheet 653-506. S&C Electric Company. 653-506. https://www.sandc.com/globalassets/sac-electric/documents/public---documents/sales-manual-library---external-view/instruction-sheet-653-506.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.
