Servotech Online UPS Catalogue: ST900 PRO 1-3 kVA (p.3)
Original title Servotech Online UPS catalogue, ST900 PRO, PDF p.3
Servotech
Servotech ST900 PRO is a 1, 2 and 3 kVA single-phase high-frequency online UPS: 0.8 output power factor, 95-97 percent ECO efficiency, 0 ms mains-to-battery transfer, IP 21.
On this page
Overview
The document is a 2022 online UPS catalogue from India's Servotech; the section examined is the feature page and model table of the ST900 PRO. The model comes in 1, 2 and 3 kVA with a 0.8 output power factor. Features: high-frequency online double conversion, DSP control, active PFC with input power factor up to 0.99, a wide 110 to 300 Vac input range, a 40 to 70 Hz frequency range, cold start, advanced battery management, linear derating at low input voltage and 50/60 Hz frequency conversion.
Technical table: nominal input is 208/220/230/240 Vac; the input range is 110 to 280 V at 50 percent load and below and 170 to 280 V at 100 percent load; input power factor is 0.99 or above; THDi is below 6 percent; the bypass range is -25/+15 percent (settable). Output voltage is settable from the LCD with ±1 percent regulation, THDv below 2 percent on linear and 5 percent on non-linear load and a 3:1 crest factor. Overload is 1 minute at 105-125 percent, 30 seconds at 125-150 percent and 300 ms above 150 percent. Efficiency in mains mode is above 90, 91 and 92 percent for 1, 2 and 3 kVA, and above 95, 96 and 97 percent in ECO mode.
Transfer time is 0 ms from mains to battery mode and typically 4 ms from inverter to bypass. The standard model restores 90 percent of capacity in 3 hours; for the long-time model it depends on battery capacity. Operation: IP 21, noise below 40 dB at 1 m, altitude below 1000 m (1 percent derating per additional 100 m). Capacity derates to 70 percent in CUCF mode and to 90 percent when the output voltage is set to 208 Vac. Because the table puts standard (S) and long-time (H) model subvariants together, no specific battery and size configuration can be picked from this summary; the kW rating is not given separately in the document.
The catalogue also introduces the ST900 G4 models (5-10 kVA and 10-20 kVA) in the same family; these are outside the scope of this summary.
Key points
- ST900 PRO: 1, 2 and 3 kVA, output power factor 0.8, single phase.
- Input range: 110 to 280 V at 50 percent load and below, 170 to 280 V at 100 percent load; frequency 40 to 70 Hz.
- Input power factor 0.99 or above, THDi below 6 percent.
- Output ±1 percent, THDv below 2 percent (linear) and 5 percent (non-linear), crest factor 3:1.
- Efficiency above 90/91/92 percent in mains mode and above 95/96/97 percent in ECO mode (1/2/3 kVA).
- Overload: 1 min at 105-125 percent, 30 s at 125-150 percent, 300 ms above 150 percent.
- Transfer is 0 ms from mains to battery mode and typically 4 ms from inverter to bypass.
- Capacity derates to 70 percent in CUCF mode and 90 percent at 208 Vac output; IP 21, noise below 40 dB.
Using it in design
- With a 0.8 output power factor, do not equate kW with kVA; check the load in kW.
- Input voltage is load-dependent (110 V at 50 percent load, 170 V at 100 percent); compare battery use on a weak supply with this window.
- If CUCF (frequency conversion) or 208 V output is used, apply the capacity derating (70 and 90 percent) to the load list.
- Settle battery and size from the standard and long-time subvariants with the manufacturer.
- Weigh the 95-97 percent ECO-mode efficiency against the 4 ms bypass transfer and load tolerance.
Who should read it
Designers selecting single-phase UPS for small offices and edge sites, and teams preparing catalogue data.
Document contents
- About Servotech
- ST900 PRO 1-3 kVA: features and options
- ST900 PRO: specifications
- ST900 G4 5-10 kVA
- ST900 G4 10-20 kVA
Publication details
- Authors
- Servotech
- Publisher
- Servotech
- Year
- Year not stated
- Document language
- Unverified
- Source type
- Manufacturer
- Access
- Free to read
- Licence
- Copyright retained; citation only: the publisher’s terms apply to the original document
Original licence note
No document-specific redistribution permission was established. Bibliographic reference only.
Citation
Servotech Servotech Online UPS catalogue, ST900 PRO, PDF p.3. Servotech. https://www.servotech.in/blog/wp-content/uploads/2022/12/Servotech-Online-UPS-Catalog.pdf
All content and rights belong to the respective authors and publishers. SoSo CAD provides only the citation, its own summary and a link to the source, and is not responsible for the sources' content.